Summary
PRRES20173808
Building Permit - Residential
Certificate of Occupancy
SILVERSTONE DEVELOPMENT LLC
NEW SINGLE FAMILY
NEW HOUSE - FINISHED BASEMENT - COVERED DECK
11/21/2017
12/08/2017
09/12/2018
Locations
Contacts
SILVERSTONE DEVELOPMENT LLC, Address:1248 SW WYSTERIA DR  
D AND D BUILDING INC, Address:PO BOX 7014, Phone:(816) 491-2125  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
INTREPID ELECTRIC LLC, Address:620 S KISNER CIR, Phone:(816) 796-2781  
MILLER PLUMBING CO, Address:PO BOX 393 , Phone:(913) 851-1333  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 11/23/2017 12/04/2017
Kim Brennan
14 Identify roof covering material (IRC Section R905)
Corrective Action Required
11/22/2017

Identify roof covering material (IRC Section R905)
20 Footings, column pads, piers and grade beams - reinforcement
Corrective Action Required
11/22/2017

Footings, column pads, piers and grade beams - reinforcement size and spacing. no reinforcement size and spacing for column pads in the garage.
33 Identify braced wall locations and length of braced wall panel(s).
Corrective Action Required
11/22/2017

Identify braced wall locations and length of braced wall panel(s). (IRC Section R602.10)
37 Provide details for any walls over 10 feet in height.
Corrective Action Required
11/22/2017

Provide details for any walls over 10 feet in height. Include stud grade, size, spacing and actual, uninterrupted height. (IRC Section 602.3.1 and Table 602.3(5) & 602.3.1)
36 Identify interior load bearing walls.
Corrective Action Required
11/22/2017

Identify interior load bearing walls. (IRC Section R602) unable to follow the load path
Plot Plan Review Approved 11/23/2017 11/27/2017
Troy Thompson
Rear yard dimension
Corrective Action Required
11/22/2017

The rear yard demision(s) must be provided on the plot plan. -The corner of the covered patio is outside of the rear 30' build line.
Lot elevations
Corrective Action Required
11/22/2017

Existing and finish elevations at all property corners must be provided on the plot plan. -Can you please double check the elvation at the north rear corner of the property
Basement egress
Corrective Action Required
11/22/2017

