Summary
PRRES20193546
Building Permit - Residential
Certificate of Occupancy
CMH PARKS INC
NEW SINGLE FAMILY
NEW SINGLE FAMILY PARTIALLY FINISHED BASEMENT STOP WORK ORDER generated on 06/15/2020 12:00 AM by username 'Patrick Schonfeldt'. STOP WORK ORDER removed on 06/23/2020 12:00 AM by username 'Mark Harding'.
12/06/2019
12/11/2019
11/09/2020
Locations
Contacts
CMH PARKS INC, Address:5000 CLAYTON RD  
CLAYTON PROPERTIES GROUP, INC, Address:10450 Holmes Rd Suite 100, Phone:(816) 246-6700  
PERMITTING@SUMMITHOMESKC.COM  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 12/10/2019 12/10/2019
Steve Conrick
Residential Plan Review Approved 12/10/2019 12/10/2019
Steve Conrick
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $814.71 $814.71 Paid 12/11/2019
Right of Way Permit Fee $80.00 $80.00 Paid 12/11/2019
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 12/11/2019
8331507-Sewer Connection Fee $390.00 $390.00 Paid 12/11/2019
Water Tap Fee $3,477.00 $3,477.00 Paid 12/11/2019
Water Meter Fee $425.02 $425.02 Paid 12/11/2019
3rd and Subsequent Inspection Fee (Per Hour) $50.00 $50.00 Paid 06/18/2020
3rd and Subsequent Inspection Fee (Per Hour) $50.00 $50.00 Paid 06/18/2020
3rd and Subsequent Inspection Fee (Per Hour) $50.00 $50.00 Paid 06/18/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 1/7/2020 (3:15) 1/7/2020 01/07/2020
Misc
Corrective Action Required
01/07/2020
Staple plans together on future inspections Post site address Ok to pour
Underslab Plumbing Inspection - Residential Passed 2/21/2020 2/21/2020 02/21/2020
Sewer Service Inspection - R Passed 3/4/2020 3/4/2020 03/04/2020
Water Service Inspection - R Passed 3/5/2020 (10:30) 3/5/2020 03/05/2020
Piers/Caissons Inspection - Residential Failed 4/24/2020 (9:00) 4/24/2020 at 9:40 AM 04/24/2020
Misc
Corrective Action Required
04/24/2020
- PROVIDE (4) # 4 VERT BARS PER PLAN - (1) 24 X 36 (1) 24 x 48
Piers/Caissons Inspection - Residential Failed 5/8/2020 5/8/2020 05/08/2020
Misc
Corrective Action Required
04/24/2020
- PROVIDE (4) # 4 VERT BARS PER PLAN - (1) 24 X 36 (1) 24 x 48
Misc
Corrective Action Required
05/08/2020
REMOVE MUD AND WATER FROM EAST PIER (1) 36 X 53 (1) FULL OF MUD & WATER
Piers/Caissons Inspection - Residential Passed 5/11/2020 (11:00) 5/11/2020 05/11/2020
Misc
Resolved
05/11/2020
- PROVIDE (4) # 4 VERT BARS PER PLAN - (1) 24 X 36 (1) 24 x 48
Misc
Resolved
05/11/2020
REMOVE MUD AND WATER FROM EAST PIER (1) 36 X 53 (1) 30 X 36 W/ (4) # 4 VERT BARS EACH ON SITE
Gas Piping Inspection - Residential Passed 6/1/2020 6/1/2020 06/01/2020
Electrical Service Inspection Failed 6/1/2020 6/1/2020 06/01/2020
Misc
Corrective Action Required
06/01/2020
- Color code ufer ground
Gas Service Inspection - Residential Failed 6/1/2020 6/1/2020 06/01/2020
Misc
Corrective Action Required
06/01/2020
- Gas pressure at 5 psi, minimum 10 psi hold for 15 minutes
All Rough Inspection - Residential Failed 6/1/2020 6/1/2020 06/01/2020
Misc
Corrective Action Required
06/01/2020
- Seal all penetrations at top and bottom plates, penetrations for plumbing and electrical through floor - address stud with termite damage in garage - Tighten all anchor bolts in garage - PFH garage per plans - EC#2 hold downs per plans - Protect and secure pex at showers - Seal around gaps of Fireblock, NM electrical, and DWV at chase next to master shower - Protect and secure pex at laundry - Nail corner and framing intersections per code and plans - Fireblock all tub and shower traps - Truss bracing and hangers per plans - Fireblock above fireplace - Color code ufer ground - Fireblock between stud and foundation wall vertical every 10’ per code in finished basement - Fireblock gap at horizontal between top plate and foundation in finished basement per code - Install and secure pex through master bath floor and seal penetrations - Protection plates at DWV basement
