Permit Application Status

PRRES20200481


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20200481
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - COVERED DECK - SUSPENDED SLAB STOP WORK ORDER generated on 04/29/2020 12:00 AM by username 'Mark Harding'. Order lifted bases on email and discution.MARK HARDING 05/04/2020 12:21 PM STOP WORK ORDER removed on 05/04/2020 12:00 AM by username 'Mark Harding'.
02/26/2020
03/18/2020
01/06/2021
Locations
Contacts
NEW MARK HOMES - KC LLC, Address:5207 NW CROOKED ROAD, Phone:(816) 969-9010  
ASHLEY@NEWMARKHOMESKC.COM  
HARRINGTON BROTHERS HEATING & COOLING, Address:15630 S KEELER ST, Phone:(913) 422-5444  
CLASS ONE ELECTRIC INC, Address:PO BOX 24343, Phone:(913) 915-1767  
R & R PLUMBING INC, Address:2001 GASLIGHT DR, Phone:(816) 772-5431  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 02/28/2020 03/17/2020
Dylan Eppert
North arrow and scale
Corrective Action Required
02/27/2020

The plot plan must be submitted on either (1) 81/2” x 11”, (2) 81/2”x 14”, or (3) 11” x 17” paper. All information on the plot plan must be drawn to scale. Scale must be 1” = 10’, 20’, or 30’; smaller scales that are multiples of the preceding scales may be used if necessary to represent large sites. All information on the plot plan must be clearly legible.) PLOT PLAN DOES NOT SCALE OUT.
Deck location
Corrective Action Required
02/27/2020

Deck location, with dimensions to property lines must be provided on the plot plan.
Right-of-way
Corrective Action Required
02/27/2020

The right-of-way with dimensions must be provided on the plot plan. SHOULD BE A 50' R/W
Spot elevations
Corrective Action Required
02/27/2020

Spot elevations and/or drainage flow arrows shall be provided throughout the lot. ONCE I RECEIVE SCALE PLOT PLAN I CAN CHECK GRADING.
Basement egress
Corrective Action Required
02/27/2020

Basement egress location(s) and elevation of the lowest adjacent grade must be provided on the plot plan.
Residential Plan Review Approved 02/28/2020 03/13/2020
Dylan Eppert
37 Provide details for any walls over 10 feet in height.
Corrective Action Required
02/27/2020