Basement egress location(s) and elevation of the lowest adjacent grade must be provided on the plot plan.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,460.13 $1,460.13 Paid 12/08/2017
Right of Way Permit Fee $75.00 $75.00 Paid 12/08/2017
8331507-Sewer Connection Fee $600.00 $600.00 Paid 12/08/2017
Water Tap Fee $3,343.00 $3,343.00 Paid 12/08/2017
Water Meter Fee $431.83 $431.83 Paid 12/08/2017
3rd and Subsequent Inspection Fee (Per Hour) $60.00 $60.00 Paid 07/31/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 12/14/2017 (8:00) 12/14/2017 at 8:35 AM 12/14/2017
Underslab Plumbing Inspection - Residential Passed 1/4/2018 1/3/2018 at 1:45 PM 01/03/2018
Sewer Service Inspection - R Passed 1/9/2018 (10:30) 1/9/2018 at 11:05 AM 01/09/2018
Water Service Inspection - R Passed 1/9/2018 (10:30) 1/9/2018 at 11:10 AM 01/09/2018
Piers/Caissons Inspection - Residential Passed 3/2/2018 at 12:50 PM 03/02/2018
Erosion Control Inspection Residential Failed 3/26/2018 03/26/2018
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
03/26/2018
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Gas Service Inspection - Residential Failed 3/26/2018 3/26/2018 at 9:45 AM 03/26/2018
Miscellaneous Correction
Corrective Action Required
03/26/2018
**INSPECTION DENIED DUE TO EROSION CONTROL DEFICIENCY
All Rough Inspection - Residential Not Ready 4/5/2018 at 9:35 AM 04/05/2018
Miscellaneous Correction
Corrective Action Required
04/05/2018
**INSPECTION DENIED DUE TO EROSION CONTROL DEFICIENCY
Electrical Service Inspection Not Ready 4/5/2018 04/05/2018
Miscellaneous Correction
Corrective Action Required
04/05/2018
**INSPECTION DENIED DUE TO EROSION CONTROL DEFICIENCY
Gas Service Inspection - Residential Not Ready 4/5/2018 04/05/2018
Miscellaneous Correction
Corrective Action Required
03/26/2018
**INSPECTION DENIED DUE TO EROSION CONTROL DEFICIENCY
Gas Service Inspection - Residential Passed 4/6/2018 4/6/2018 04/06/2018
Miscellaneous Correction
Resolved
04/06/2018
**INSPECTION DENIED DUE TO EROSION CONTROL DEFICIENCY
Electrical Service Inspection Failed 4/6/2018 4/6/2018 04/06/2018
Miscellaneous Correction
Corrective Action Required
04/05/2018
-Install a listed rebar grounding clamp. The currently install one is for copper rod connection. Avoid copper-iron contact
All Rough Inspection - Residential Failed 4/6/2018 4/6/2018 at 9:20 AM 04/06/2018
Miscellaneous Correction
Corrective Action Required
04/05/2018
FRAMING: -Nail all exterior CSPF wall siding per code -Frame CSPF walls per A/4 plan detail (greatroom and dining) -Expose rear patio framing support -Toe nail joists to wall top plates -Solidblock between joists above i beam and bearing wall -Engineer to address non-continuous 2x6 studs at rear great-room wall -Solidblock underneath lvl beam point loads outside middle bedroom and loft -Joist cut above master bath toilet -Install washer and anchor nut in master bedroom -Cut joist below master toilet -Provide solidblock support underneath foyer and mud lvl beams point loads and underneath dining I beam -Replace defective stud at loft -Non-continuous studs at front bed -Provide attic access to roof space above master bed -Install 4 studs under triple lvl all the way to the I beam in basement -Brace interior walls per plan -Install support post at lvl-lvl connection per plan ELECTRICAL: -Fasten receptacle boxes in master bedroom wall -Bond gas piping -Provide wall receptacle spacing per code near basement wet bar and hallway -Install a receptacle in unfinished space under stoop PLUMBING: -Protect water lines near refrigerator -Vent tub trap per code (above master toilet) -Waste stack clean out adjacent to basement shower shall be accessible MECHANICAL: -Connect duct to bath fan in master bath -Vent basement bath fan **DO NOT INSULATE
All Rough Inspection - Residential Failed 4/10/2018 4/10/2018 at 9:20 AM 04/10/2018
