Permit Application Status

PRRES20191818


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20191818
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - COVERED DECK - FINISHED BASEMENT
07/10/2019
07/29/2019
07/02/2020
Locations
Contacts
TRUMARK HOMES, LLC, Address:424 SE MAXWELL DR, Phone:(816) 564-5613  
BLUE VALLEY HEATING & COOLING LLC, Address:P O BOX 241, Phone:(816) 867-5122  
IMPACT ELECTRICAL SOLUTIONS LLC, Address:14 ANCHOR DRIVE, Phone:(816) 674-9345  
A BRIGHT PLUMBING LLC, Address:201 NE WOODBURY DR, Phone:(816) 867-4540  
YANCIK@SBCGLOBAL.NET  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 07/12/2019 07/29/2019
Development Center
05 Provide square footage of living area, garage area, unfinished basement
Corrective Action Required
07/10/2019

Provide square footage of living area, garage area, unfinished basement area, etc (IRC Section R304) No square footage shown for covered deck or the garage
Miscellaneous Correction
Corrective Action Required
07/10/2019

Plans show optional master bath, optional half bath and bar in the basement and optional walkout. Plans will not be accepted that shows these "optional" options on the drawings. Please show what will be built only.
Plot Plan Review Approved 07/12/2019 07/15/2019
Steve Conrick
Basement egress
Corrective Action Required
07/12/2019