Provide details for any walls over 10 feet in height. Include stud grade, size, spacing and actual, uninterrupted height. (IRC Section 602.3.1 and Table 602.3(5) & 602.3.1)
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,234.04 $1,234.04 Paid 03/18/2020
8331507-Sewer Connection Fee $450.00 $450.00 Paid 03/18/2020
8331401-Water Tap Fee $3,477.00 $3,477.00 Paid 03/18/2020
8350015-Water Meter Fee $425.02 $425.02 Paid 03/18/2020
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 03/18/2020
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 03/18/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Miscellaneous Inspection Failed - Stop Work 04/29/2020
Misc
Corrective Action Required
04/29/2020
-no footing inspection on file, foundation poured. - no address posted - no erosion control stop construction issued.
Erosion Control Inspection Residential Partial 5/4/2020 05/04/2020
Misc
Corrective Action Required
05/04/2020
install erosion control on the back side of the lot asap. front and gravel intrance installed.
Footing Inspection - Residential Passed 5/4/2020 05/04/2020
Misc
Informational
05/04/2020
ENGINEER LETTER SUBMITTED - LETTER FROM BUILDER SUBMITTED. OK TO PROCEED.
Sewer Service Inspection - R Passed 5/6/2020 (1:00) 5/6/2020 05/06/2020
Water Service Inspection - R Passed 5/8/2020 5/8/2020 at 1:27 PM 05/08/2020
Underslab Plumbing Inspection - Residential Passed 5/15/2020 5/15/2020 05/15/2020
All Rough Inspection - Residential Partial 7/8/2020 7/8/2020 07/08/2020
Miscellaneous Correction
Informational
07/08/2020
-PORTAL FRAMING; NAIL PATTERN,AND STRAPS COMPLETE
All Rough Inspection - Residential Partial 7/24/2020 7/24/2020 07/24/2020
Miscellaneous Correction
Informational
07/08/2020
-PORTAL FRAMING; NAIL PATTERN,AND STRAPS COMPLETE - (2) 24X36 PIERS FOR DECK
Electrical Service Inspection Passed 9/3/2020 9/3/2020 09/03/2020
Gas Service Inspection - Residential Failed 9/3/2020 9/3/2020 09/03/2020
Miscellaneous Correction
Corrective Action Required
09/03/2020
-NO PRESSURE ON GAUGE, MISSING PLUG
All Rough Inspection - Residential Failed 9/3/2020 9/3/2020 09/03/2020
Miscellaneous Correction
Informational
07/24/2020
-PORTAL FRAMING; NAIL PATTERN,AND STRAPS COMPLETE - (2) 24X36 PIERS FOR DECK
Miscellaneous Correction
Corrective Action Required
09/03/2020
-TIGHTEN ANCHOR BOLTS IN GARAGE -NAIL RAFTERS TO JOISTS PER CODE -NAIL ALL CORNER STUDS AND INTERSECTION WALLS PER CODE -SEAL PENETRATION IN BOTTOM PLATE NEAR GARAGE ENTRY -FIREBLOCK FIREPLACE/ BEDROOM WALL AND SOFFIT TO PREVENT HORIZONTAL FIRE SPREAD -STRAP ALL VERTICAL DWV 2” AND SMALLER AT MIDPOINT PER CODE -COMPLETE PLUMBING THROUGHOUT -CORRECT BEARING STUD OVER NOTCHED AT LVL IN GREAT ROOM/ BATH BY STAIRS -PROVIDE PROTECTION PLATES AND COMPLETE DWV VENT IN BED 2 CLOSET -MISSING (4) 2X4 BEARING AT LVL BY STAIRS -MISSING (2) 2X6 AT FIREPLACE -MISSING (2) 2X4 AT MASTER SHOWER -FIREBLOCK DEAD SPACE BETWEEN MASTER BATH AND SECOND BATH -TIGHTEN ANCHOR BOLTS IN BASEMENT -ADD ANCHOR BOLTS WITHIN 12” OF PLATE BREAK IN BASEMENT EAST WALL -ADD (2) ANCHOR BOLTS IN PLATE ON WEST WALL -STRAP TOP PLATE ON WEST BASEMENT WALL WHERE PLATE OVERLAP LESS THAN 24” -MISSING PLUG IN GAS LINE BY FURNACE -NO PRESSURE ON GAS LINE -MISSING (2) 2X6 IN NW CORNER BASEMENT -MISSING (4) 2X6 AT NORTH WALL BY WINDOW
All Rough Inspection - Residential Failed 9/11/2020 9/11/2020 09/11/2020
Miscellaneous Correction
Informational
09/03/2020
-PORTAL FRAMING; NAIL PATTERN,AND STRAPS COMPLETE - (2) 24X36 PIERS FOR DECK
Miscellaneous Correction
Corrective Action Required
09/03/2020
**DO NOT INSULATE** -SEAL PENETRATION IN BOTTOM PLATE NEAR GARAGE ENTRY-MUD ROOM -COMPLETE PLUMBING MASTER BATH TRAP -SEAL GAP IS N FIREBLOCK AT DEAD SPACE BETWEEN MASTER BATH AND SECOND BATH --BOND GAS LINE
Gas Piping Inspection - Residential Failed 9/11/2020 9/11/2020 09/11/2020