All Rough Inspection - Residential Failed - Stop Work 6/15/2020 6/15/2020 06/15/2020
Misc
Corrective Action Required
06/01/2020
6/15/20 - NO INSPECTION PERFORMED, STOP WORK ISSUED, HOUSE HAS BEEN INSULATED AND SHEETROCK HAS BEEN INSTALLED WITHOUT APPROVAL. REMOVE ALL SHEETROCK AND INSULATION FOR INSPECTION. - Seal all penetrations at top and bottom plates, penetrations for plumbing and electrical through floor - address stud with termite damage in garage - Tighten all anchor bolts in garage - PFH garage per plans - EC#2 hold downs per plans - Protect and secure pex at showers - Seal around gaps of Fireblock, NM electrical, and DWV at chase next to master shower - Protect and secure pex at laundry - Nail corner and framing intersections per code and plans - Fireblock all tub and shower traps - Truss bracing and hangers per plans - Fireblock above fireplace - Color code ufer ground - Fireblock between stud and foundation wall vertical every 10’ per code in finished basement - Fireblock gap at horizontal between top plate and foundation in finished basement per code - Install and secure pex through master bath floor and seal penetrations - Protection plates at DWV basement
All Rough Inspection - Residential Failed - Stop Work 6/17/2020 06/17/2020
Misc
Corrective Action Required
06/15/2020
6/15/20 - NO INSPECTION PERFORMED, STOP WORK ISSUED, HOUSE HAS BEEN INSULATED AND SHEETROCK HAS BEEN INSTALLED WITHOUT APPROVAL. REMOVE ALL SHEETROCK AND INSULATION FOR INSPECTION. - Seal all penetrations at top and bottom plates, penetrations for plumbing and electrical through floor - Protect and secure pex at showers - Nail corner and framing intersections per code and plans - Truss bracing and hangers per plans - Fireblock between stud and foundation wall vertical every 10’ per code in finished basement - Fireblock gap at horizontal between top plate and foundation in finished basement per code -REAR WALL OF BASEMENT WE CANT SEE.
Misc
Corrective Action Required
06/17/2020
Fee due- REMOVE AL SHEETROCK FROM CEILINGS FOR INSPECTION. CONTACT MARK HARDING FOR RE-INSPECTION
All Rough Inspection - Residential Failed 6/23/2020 06/23/2020
Misc
Resolved
06/23/2020
6/15/20 - NO INSPECTION PERFORMED, STOP WORK ISSUED, HOUSE HAS BEEN INSULATED AND SHEETROCK HAS BEEN INSTALLED WITHOUT APPROVAL. REMOVE ALL SHEETROCK AND INSULATION FOR INSPECTION. - Seal all penetrations at top and bottom plates, penetrations for plumbing and electrical through floor - Protect and secure pex at showers - Nail corner and framing intersections per code and plans - Truss bracing and hangers per plans - Fireblock between stud and foundation wall vertical every 10’ per code in finished basement - Fireblock gap at horizontal between top plate and foundation in finished basement per code -REAR WALL OF BASEMENT WE CANT SEE.
Misc
Resolved
06/23/2020
Fee due- REMOVE AL SHEETROCK FROM CEILINGS FOR INSPECTION. CONTACT MARK HARDING FOR RE-INSPECTION
Misc
Corrective Action Required
06/23/2020
- Nail all double trusses per plans
All Rough Inspection - Residential Passed 6/24/2020 6/24/2020 06/24/2020
Misc
Resolved
06/24/2020
Driveway Inspection Passed 7/2/2020 (Ready Now) 7/2/2020 07/02/2020
Misc
Informational
07/02/2020
On Thursday, July 2, 2020. A driveway and sidewalk inspection was performed. Found subgrade and forms ready for concrete. Inspection passed!
