Permit Application Status

PRRES20192766


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20192766
Building Permit - Residential
Certificate of Occupancy
SILVERSTONE DEVELOPMENT LLC
NEW SINGLE FAMILY
NEW SINGLE FAMILY COVERED DECK PARTIAL BASEMENT FINISH
09/25/2019
10/18/2019
03/25/2020
04/21/2021
Locations
Contacts
SILVERSTONE DEVELOPMENT LLC, Address:PO BOX 346  
NICK ZVACEK CONSTRUCTION LLC, Address:1009 INDUSTRIAL DR, Phone:(816) 213-7204  
JEFF.BOEHM@ZVACEKCONSTRUCTION.COM  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
COMFORT SYSTEMS HTG/CLG, Address:128 W Markey Rd, Phone:(816) 322-1013  
CENTURY PLUMBING, Address:14001 CENTURY LN, Phone:(816) 765-6066  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 10/04/2019 10/02/2019
Steve Conrick
Plot Plan Review Approved 09/27/2019 10/02/2019
Steve Conrick
Legal description
Corrective Action Required
09/27/2019

The legal description, including plat or phase number and lot number, and street address must be provided on the plot plan. Correct Goshon to Goshen in address and on street.
City infrustructure
Corrective Action Required
09/27/2019

Show all manholes, water valve boxes, fire hydrants, and stormwater structures. Missing FH and valve
Deck location
Corrective Action Required
09/27/2019

Deck location, with dimensions to property lines must be provided on the plot plan. Label deck as covered
Right-of-way
Corrective Action Required
09/27/2019

The right-of-way with dimensions must be provided on the plot plan.
Drainage swales
Corrective Action Required
09/27/2019