Miscellaneous Correction
Corrective Action Required
04/06/2018
FRAMING: -Nail all exterior CSPF wall siding per code **look at the brace wall nailing detail. Nail to stud and header @ 3" oc just like the garage portal brace wall -Frame CSPF walls per A/4 plan detail (greatroom and dining) -Expose rear patio framing support -Toe nail joists to wall top plates **3-8d toe nails -Engineer to address non-continuous 2x6 studs at rear great-room wall -Cut joist below master toilet **have your engineer look at this and address fix -Provide solidblock support underneath foyer and mud lvl beams point loads and underneath dining I beam -Brace interior walls per plan ELECTRICAL: -Provide wall receptacle spacing per code near basement wet bar **at any point along the wall-except the hall way-there shall be a receptacle within six ft -Install a receptacle in unfinished space under stoop **DO NOT INSULATE
Electrical Service Inspection Failed 4/10/2018 04/10/2018
Miscellaneous Correction
Corrective Action Required
04/06/2018
-Install a listed rebar grounding clamp. The currently install one is for copper rod connection. Avoid copper-iron contact
All Rough Inspection - Residential Failed 4/11/2018 4/11/2018 at 9:45 AM 04/11/2018
Miscellaneous Correction
Corrective Action Required
04/10/2018
-Nail all exterior CSPF wall siding per code **look at the brace wall nailing detail. Nail to stud and header @ 3" oc just like the garage portal brace wall -Frame CSPF walls per A/4 plan detail (greatroom and dining) **have the engineer address. Brace wall requires min double 12" nominal beam; nail siding 3" oc to studs, 3" grid nailing to header; nail 3" oc to rim below; strap at the inner side of the brace walls. -Expose rear patio framing support **how is that ridge beam supported? Is the roof tied down to the posts? I want to see. Have your engineer look at this also **you will have to dig a new pier all the way down to bearing soil -Engineer to address non-continuous 2x6 studs at rear great-room wall **can a single king stud and cross header handle the wind load? -Cut joist below master toilet **have your engineer look at this and address fix -Provide solidblock support underneath foyer and underneath dining I beam **close the return air **need solid support under the rear dining I beam point load **OK TO INSULATE
All Rough Inspection - Residential Failed 4/17/2018 4/17/2018 at 1:15 PM 04/17/2018
Miscellaneous Correction
Corrective Action Required
04/11/2018
-Frame CSPF walls per A/4 plan detail **for the greatroom brace walls, fill in gap between blocking and header and nail blockings to header. Framer should have installed the 1/2"-3/4" filler between the header and the blockings before nailing the straps -Cut joist below master toilet **the engineer letter says a full length joist was added, but it wasn't. Please take a look again -Provide solidblock support underneath foyer **close the return air. Outside the mechanical rm door, look up to the ceiling furdown space. See the framer pulled down the return air pan-sheet so he could add support for the beam above? I want the return air space closed off from the ceiling furdown space **OK TO INSULATE
Electrical Service Inspection Failed 4/23/2018 04/23/2018
Miscellaneous Correction
Corrective Action Required
04/10/2018
-Install a listed rebar grounding clamp.
All Rough Inspection - Residential Failed 4/23/2018 4/23/2018 at 10:25 AM 04/23/2018
Miscellaneous Correction
Corrective Action Required
04/17/2018
-Cut joist below master toilet **complete the plumbing **REINSPECTION FEE ASSESSED. THIS IS THE 6TH TIME THAT I'VE BEEN HERE.
All Rough Inspection - Residential Passed 4/25/2018 4/25/2018 at 10:46 AM 04/25/2018
Miscellaneous Correction
Resolved
04/25/2018
