Summary
PRRES20191998
Building Permit - Residential
Certificate of Occupancy
SAB CONSTRUCTION LLC
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - COVERED DECK
07/25/2019
07/31/2019
05/04/2020
Locations
Contacts
SAB CONSTRUCTION LLC, Address:PO BOX 942, Phone:(816) 524-3855  
SAB CONSTRUCTION INC, Address:PO BOX 942, Phone:(816) 524-3855  
MIKE BRYANT HEATING & COOLING , Address:1711 E 123RD , Phone:(913) 441-7807  
C-R ELECTRICAL LLC, Address:4539 RIDGEWAY, Phone:(816) 803-3500  
GARRISON PLUMBING, Address:15430 S MAHAFFIE ST STE 102, Phone:(913) 768-1311  
ROBERT@SABHOMES.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 07/29/2019 07/31/2019
Development Center
Misc
Corrective Action Required
07/25/2019

This plan references the 2012 code book and it should reference the 2018 code book
Miscellaneous Correction
Corrective Action Required
07/25/2019

The electrical contractor listed on this permit does not have a valid business license
Plot Plan Review Approved 07/29/2019 07/29/2019
Steve Conrick
Legal description
Corrective Action Required
07/25/2019

The legal description, including plat or phase number and lot number, and street address must be provided on the plot plan. The plot plan shows the address as being NW when it should be NE
Misc
Corrective Action Required
07/25/2019

The plot plan shows a patio and should show a covered deck
Easements
Corrective Action Required
07/26/2019

All easements with dimensions must be provided on the plot plan. *The easement in the front of the property is 15' not 10'
As-graded plot plan
Corrective Action Required
07/26/2019

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy. *add "AS-GRADED PLOT PLAN IS REQUIRED PRIOR TO SODDING."
Monticello Landscaping
Corrective Action Required
08/05/2019

