Review Type |
Outcome |
Est. Completion Date |
Completed |
Plot Plan Review
|
Approved
|
10/07/2019
|
10/03/2019
|
|
Steve Conrick
|
|
|
Residential Plan Review
|
Approved
|
10/07/2019
|
10/03/2019
|
|
Steve Conrick
|
|
06 Designate use of each room or space
Corrective Action Required
Designate use of each room or space including but not limited to; basement storage, garages, and attic areas intended for storage space.
CLEAN UP LINEWORK IN BASEMENT AND 1ST AND 2ND FLOORS TO CLEARIFY ROOM DESIGNINATION. (I.E. KITCHEN AND UPSTAIRS BATHROOM ARE OVERLAPING ON SHEET A105)
|
|
07 Identify emergency escape openings from bedrooms
Corrective Action Required
Identify emergency escape openings from bedrooms and basement(s). (IRC Section R310 as amended per Ordinance)
|
|
08 Designate locations of smoke detectors and carbon monoxide detectors
Corrective Action Required
Designate locations of smoke detectors and carbon monoxide detectors. (IRC Section R314 and R315)
ADD COMBO DETECTOR NEAR ADDIE'S ROOM ON SHEET A106
|
|
10 Combustion air
Corrective Action Required
Provide combustion air calculations and specify transfer air grilles for fuel burning appliances located in confined space(s). (IRC Chapter 17 and Section G2407)
|
|
11 Designate R-value(s) for floors, walls, ceilings, roof/ceilings.
Corrective Action Required
Designate R-value(s) for floors, walls, ceilings, roof/ceilings. (LSCO 7-802)
|
|
33 Identify braced wall locations and length of braced wall panel(s).
Corrective Action Required
Identify braced wall locations and length of braced wall panel(s). (IRC Section R602.10)
|
|
37 Provide details for any walls over 10 feet in height.
Corrective Action Required
Provide details for any walls over 10 feet in height. Include stud grade, size, spacing and actual, uninterrupted height. (IRC Section 602.3.1 and Table 602.3(5) & 602.3.1)
|
|
|
Plot Plan Review
|
Approved
|
09/25/2019
|
09/25/2019
|
|
Steve Conrick
|
|
As-graded plot plan
Corrective Action Required
A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
|
|
City infrustructure
Corrective Action Required
Show all manholes, water valve boxes, fire hydrants, and stormwater structures.
CALL OUT FIELD INLET WITH TOP AND WEIR ELEVATION
|
|
Drainage swales
Corrective Action Required
Drainage swales (where required); show spot elevations within the swale as required to conform to the approved master drainage plan (if applicable), must be provideD
|
|
Lot elevations
Corrective Action Required
Existing and finish elevations at all property corners must be provided on the plot plan.
VERIFY LOT CORNER ELEVATIONS ARE CORRECT. THEY ARE SHOWN DIFFERENT THAT WHAT IS ON THE MOST RECENT AS-GRADED MDP
|
|
|
Residential Plan Review
|
Rejected
|
09/25/2019
|
09/23/2019
|
|
Steve Conrick
|
|
06 Designate use of each room or space
Corrective Action Required
Designate use of each room or space including but not limited to; basement storage, garages, and attic areas intended for storage space.
CLEAN UP LINEWORK IN BASEMENT AND 1ST AND 2ND FLOORS TO CLEARIFY ROOM DESIGNINATION. (I.E. KITCHEN AND UPSTAIRS BATHROOM ARE OVERLAPING ON SHEET A105)
|
|
07 Identify emergency escape openings from bedrooms
Corrective Action Required
Identify emergency escape openings from bedrooms and basement(s). (IRC Section R310 as amended per Ordinance)
|
|
08 Designate locations of smoke detectors and carbon monoxide detectors
Corrective Action Required
Designate locations of smoke detectors and carbon monoxide detectors. (IRC Section R314 and R315)
ADD COMBO DETECTOR NEAR ADDIE'S ROOM ON SHEET A106
|
|
10 Combustion air
Corrective Action Required
Provide combustion air calculations and specify transfer air grilles for fuel burning appliances located in confined space(s). (IRC Chapter 17 and Section G2407)
|
|
11 Designate R-value(s) for floors, walls, ceilings, roof/ceilings.
Corrective Action Required
Designate R-value(s) for floors, walls, ceilings, roof/ceilings. (LSCO 7-802)
|
|
33 Identify braced wall locations and length of braced wall panel(s).
Corrective Action Required
Identify braced wall locations and length of braced wall panel(s). (IRC Section R602.10)
|
|
37 Provide details for any walls over 10 feet in height.
Corrective Action Required
Provide details for any walls over 10 feet in height. Include stud grade, size, spacing and actual, uninterrupted height. (IRC Section 602.3.1 and Table 602.3(5) & 602.3.1)
|
|
|