Miscellaneous Correction
Corrective Action Required
09/11/2020
-BOND GAS LINE
All Rough Inspection - Residential Failed 9/15/2020 9/15/2020 09/15/2020
Miscellaneous Correction
Informational
09/11/2020
-PORTAL FRAMING; NAIL PATTERN,AND STRAPS COMPLETE - (2) 24X36 PIERS FOR DECK
Miscellaneous Correction
Corrective Action Required
09/11/2020
--BOND GAS LINE -DECK FRAMING INCOMPLETE
All Rough Inspection - Residential Passed 09/21/2020
Miscellaneous Correction
Informational
09/15/2020
-PORTAL FRAMING; NAIL PATTERN,AND STRAPS COMPLETE - (2) 24X36 PIERS FOR DECK
Miscellaneous Correction
Resolved
09/21/2020
--BOND GAS LINE
Erosion Control Inspection Residential Failed 09/29/2020
Misc
Partial Correction
10/09/2020
-erosion control requires continuous maintenance. Please repair damaged sections -Remove debris from curb/gutter immediately
Gas Service Inspection - Residential Passed 10/21/2020 10/21/2020 10/20/2020
Miscellaneous Correction
Resolved
10/20/2020
-NO PRESSURE ON GAUGE, MISSING PLUG
Gas Piping Inspection - Residential Passed 10/20/2020
Miscellaneous Correction
Resolved
10/20/2020
-BOND GAS LINE
Occupancy Inspection - Codes Residential Failed 11/23/2020 11/23/2020 11/23/2020
Misc
Corrective Action Required
11/23/2020
-No driveway or sidewalk inspections on record, contact Development Services to resolve this issue -Provide building address. Minimum 4 inch high, half-inch stroke, on contrasting background and in illuminated area -Remove debris from street curb/gutter and sidewalk immediately. No further inspections until completed -Final grade and sod per approved plot -Provide exterior and garage/dwelling door hardware -Provide gutters and downspouts -Downspout and sump piping to discharge minimum 36 inches from foundation -Provide exterior HVAC equipment with properly sized breaker -Remove screen from dryer vent termination -Complete electrical installation. Floor outlet boxes. Boxes must also be flush with combustible services -Complete interior guard rail at stairs to basement -Ensure all electrical outlet plate covers are installed -Complete plumbing installation, master shower & garage sink -Air gap dishwasher discharge piping -Garage/dwelling separation door required to self close and self latch -Trim garage attic access and ensure tight fitting installation -Provide water heater temperature and pressure relief discharge piping -Connect water heater to gas piping per manufacturers installation instructions -Complete water heater gas vent termination per manufacturers installation instructions -Remove trash and construction debris
Deck Final Inspection - Residential Passed 11/23/2020
Driveway Inspection Passed 11/6/2020 11/6/2020 12/02/2020
Misc
Informational
12/02/2020
On Wednesday, 12-02-2020. I performed a sidewalk inspection and passed the grade and forming to pour the sidewalk.
Occupancy Inspection - Codes Residential Failed 12/3/2020 12/3/2020 12/03/2020
Misc
Corrective Action Required
11/23/2020
-No driveway or sidewalk inspections on record, contact Development Services to resolve this issue -Provide building address. Minimum 4 inch high, half-inch stroke, on contrasting background and in illuminated area -Remove debris from street curb/gutter and sidewalk immediately. No further inspections until completed -Final grade and sod per approved plot -Provide exterior and garage/dwelling door hardware -Provide gutters and downspouts -Downspout and sump piping to discharge minimum 36 inches from foundation -Provide exterior HVAC equipment with properly sized breaker -Remove screen from dryer vent termination -Complete electrical installation. Floor outlet boxes. Boxes must also be flush with combustible services -Complete