Per Ordinance 7690, Section 3.10 The builders are required to put in a minimum of three Evergreen trees, two ornamental trees and three shrubs, on each lot adjacent to the Lake Ridge Meadows and Dalton's Ridge subdivisions, acknowledging that the goal is to provide a visual buffer for the property to the north. No final certificate of occupancy shall be issued for an individually affected lot until such time as the required number of trees and shrubs are planted on said lot. The required landscaping shall be planted within 20 feet of the rear proerty line. The required landscaping shall meet the minimum size requirements of the UDO at the time of planting (i.e. 8' for Evergreen trees, 3" caliper for ornamental trees and 2-gallon container for shrubs).
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,459.28 $1,459.28 Paid 07/31/2019
Right of Way Permit Fee $80.00 $80.00 Paid 07/31/2019
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 07/31/2019
8331507-Sewer Connection Fee $600.00 $600.00 Paid 07/31/2019
Water Tap Fee $3,477.00 $3,477.00 Paid 07/31/2019
Water Meter Fee $425.02 $425.02 Paid 07/31/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 8/12/2019 (1:45) 8/12/2019 at 1:45 PM 08/12/2019
Sewer Service Inspection - R Passed 8/16/2019 (1:00) 8/16/2019 at 1:00 PM 08/16/2019
Water Service Inspection - R Partial 8/16/2019 08/16/2019
Water Service Inspection - R Passed 8/19/2019 (9:15) 8/19/2019 at 10:05 AM 08/19/2019
Erosion Control Inspection Residential Partial 9/6/2019 09/06/2019
Misc
Informational
09/06/2019
EROSION CONTROL IS IN COMPLIANCE. MAINTAIN EROSION CONTROL
Underslab Plumbing Inspection - Residential Passed 9/6/2019 9/6/2019 at 9:45 AM 09/06/2019
Erosion Control Inspection Residential Failed 9/12/2019 09/12/2019
Misc
Corrective Action Required
09/12/2019
REPAIR SILT FENCE ALONG THE STREET. STREET IS GENERALLY CLEAN
Piers/Caissons Inspection - Residential Passed 9/12/2019 9/12/2019 at 9:30 AM 09/12/2019
Gas Service Inspection - Residential Passed 11/1/2019 11/01/2019
Electrical Service Inspection Failed 11/1/2019 11/01/2019
Misc
Corrective Action Required
11/01/2019
-Bond service disconnect enclosure
All Rough Inspection - Residential Failed 11/1/2019 at 9:05 AM 11/01/2019
Misc
Corrective Action Required
11/01/2019
FRAMING: -Fb garage wall space from fur-down ceiling space -Solid block cantilevered joists -Verification of deck roof beam support -Support ridge above foyer to lvl rafter -Studs not continuous from floor to ceiling at 2nd floor walls -Support ridge above master bathroom to bearing wall/beam -Support bedroom ridges to bearing wall -Support double 2x10 ceiling beam at laundry/hallway wall with double studs -Install joist hangers in basement ELECTRICAL: -Provide a rear outdoor receptacle readily accessible from and within 6.5 ft of grade -Move smoke alarm to within 12” of ceiling PLUMBING: -Install stud shoe for over bored stud in laundry **OK TO INSULATE
Electrical Service Inspection Passed 11/7/2019 11/7/2019 11/07/2019
Misc
Resolved
11/07/2019
-Bond service disconnect enclosure
All Rough Inspection - Residential Failed 11/7/2019 11/7/2019 11/07/2019
Misc
Corrective Action Required
11/01/2019
FRAMING: -Fb garage wall space from fur-down ceiling space. -Verification of deck roof beam support, support ridge as a beam or install rafter ties in lower 1/3 of rafters. -Support ridge above foyer to lvl rafter
All Rough Inspection - Residential Passed 11/8/2019 at 2:20 PM 11/08/2019
Misc
Resolved
11/08/2019
FRAMING: -Fb garage wall space from fur-down ceiling space. -Verification of deck roof beam support, support ridge as a beam or install rafter ties in lower 1/3 of rafters. -Support ridge above foyer to lvl rafter
Driveway Inspection Partial 1/7/2020 (A.M.) 1/7/2020 at 2:00 PM 01/08/2020
Misc
Informational
01/08/2020
The driveway has been formed, rock installed and compacted. Ready to pour.
Driveway Inspection Passed 1/9/2020 02/03/2020
Misc
Informational
01/08/2020
The driveway has been formed, rock installed and compacted. Ready to pour.
Misc
Informational
02/03/2020
Driveway- passed inspection.
Erosion Control Inspection Residential Passed 02/07/2020
Misc
Resolved
02/07/2020
REPAIR SILT FENCE ALONG THE STREET. STREET IS GENERALLY CLEAN
Occupancy Inspection - Codes Residential Failed 2/7/2020 2/7/2020 at 9:35 AM 02/07/2020
Misc
Corrective Action Required
02/07/2020
-As-graded plot plan is required prior to sodding -Provide landscaping at rear per city ordinance -Final grade, sod, downspout and sump pump extensions -Make sure that the sewer tracer wire and port are installed and available at grade level -Seal exterior lights. Front entry lights not meeting security code -Handrail not continuous for the entire upper floor stair flight. FYI: the winder tread is not a landing -Install water hammering arrestor for dish washer -Fb garage wall penetrations -Provide afci protection per NEC 210.12 -Install breaker lock for circuit feeding the kitchen hood
Occupancy Inspection - Codes Residential Temporary C of O 2/13/2020 2/13/2020 at 9:40 AM 02/13/2020
Misc
Corrective Action Required
02/07/2020
-As-graded plot plan is required prior to sodding -Provide landscaping at rear per city ordinance -Final grade, sod, downspout and sump pump extensions -Make sure that the sewer tracer wire and port are installed and available at grade level
Occupancy Inspection - Codes Residential Full C of O 5/4/2020 5/4/2020 at 10:25 AM 05/04/2020
Misc
Resolved
05/04/2020
-As-graded plot plan is required prior to sodding -Provide landscaping at rear per city ordinance -Final grade, sod, downspout and sump pump extensions -Make sure that the sewer tracer wire and port are installed and available at grade level
Documents & Images
Date Uploaded File Type Document Name
07/25/2019 Letter Codes Residential Plan Review
07/26/2019 Letter Codes Residential Plan Review
07/31/2019 Receipt Receipt for transaction: 2019-005216
07/31/2019 Letter DS Building Permit
08/02/2019 Plot Plan DOC080219-08022019103640
08/12/2019 Letter INSPECTION SUMMARY
08/16/2019 Letter INSPECTION SUMMARY
08/16/2019 Letter INSPECTION SUMMARY
08/19/2019 Letter INSPECTION SUMMARY
09/06/2019 Letter INSPECTION SUMMARY
09/06/2019 Letter INSPECTION SUMMARY
09/12/2019 Letter INSPECTION SUMMARY
09/12/2019 Letter INSPECTION SUMMARY
11/01/2019 Letter INSPECTION SUMMARY
11/01/2019 Letter INSPECTION SUMMARY
11/01/2019 Letter INSPECTION SUMMARY
11/07/2019 Letter INSPECTION SUMMARY
11/07/2019 Letter INSPECTION SUMMARY
11/08/2019 Letter INSPECTION SUMMARY
01/08/2020 Letter DE-Daily Inspection Summary
02/03/2020 Letter INSPECTION SUMMARY
02/07/2020 Letter INSPECTION SUMMARY
02/07/2020 Letter INSPECTION SUMMARY
02/13/2020 Letter Codes Temporary Certificate of Occupancy
05/04/2020 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home