Drainage swales (where required); show spot elevations within the swale as required to conform to the approved master drainage plan (if applicable), must be provided Label swale running along ne property line
Residential Plan Review Approved 10/01/2019 09/27/2019
Steve Conrick
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,069.13 $1,069.13 Paid 10/18/2019
Right of Way Permit Fee $80.00 $80.00 Paid 10/18/2019
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 10/18/2019
8331507-Sewer Connection Fee $390.00 $390.00 Paid 10/18/2019
Water Tap Fee $3,477.00 $3,477.00 Paid 10/18/2019
Water Meter Fee $425.02 $425.02 Paid 10/18/2019
Not Ready Inspection Fee $50.00 $50.00 Paid 04/20/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Failed 10/29/2019 10/29/2019 at 12:15 PM 10/29/2019
Misc
Corrective Action Required
10/29/2019
-INSTALL DEADMAN AT WEST SIDE AND FORM PADS NEAR STAIR PER PLAN
Footing Inspection - Residential Passed 10/29/2019 at 3:10 PM 10/29/2019
Misc
Resolved
10/29/2019
-INSTALL DEADMAN AT WEST SIDE AND FORM PADS NEAR STAIR PER PLAN
Foundation Inspection - Residential Passed 11/18/2019 11/18/2019 at 10:30 AM 11/18/2019
Sewer Service Inspection - R Passed 11/26/2019 (3:00) 11/26/2019 at 1:05 PM 11/26/2019
Underslab Plumbing Inspection - Residential Failed 11/27/2019 11/27/2019 at 8:40 AM 11/27/2019
Misc
Corrective Action Required
11/27/2019
-SHALL VENT THE SHOWER TRAP (TO WET-VENT THE WATER CLOSET). CANNOT VENT BOTH WATER CLOSET AND SHOWER TRAP. -BUILDING DRAIN MUST GO TO A GRINDER PUMP, SINCE THERE'S NOT ENOUGH FALL FOR THE SEWER AT CURRENT SEWER ELEVATION. FOUNDATION WALL WILL BE BORED ABOVE FLOOR FOR THE SEWER PIPE
Water Service Inspection - R Passed 12/3/2019 (10:45) 12/3/2019 at 11:15 AM 12/03/2019
Underslab Plumbing Inspection - Residential Passed 12/9/2019 12/9/2019 at 8:45 AM 12/09/2019
Misc
Corrective Action Required
11/27/2019
-SHALL VENT THE SHOWER TRAP (TO WET-VENT THE WATER CLOSET). CANNOT VENT BOTH WATER CLOSET AND SHOWER TRAP. -BUILDING DRAIN MUST GO TO A GRINDER PUMP, SINCE THERE'S NOT ENOUGH FALL FOR THE SEWER AT CURRENT SEWER ELEVATION. FOUNDATION WALL WILL BE BORED ABOVE FLOOR FOR THE SEWER PIPE
Piers/Caissons Inspection - Residential Not Ready 2/7/2020 2/7/2020 at 10:15 AM 02/07/2020
Misc
Corrective Action Required
02/07/2020
NOT READY. NO PIERS WERE DUG. WASTED-TRIP FEE ASSESSED
Driveway Inspection Passed 4/2/2020 4/2/2020 04/08/2020
Misc
Informational
04/08/2020
On Wednesday,4-08-2020. I visually inspected the driveway at 1104 NE Goshen Ct. Driveway met all standards and passes inspection.
Gas Service Inspection - Residential Passed 4/10/2020 04/10/2020
Electrical Service Inspection Passed 4/10/2020 04/10/2020
All Rough Inspection - Residential Failed 4/10/2020 at 8:30 AM 04/10/2020
Misc
Corrective Action Required
04/10/2020
FRAMING: -Nail siding to stud and sill plates at rear wall corners -Install hangers at deck header joist connection and trimmer joist connection to ledger board; install lag screws, etc -Fb mud wall from soffit/roof -Provide full support for beam at closet/stair wall -Install security blocking for all rear exterior doors -Install 4-studs support for the 18” lvl beam -Fb basement wall space vertically every ten ft or less; Fb basement closet&bath wall from furdown ceiling space -Anchor dill plate within 12” of basement exterior door -Install hanger at joist connection to beam at stair wall; nail beam hanger -Relocate I beam support columns at stair and bedroom wall to correct locations PLUMBING: -Protect water lines at master shower -Install wye or combination long sweep fitting at vertical to horizontal sewer connection MECHANICAL: -Close off all return air from the basement ceiling soffit; seal penetrations of return air space -Vent basement bathroom fan to outside ELECTRICAL: -Drive the grounding rod down into ground **OK TO INSULATE
All Rough Inspection - Residential Failed 4/15/2020 4/15/2020 at 9:40 AM 04/15/2020
Misc
Corrective Action Required
04/10/2020
FRAMING: -Install support device at trimmer joist connection to ledger board -Fb mud wall from soffit/roof **near garage door -Fb basement wall space vertically every ten ft or less; Fb basement closet&bath wall from furdown ceiling space **cannot use 1/2" board for fireblocking; fb hole at top of vertical fireblocking; wall in bath still not fireblocked from ceiling space; if insulation used as fireblocking must be min 16" from ceiling level down; etc -Nail all hanger nail holes at stair double joist-double joist connection -Relocate I beam support columns at stair and bedroom wall to correct locations **see plan for correct column locations PLUMBING: -Protect water lines at master shower -Install wye or combination long sweep fitting at vertical to horizontal sewer connection MECHANICAL: -Close off all return air from the basement ceiling soffit; seal penetrations of return air space
All Rough Inspection - Residential Passed 4/20/2020 4/20/2020 at 8:55 AM 04/20/2020
Misc
Resolved
04/20/2020
FRAMING: -Install support device at trimmer joist connection to ledger board -Fb mud wall from soffit/roof **near garage door -Fb basement wall space vertically every ten ft or less; Fb basement closet&bath wall from furdown ceiling space **cannot use 1/2" board for fireblocking; fb hole at top of vertical fireblocking; wall in bath still not fireblocked from ceiling space; if insulation used as fireblocking must be min 16" from ceiling level down; etc -Nail all hanger nail holes at stair double joist-double joist connection -Relocate I beam support columns at stair and bedroom wall to correct locations **see plan for correct column locations PLUMBING: -Protect water lines at master shower -Install wye or combination long sweep fitting at vertical to horizontal sewer connection MECHANICAL: -Close off all return air from the basement ceiling soffit; seal penetrations of return air space