Basement egress location(s) and elevation of the lowest adjacent grade must be provided on the plot plan. *Check egress elevations.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,014.95 $1,014.95 Paid 07/29/2019
Right of Way Permit Fee $80.00 $80.00 Paid 07/29/2019
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 07/29/2019
8331507-Sewer Connection Fee $450.00 $450.00 Paid 07/29/2019
Water Tap Fee $3,477.00 $3,477.00 Paid 07/29/2019
Water Meter Fee $425.02 $425.02 Paid 07/29/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 7/31/2019 (2:30) 7/31/2019 at 3:10 PM 07/31/2019
Sewer Service Inspection - R Passed 8/13/2019 at 2:10 PM 08/13/2019
Underslab Plumbing Inspection - Residential Passed 8/15/2019 8/15/2019 at 9:40 AM 08/15/2019
Water Service Inspection - R Passed 8/15/2019 (2:15) 8/15/2019 at 2:45 PM 08/15/2019
Piers/Caissons Inspection - Residential Failed 8/20/2019 8/20/2019 at 10:50 AM 08/20/2019
Misc
Corrective Action Required
08/20/2019
-PROVIDE PLAN ON SITE -CLEAN OUT LOOSE DIRT FROM PIER HOLES
Piers/Caissons Inspection - Residential Passed 8/20/2019 (11:30) 8/20/2019 at 1:15 PM 08/20/2019
Misc
Resolved
08/20/2019
-PROVIDE PLAN ON SITE -CLEAN OUT LOOSE DIRT FROM PIER HOLES
Erosion Control Inspection Residential Failed 9/16/2019 09/16/2019
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
09/16/2019
DEFICIENT EROSION CONTROL INSTALLATION. RESTORE EROSION CONTROL ALONG THE STREET AND CLEAN UP THE STREET NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Piers/Caissons Inspection - Residential Passed 9/16/2019 (Ready Now) 9/16/2019 at 1:45 PM 09/16/2019
Informational
09/16/2019
STAIR LANDING PIERS
Gas Service Inspection - Residential Passed 10/1/2019 10/1/2019 at 11:05 AM 10/01/2019
Erosion Control Inspection Residential Passed 10/07/2019
DCM2 ESC DEFICIENT INSTALLATION
Informational
10/07/2019
-EROSION CONTROL IS IN COMPLIANCE. MAINTAIN EROSION CONTROL UNTIL SODDING
Electrical Service Inspection Passed 10/7/2019 10/7/2019 10/07/2019
All Rough Inspection - Residential Failed 10/7/2019 10/7/2019 at 9:50 AM 10/07/2019
Misc
Corrective Action Required
10/07/2019
**Provide plan on site FRAMING: -Anchor garage column; anchor garage sill plate within 12” of break -Shim gap between garage wall sole plate and sill plate -Strap garage portal wall inner side -Strap garage top plates lapped less than 24” -Install collar tie near ridge -Fb all floor and ceiling penetrations -Nail corner studs per code -Check number of stud support for 24” lvl beam -Complete framing and secure fireplace to framing -Support hip rafters above master bedroom -Use 3/4” sheathing for fire blocking (or other approved materials), not 1/2” sheathing ; Fb basement wall from soffit and joist space -Solid block underneath triple trimmer studs of 24” lvl; Solid block under 24” lvl point load; solid block joists above I beam MECHANICAL: -Seal all penetrations of return air space throughout at wall and ceiling -Connect ducting to bath fans -Pan off RA space from fur down space. Screw the panning sheet to joist; complete RA to front bedroom PLUMBING: -Protect plumbing at master bedroom wall -Protect water line at refrigerator and above wet bar -Protect 3” plumbing in basement closet -Support plumbing per code **DO NOT INSULATE
All Rough Inspection - Residential Failed 10/9/2019 10/9/2019 at 8:30 AM 10/09/2019
Misc
Corrective Action Required
10/07/2019
FRAMING: -Anchor garage column; anchor garage sill plate within 12” of break -Shim gap between garage wall sole plate and sill plate -Strap garage portal wall inner side -Strap garage top plates lapped less than 24” -Fb all floor and ceiling penetrations -Support hip rafters above master bedroom -Fb basement wall from soffit and joist space -Solid block underneath triple trimmer studs of 24” lvl MECHANICAL: -Seal all penetrations of return air space throughout at wall and ceiling PLUMBING: -Protect plumbing at master bedroom wall -Protect water line at refrigerator and above wet bar -Protect 3” plumbing in basement closet -Support plumbing per code **OK TO INSULATE
All Rough Inspection - Residential Passed 10/11/2019 10/11/2019 at 8:35 AM 10/11/2019
Misc
Resolved
10/11/2019
FRAMING: -Anchor garage column; anchor garage sill plate within 12” of break -Shim gap between garage wall sole plate and sill plate -Strap garage portal wall inner side -Strap garage top plates lapped less than 24” -Fb all floor and ceiling penetrations -Support hip rafters above master bedroom -Fb basement wall from soffit and joist space -Solid block underneath triple trimmer studs of 24” lvl MECHANICAL: -Seal all penetrations of return air space throughout at wall and ceiling PLUMBING: -Protect plumbing at master bedroom wall -Protect water line at refrigerator and above wet bar -Protect 3” plumbing in basement closet -Support plumbing per code **OK TO INSULATE
Sidewalk Inspection Partial 12/5/2019 12/5/2019 12/06/2019
Misc
Informational
12/06/2019
Sidewalk - forms & materials passed pre-inspection.
Driveway Inspection Partial 12/5/2019 12/5/2019 12/06/2019
Misc
Informational
12/06/2019
Driveway- forms & materials passed pre-inspection.
Occupancy Inspection - Codes Residential Failed 3/24/2020 at 9:25 AM 03/24/2020
Misc
Corrective Action Required
03/24/2020
-Sidewalk and driveway not approved on record -Outside not inspected at this time. Make sure to seal all exterior lights and wall penetrations; sewer tracer wire port; 40 amp AC breaker match label -Final grade, sod -Deck: block/reinforce guardrail posts
Sidewalk Inspection Passed 3/30/2020 (A.M.) 3/30/2020 03/30/2020
Misc
Informational
12/06/2019
Sidewalk - forms & materials passed pre-inspection.
Misc
Informational
03/30/2020
The sidewalk has passed ispection
Driveway Inspection Passed 3/30/2020 (A.M.) 3/30/2020 03/30/2020
Misc
Informational
12/06/2019
Driveway- forms & materials passed pre-inspection.
Misc
Informational
03/30/2020
The diveway has passed inspection.
Occupancy Inspection - Codes Residential Temporary C of O 5/1/2020 5/1/2020 at 10:25 AM 05/01/2020
Misc
Corrective Action Required
03/24/2020
-Secure AC whip within 12" of disconnect -Final grade, sod, downspout extensions -Deck: block/reinforce guardrail posts; shim gap below joist at hangers
Occupancy Inspection - Codes Residential Full C of O 7/2/2020 7/2/2020 at 10:15 AM 07/02/2020
Misc
Resolved
07/02/2020
-Secure AC whip within 12" of disconnect -Final grade, sod, downspout extensions -Deck: block/reinforce guardrail posts; shim gap below joist at hangers
Documents & Images
Date Uploaded File Type Document Name
07/10/2019 Letter Codes Residential Plan Review
07/12/2019 Letter Codes Residential Plan Review
07/29/2019 Receipt Receipt for transaction: 2019-005119
07/29/2019 Letter DS Building Permit
07/29/2019 Plot Plan DOC072919-002
07/31/2019 Letter INSPECTION SUMMARY
08/13/2019 Letter INSPECTION SUMMARY
08/15/2019 Letter INSPECTION SUMMARY
08/15/2019 Letter INSPECTION SUMMARY
08/20/2019 Letter INSPECTION SUMMARY
08/20/2019 Letter INSPECTION SUMMARY
09/16/2019 Letter INSPECTION SUMMARY
09/16/2019 Letter INSPECTION SUMMARY
10/01/2019 Letter INSPECTION SUMMARY
10/07/2019 Letter INSPECTION SUMMARY
10/07/2019 Letter INSPECTION SUMMARY
10/07/2019 Letter INSPECTION SUMMARY
10/09/2019 Letter INSPECTION SUMMARY
10/11/2019 Letter INSPECTION SUMMARY
12/06/2019 Letter INSPECTION SUMMARY
12/06/2019 Letter INSPECTION SUMMARY
03/24/2020 Letter INSPECTION SUMMARY
03/30/2020 Letter DE-Daily Inspection Summary
03/30/2020 Letter DE-Daily Inspection Summary
05/01/2020 Letter Codes Temporary Certificate of Occupancy
07/02/2020 Letter Codes Final Certificate of Occupancy
07/02/2020 Letter Field Certificate of Occupancy
01/04/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home