Permit Application Status

PRRES20191819


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20191819
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - FINISHED BASENENT - COVERED DECK
07/10/2019
07/29/2019
07/02/2020
Locations
Contacts
BLUE VALLEY HEATING & COOLING LLC, Address:P O BOX 241, Phone:(816) 867-5122  
IMPACT ELECTRICAL SOLUTIONS LLC, Address:14 ANCHOR DRIVE, Phone:(816) 674-9345  
A BRIGHT PLUMBING LLC, Address:201 NE WOODBURY DR, Phone:(816) 867-4540  
YANCIK@SBCGLOBAL.NET  
TRUMARK HOMES, LLC, Address:424 SE MAXWELL DR, Phone:(816) 564-5613  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 07/12/2019 07/29/2019
Development Center
05 Provide square footage of living area, garage area, unfinished basement
Corrective Action Required
07/10/2019

Provide square footage of living area, garage area, unfinished basement area, etc (IRC Section R304) No square footage shown for the garage
06 Designate use of each room or space
Corrective Action Required
07/10/2019

Designate use of each room or space including but not limited to; basement storage, garages, and attic areas intended for storage space. No designation for the laundry room
Plot Plan Review Approved 07/12/2019 07/12/2019
Steve Conrick
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,007.73 $1,007.73 Paid 07/29/2019
Right of Way Permit Fee $80.00 $80.00 Paid 07/29/2019
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 07/29/2019
8331507-Sewer Connection Fee $510.00 $510.00 Paid 07/29/2019
Water Tap Fee $3,477.00 $3,477.00 Paid 07/29/2019
Water Meter Fee $425.02 $425.02 Paid 07/29/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 7/30/2019 (1:30) 7/30/2019 at 3:00 PM 07/30/2019
Sewer Service Inspection - R Passed 8/13/2019 at 2:15 PM 08/13/2019
Underslab Plumbing Inspection - Residential Passed 8/15/2019 8/15/2019 at 9:35 AM 08/15/2019
Water Service Inspection - R Passed 8/15/2019 (2:15) 8/15/2019 at 2:50 PM 08/15/2019
Piers/Caissons Inspection - Residential Failed 8/20/2019 8/20/2019 at 10:45 AM 08/20/2019
Misc
Corrective Action Required
08/20/2019
-PROVIDE PLAN ON SITE -CLEAN OUT LOOSE DIRT FROM PIER HOLES
Piers/Caissons Inspection - Residential Passed 8/20/2019 (11:30) 8/20/2019 at 1:10 PM 08/20/2019
Misc
Resolved
08/20/2019
-PROVIDE PLAN ON SITE -CLEAN OUT LOOSE DIRT FROM PIER HOLES
Erosion Control Inspection Residential Failed 9/16/2019 09/16/2019
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
09/16/2019
DEFICIENT EROSION CONTROL INSTALLATION. RESTORE EROSION CONTROL ALONG THE STREET AND CLEAN UP THE STREET NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Piers/Caissons Inspection - Residential Passed 9/16/2019 (Ready Now) 9/16/2019 at 1:40 PM 09/16/2019
Informational
09/16/2019
STAIR LANDING PIERS
Electrical Service Inspection Passed 10/1/2019 10/1/2019 10/01/2019
Gas Service Inspection - Residential Passed 10/1/2019 10/1/2019 10/01/2019
All Rough Inspection - Residential Failed 10/1/2019 10/1/2019 at 9:00 AM 10/01/2019
Misc
Corrective Action Required
10/01/2019
FRAMING: -Install collar ties spaced no more than 4 ft -Fb all floor and ceiling penetrations -Vapor barrier missing at rear deck door -Fill in void behind deck door hinges; install security blocking -Move roof support struts above master bedroom small closet to bearing wall -Fb basement wall vertically spaced at ten ft or less; Fb rear wall from joist space (gap) -Toe nail basement joists to sill plates -Install full support underneath trimmer studs below fireplace MECHANICAL: -Connect duct to bath fans -Fasten fireplace to framing -Seal return air space above basement bathroom (at solid blocking above I beam) -Pan off return air space below pantry and above front basement bedroom from I beam space **OK TO INSULATE
Erosion Control Inspection Residential Passed 10/1/2019 10/01/2019
DCM2 ESC DEFICIENT INSTALLATION
Informational
10/01/2019