interior guard rail at stairs to basement -Ensure all electrical outlet plate covers are installed -Complete plumbing installation, master shower & garage sink -Air gap dishwasher discharge piping -Garage/dwelling separation door required to self close and self latch -Trim garage attic access and ensure tight fitting installation -Provide water heater temperature and pressure relief discharge piping -Connect water heater to gas piping per manufacturers installation instructions -Complete water heater gas vent termination per manufacturers installation instructions -Remove trash and construction debris
Misc
Corrective Action Required
12/03/2020
Inspection denied for non compliance with inspection report from 11/23/2020 item #3, “Remove debris from street curb/gutter and sidewalk immediately. No further inspections until complete”
Occupancy Inspection - Codes Residential Temporary C of O 12/7/2020 12/7/2020 12/07/2020
Misc
Corrective Action Required
12/03/2020
-No sidewalk inspection on record, contact Development Services to resolve this issue -Final grade and sod per approved plot -Downspout and sump piping to discharge minimum 36 inches from foundation TCO VALID THROUGH 1/7/2021
Misc
Resolved
12/07/2020
Inspection denied for non compliance with inspection report from 11/23/2020 item #3, “Remove debris from street curb/gutter and sidewalk immediately. No further inspections until complete”
Plot Plan Inspection Passed 01/05/2021
Occupancy Inspection - Codes Residential Temporary C of O 1/5/2021 1/5/2021 01/05/2021
Misc
Corrective Action Required
12/07/2020
-No sidewalk inspection on record, contact Development Services to resolve this issue 10 day TCO extension granted TCO VALID THROUGH 1/17/2021
Sidewalk Inspection Passed 12/2/2020 12/2/2020 01/05/2021
Misc
Informational
01/05/2021
On Tuesday, 1-05-2021. A visual inspection was conducted and found City sidewalk was completed and passes inspection.
Occupancy Inspection - Codes Residential Full C of O 1/6/2021 1/6/2021 01/06/2021
Misc
Resolved
01/06/2021
-No sidewalk inspection on record, contact Development Services to resolve this issue 10 day TCO extension granted TCO VALID THROUGH 1/17/2021
Documents & Images
Date Uploaded File Type Document Name
02/27/2020 Letter Codes Residential Plan Review
03/18/2020 Receipt Receipt for transaction: 2020-001206
03/18/2020 Letter DS Building Permit
03/18/2020 Plot Plan DOC031820-001
04/29/2020 Letter Stop Work Order
04/29/2020 1912 SW River Run Dr_FTG INSP_2020-04-02
05/04/2020 Letter INSPECTION SUMMARY
05/04/2020 Letter INSPECTION SUMMARY
05/06/2020 Letter INSPECTION SUMMARY
05/08/2020 Letter INSPECTION SUMMARY
05/15/2020 Letter INSPECTION SUMMARY
05/15/2020 Letter INSPECTION SUMMARY
07/08/2020 Letter INSPECTION SUMMARY
07/24/2020 Letter INSPECTION SUMMARY
09/03/2020 Letter INSPECTION SUMMARY
09/03/2020 Letter INSPECTION SUMMARY
09/03/2020 Letter INSPECTION SUMMARY
09/11/2020 Letter INSPECTION SUMMARY
09/11/2020 Letter INSPECTION SUMMARY
09/15/2020 Letter INSPECTION SUMMARY
09/15/2020 Letter INSPECTION SUMMARY
09/21/2020 Letter INSPECTION SUMMARY
09/29/2020 Letter INSPECTION SUMMARY
10/09/2020 Letter INSPECTION SUMMARY
10/20/2020 Letter INSPECTION SUMMARY
10/20/2020 Letter INSPECTION SUMMARY
10/20/2020 Letter INSPECTION SUMMARY
11/23/2020 Letter INSPECTION SUMMARY
11/23/2020 Letter INSPECTION SUMMARY
12/03/2020 Letter INSPECTION SUMMARY
12/03/2020 Letter INSPECTION SUMMARY
12/07/2020 Letter Codes Temporary Certificate of Occupancy
01/05/2021 Letter INSPECTION SUMMARY
01/05/2021 Letter Codes Temporary Certificate of Occupancy
01/05/2021 Letter INSPECTION SUMMARY
01/06/2021 Letter Codes Final Certificate of Occupancy
01/06/2021 Letter INSPECTION SUMMARY
01/11/2021 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home