Occupancy Inspection - Codes Residential Failed 11/12/2020 11/12/2020 11/12/2020
Corrective Action Required
11/12/2020
**NOT READY FEE ASSESSED ON FEB-07 **STREET CLEANUP REQUIRED. INSTALL EROSION CONTROL ALONG STREET AND BACK SIDE OF LOT -Piers not approved by the city. Have engineer submit letter to the city approving the piers -Final grade, sod, downspout and sump pump extensions -Install the sewer tracer wire and port -Seal exterior wall penetrations, seal above AC disconnect, meter, etc -Install tamper-proof caps at AC valves -Lag the deck ledger board through the spacers ; support outer deck joists to building per code and provide air gap between siding and ledger board -City amendment of the NEC requires all dedicated non-gfci receptacles in garage and unfinished basement to be identified (label, marking, etc) -Remove all items from garage -Pendant light fixture not allowed within the master bathroom tub zone -Isolate the low voltage from normal power inside fireplace switch box -Screw the exterior door embedded brace into the studs with 3” screws -Window located within 24” of basement walkout door must be safety glazing window -Provide gfci protection for dish washer -Install breaker lock for oven and cooktop -Remove all foundation wall ties -Cut off excess ufer rebar -Install gate valve for sewer pump discharge pipe
Occupancy Inspection - Codes Residential Failed 12/29/2020 12/29/2020 12/29/2020
Misc
Corrective Action Required
11/12/2020
**EXCEPT FOR SODDING, IT SEEMS LIKE NOTHING HAS BEEN DONE. -Not-ready fee accessed on Feb-07 has not been paid. No occupancy shall be issued until the fee, the piers approval, and all interior deficiencies are corrected -Piers not approved by the city. Have engineer submit letter to the city approving the piers -Final grade, sod, downspout and sump pump extensions -Install the sewer tracer wire and port -Seal exterior wall penetrations, seal above AC disconnect, meter, etc -Install tamper-proof caps at AC valves -Lag the deck ledger board through the spacers; support outer deck joists to building per code and provide air gap between siding and ledger board -City amendment of the NEC requires all dedicated non-gfci receptacles in garage and unfinished basement to be identified (label, marking, etc) -Remove all items from garage -Pendant light fixture not allowed within the master bathroom tub zone -Isolate the low voltage from normal power inside fireplace switch box -Window located within 24” of basement walkout door must be safety glazing window -Provide gfci protection for dish washer -Install breaker lock for oven and cooktop -Remove all foundation wall ties -Cut off excess ufer rebar -Install gate valve for sewer pump discharge pipe
Occupancy Inspection - Codes Residential Failed 2/10/2021 2/10/2021 02/10/2021
Misc
Corrective Action Required
11/12/2020
-Not-ready fee accessed on Feb-07 has not been paid. No occupancy shall be issued until the fee, the piers approval, and all interior deficiencies are corrected -Piers not approved by the city. Have engineer submit letter to the city approving the piers -Install downspout and sump pump extensions -Install the sewer tracer wire and port -Lag the deck ledger board through the spacers; install and support outer deck joists per code
Piers/Caissons Inspection - Residential Passed 2/18/2021 02/18/2021
Misc
Informational
02/18/2021
CONVERSTION WITH CYRUYS COX - cc CONCRETE TOOK OVER FORM THE PERVIOUS CONTRACTOR AND REDRILLED THE PIERS 36" AND POURED THEM. THE HOUSE AT 1108 WAS INSPECTECT AND POURED THE DAY BEFORE. FROM THE CONVERSTION WE HAD THE PIERS ARE APPROVED. MARK HARDING 02/18/2021 4:30 PM
Occupancy Inspection - Codes Residential Failed 4/16/2021 4/16/2021 04/16/2021
Misc
Corrective Action Required
02/10/2021
-Not-ready fee accessed on Feb-07 has not been paid. No occupancy shall be issued until the fee is paid -Install downspout and sump pump extensions -Install the sewer tracer port
Occupancy Inspection - Codes Residential Full C of O 4/21/2021 04/21/2021
Misc
Informational
04/21/2021
**THE SEWER LINE IS CLOGGED. THE SEWER CAP OUTSIDE WAS BLOWN OFF BY OVERFLOWING SEWAGE. THE PLUMBER IS ON SITE TO UNCLOG THE SEWER
Documents & Images
Date Uploaded File Type Document Name
09/27/2019 Letter Codes Residential Plan Review
10/18/2019 Receipt Receipt for transaction: 2019-006871
10/18/2019 Letter DS Building Permit
10/18/2019 Plot Plan 1104 NE Goshen
10/29/2019 Letter INSPECTION SUMMARY
10/29/2019 Letter INSPECTION SUMMARY
11/18/2019 Letter INSPECTION SUMMARY
11/26/2019 Letter INSPECTION SUMMARY
11/27/2019 Letter INSPECTION SUMMARY
12/03/2019 Letter INSPECTION SUMMARY
12/09/2019 Letter INSPECTION SUMMARY
02/07/2020 Letter INSPECTION SUMMARY
04/10/2020 Letter INSPECTION SUMMARY
04/10/2020 Letter INSPECTION SUMMARY
04/10/2020 Letter INSPECTION SUMMARY
04/15/2020 Letter INSPECTION SUMMARY
04/20/2020 Letter INSPECTION SUMMARY
11/12/2020 Letter INSPECTION SUMMARY
12/29/2020 Letter INSPECTION SUMMARY
12/29/2020 Letter INSPECTION SUMMARY
02/10/2021 Letter INSPECTION SUMMARY
02/18/2021 Letter INSPECTION SUMMARY
04/16/2021 Letter INSPECTION SUMMARY
04/20/2021 Receipt Receipt for transaction:2021-002076
04/21/2021 Letter Codes Final Certificate of Occupancy
04/21/2021 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home