-EROSION CONTROL IS IN COMPLIANCE. MAINTAIN EROSION CONTROL UNTIL SODDING
All Rough Inspection - Residential Failed 10/3/2019 10/3/2019 at 9:40 AM 10/03/2019
Misc
Corrective Action Required
10/01/2019
FRAMING: -Toe nail basement joists to sill plates -Install full support underneath trimmer studs below fireplace MECHANICAL: -Fasten fireplace to framing -Seal return air space above basement bathroom (at solid blocking above I beam) **OK TO INSULATE
All Rough Inspection - Residential Passed 10/7/2019 10/7/2019 at 9:40 AM 10/07/2019
Misc
Resolved
10/07/2019
FRAMING: -Toe nail basement joists to sill plates -Install full support underneath trimmer studs below fireplace MECHANICAL: -Fasten fireplace to framing -Seal return air space above basement bathroom (at solid blocking above I beam) **OK TO INSULATE
Driveway Inspection Partial 11/15/2019 11/15/2019 11/15/2019
Misc
Informational
11/15/2019
Driveway - forms and materials passed pre-inspection.
Sidewalk Inspection Partial 12/6/2019 (A.M.) 12/6/2019 12/06/2019
Misc
Informational
12/06/2019
Sidewalk- forms & materials passed pre-inspection.
Occupancy Inspection - Codes Residential Failed 3/24/2020 at 10:10 AM 03/24/2020
Misc
Corrective Action Required
03/24/2020
-Sidewalk and driveway not approved on record -Outside not inspected at this time. Make sure to seal all exterior lights and wall penetrations; sewer tracer wire port; 40 amp AC breaker match label -Final grade, sod -Garage door not self closing -Exterior deck door lock not compliant. Lock must be able to activate without use of key from egress side -Deck: install joist hangers; block/reinforce guardrail posts -Install water service pressure reducer -Secure water service pex line
Occupancy Inspection - Codes Residential Temporary C of O 3/30/2020 3/30/2020 at 8:45 AM 03/30/2020
Misc
Corrective Action Required
03/24/2020
-Sidewalk and driveway not approved on record -Final grade, sod -Deck: install hanger at deck beam connection to ledger; shim gap between joists and hangers -Install anti-backflow device at hose bibb
Driveway Inspection Passed 3/30/2020 03/30/2020
Misc
Informational
03/30/2020
Driveway - forms and materials passed pre-inspection.
Misc
Informational
03/30/2020
Driveway passed.
Driveway Inspection Passed 3/30/2020 3/30/2020 03/30/2020
Misc
Informational
11/15/2019
Driveway - forms and materials passed pre-inspection.
Sidewalk Inspection Passed 3/30/2020 (A.M.) 3/30/2020 03/30/2020
Misc
Informational
12/06/2019
Sidewalk- forms & materials passed pre-inspection.
Misc
Informational
03/30/2020
The sidewalk has passed.
Occupancy Inspection - Codes Residential Full C of O 7/2/2020 7/2/2020 at 10:20 AM 07/02/2020
Misc
Resolved
07/02/2020
-Final grade, sod -Deck: install hanger at deck beam connection to ledger; shim gap between joists and hangers
Documents & Images
Date Uploaded File Type Document Name
07/10/2019 Letter Codes Residential Plan Review
07/29/2019 Receipt Receipt for transaction: 2019-005117
07/29/2019 Letter DS Building Permit
07/29/2019 Plot Plan DOC072919-001
07/30/2019 Letter INSPECTION SUMMARY
08/13/2019 Letter INSPECTION SUMMARY
08/15/2019 Letter INSPECTION SUMMARY
08/15/2019 Letter INSPECTION SUMMARY
08/20/2019 Letter INSPECTION SUMMARY
08/20/2019 Letter INSPECTION SUMMARY
09/16/2019 Letter INSPECTION SUMMARY
09/16/2019 Letter INSPECTION SUMMARY
10/01/2019 Letter INSPECTION SUMMARY
10/01/2019 Letter INSPECTION SUMMARY
10/01/2019 Letter INSPECTION SUMMARY
10/01/2019 Letter INSPECTION SUMMARY
10/03/2019 Letter INSPECTION SUMMARY
10/07/2019 Letter INSPECTION SUMMARY
12/06/2019 Letter INSPECTION SUMMARY
03/24/2020 Letter INSPECTION SUMMARY
03/30/2020 Letter Codes Temporary Certificate of Occupancy
03/30/2020 Letter DE-Daily Inspection Summary
03/30/2020 Letter DE-Daily Inspection Summary
07/02/2020 Letter Codes Final Certificate of Occupancy
07/02/2020 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home