Gas Service Inspection - Residential Failed 8/13/2020 8/13/2020 08/13/2020
Misc
Corrective Action Required
06/01/2020
- Gas pressure at 5 psi, minimum 10 psi hold for 15 minutes - 8/13 no gauge present for pressure test
Electrical Service Inspection Passed 8/13/2020 8/13/2020 08/13/2020
Misc
Resolved
08/13/2020
Gas Service Inspection - Residential Passed 8/20/2020 8/20/2020 08/20/2020
Misc
Resolved
08/20/2020
Occupancy Inspection - Codes Residential Failed 9/16/2020 9/16/2020 09/16/2020
Misc
Corrective Action Required
09/16/2020
- GFCI protection required at laundry receptacle - Adjust garage door to allow latching - Size rock used for attic access door to fit properly for opening - Handrail required at basement stairs - Living room floor receptacle to be flush with surface, no setback allowed with combustible surface - Basement stairs - 1/2 gypsum required at under side of stairs for protection R302.7 - Complete final grade and sod - Splash blocks at all downspout and sump pump discharge locations, minimum distance 36” from foundation - Final Sidewalk Inspection
Occupancy Inspection - Codes Residential Failed 9/25/2020 9/25/2020 09/25/2020
Misc
Corrective Action Required
09/16/2020
- Adjust garage door to allow latching - Living room floor receptacle to be flush with surface, no setback allowed with combustible surface - Complete final grade and sod - Splash blocks at all downspout and sump pump discharge locations, minimum distance 36” from foundation - Final Sidewalk Inspection
Sidewalk Inspection Passed 7/2/2020 (Ready Now) 9/29/2020 09/29/2020
Misc
Informational
09/28/2020
On July, 2 2020 and sidewalk inspection was performed and passed inspection.
Misc
Informational
09/28/2020
On July, 2 2020 and sidewalk inspection was performed and passed inspection.
Occupancy Inspection - Codes Residential Failed 10/7/2020 10/7/2020 10/07/2020
Misc
Corrective Action Required
09/25/2020
- Living room floor receptacle to be flush with surface, no setback allowed with combustible surface - Complete final grade and sod
Occupancy Inspection - Codes Residential Temporary C of O 10/9/2020 10/9/2020 10/09/2020
Misc
Corrective Action Required
10/07/2020
- Complete final grade and sod OK FOR TCO
Plot Plan Inspection Passed 11/09/2020
Occupancy Inspection - Codes Residential Full C of O 11/9/2020 11/9/2020 11/09/2020
Misc
Resolved
11/09/2020
Documents & Images
Date Uploaded File Type Document Name
12/11/2019 Receipt Receipt for transaction: 2019-007683
12/11/2019 Letter DS Building Permit
12/12/2019 Plot Plan DOC121219-12122019095412
01/07/2020 Letter INSPECTION SUMMARY
02/21/2020 Letter INSPECTION SUMMARY
03/04/2020 Letter INSPECTION SUMMARY
03/05/2020 Letter INSPECTION SUMMARY
04/24/2020 Letter INSPECTION SUMMARY
05/08/2020 Letter INSPECTION SUMMARY
05/11/2020 Letter INSPECTION SUMMARY
06/01/2020 Letter INSPECTION SUMMARY
06/01/2020 Letter INSPECTION SUMMARY
06/01/2020 Letter INSPECTION SUMMARY
06/01/2020 Letter INSPECTION SUMMARY
06/15/2020 Letter Stop Work Order
06/17/2020 Letter Stop Work Order
06/18/2020 Receipt Receipt for transaction:2020-003289
06/23/2020 Letter INSPECTION SUMMARY
06/24/2020 Letter INSPECTION SUMMARY
08/13/2020 Letter INSPECTION SUMMARY
08/13/2020 Letter INSPECTION SUMMARY
08/20/2020 Letter INSPECTION SUMMARY
09/16/2020 Letter INSPECTION SUMMARY
09/25/2020 Letter INSPECTION SUMMARY
10/07/2020 Letter INSPECTION SUMMARY
10/09/2020 Letter Codes Temporary Certificate of Occupancy
11/09/2020 Letter INSPECTION SUMMARY
11/09/2020 Letter Field Certificate of Occupancy
11/09/2020 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.