-Cut joist below master toilet **complete the plumbing **REINSPECTION FEE ASSESSED. THIS IS THE 6TH TIME THAT I'VE BEEN HERE.
Piers/Caissons Inspection - Residential Passed 5/11/2018 5/11/2018 at 9:20 AM 05/11/2018
Electrical Service Inspection Passed 5/22/2018 5/22/2018 at 8:45 AM 05/22/2018
Miscellaneous Correction
Resolved
05/22/2018
-Install a listed rebar grounding clamp.
Driveway Inspection Partial 6/12/2018 6/12/2018 at 8:45 AM 06/12/2018
Misc
Informational
04/25/2018
**REINSPECTION FEE ASSESSED.
Informational
06/12/2018
Jeremy Young 06/12/2018 8:56 AM Contractor has sufficient rock base. He will compact one more time before pouring. There is not a sidewalk on the plot plan for the address. I have informed them to use the KCMMB 4K mix.
Driveway Inspection Passed 6/18/2018 at 11:45 AM 06/18/2018
Informational
06/18/2018
Jeremy Young 06/18/2018 11:49 AM Contractor has poured the driveway. There is at least 6" of concrete in the ROW approach. They have used the correct mix and the expansion joint is present.
Occupancy Inspection - Codes Residential Failed 7/27/2018 7/27/2018 at 8:40 AM 07/27/2018
Misc
Corrective Action Required
07/27/2018
-CLEAN STREET -FINAL GRADE, SOD, SPLASHBLOCKS, SUMP PUMP EXTENSION -INSTALL ROOF DRAINAGE SYSTEM -SEAL EXTERIOR: WALL PENETRATIONS, LIGHTS, HOSE BIBB, ETC -EXPOSE WATER METER. LID SHALL BE AT GRADE LEVEL. METER-LID DISTANCE SHALL BE 14"-18" PER STANDARD -SEWER TRACER BOX AND TRACER WIRE SHALL BE ACCESSIBLE AT GRADE LEVEL -SECURE AC WHIP PER CODE -ADD ANOTHER RUNG NEAR TOP OF BASEMENT ESCAPE WINDOW WELL, WITHIN 18" OF THE NEXT ONE BELOW -PROVIDE MIN. 6" CLEARANCE FROM BOTTOM OF SIDING TO BASEMENT ESCAPE WELL BED -ESTABLISH GAS SERVICE -ADJUST GARAGE DOOR CLOSERS -INSTALL EXTENSION RINGS FOR KITCHEN COUNTERTOP RECEPTACLE BOXES RECESS MORE THAN 1/4" FROM WALL SURFACE -SECURE NM CABLE AT HOOD RECEPTACLE -CLOTHES WASHER RECEPTACLE WITHIN SIX FT OF THE SINK SHALL BE GFCI-PROTECTED -PROVIDE MIN. 12" CLEARANCE FROM LED LUMINAIRE TO SHELF AT LOFT CLOSET PER NEC 410.16(C)(1) FOR SURFACE-MOUNTED LED LUMINAIRE -SECURE WATER HEATER RACEWAY PER CODE -ANCHOR COLUMN TO FLOOR IN MECH. RM -PROVIDE AFCI PROTECTION FOR THE SMOKE ALARM CIRCUIT -SECURE ALL WIRING AT CONNECTIONS TO SERVICE PANEL
Occupancy Inspection - Codes Residential Temporary C of O 8/1/2018 at 9:30 AM 08/01/2018
Misc
Corrective Action Required
07/27/2018
-FINAL GRADE, SOD, SPLASHBLOCKS, SUMP PUMP EXTENSION -INSTALL ROOF DRAINAGE SYSTEM -SEAL EXTERIOR: WALL PENETRATIONS, LIGHTS, HOSE BIBB, ETC -EXPOSE WATER METER. LID SHALL BE AT GRADE LEVEL. METER-LID DISTANCE SHALL BE 14"-18" PER STANDARD -SEWER TRACER BOX AND TRACER WIRE SHALL BE ACCESSIBLE AT GRADE LEVEL
Erosion Control Inspection Residential Passed 08/28/2018
DCM2 ESC DEFICIENT INSTALLATION
Resolved
08/28/2018
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Occupancy Inspection - Codes Residential Full C of O 9/12/2018 9/12/2018 at 8:30 AM 09/12/2018
Misc
Resolved
09/12/2018
-FINAL GRADE, SOD, SPLASHBLOCKS, SUMP PUMP EXTENSION
Documents & Images
Date Uploaded File Type Document Name
11/22/2017 Letter Codes Residential Plan Review
11/22/2017 Letter Codes Residential Plan Review
12/08/2017 Receipt Receipt for transaction: 2017-007576
12/08/2017 Letter Codes Building Permit
12/08/2017 Plot Plan DOC120817-006
12/14/2017 Letter Inspection Summary
01/03/2018 Letter Inspection Summary
01/09/2018 Letter Inspection Summary
03/02/2018 Letter Inspection Summary
03/26/2018 Letter Inspection Summary
04/05/2018 Letter Inspection Summary
04/06/2018 Letter Inspection Summary
04/10/2018 Letter Inspection Summary
04/11/2018 Letter Inspection Summary
04/13/2018 Engineer Report/Study DOC041318-030
04/17/2018 Letter Inspection Summary
04/23/2018 Letter Re-Inspection Fee
04/23/2018 Letter Inspection Summary
04/25/2018 Letter Inspection Summary
05/11/2018 Letter Inspection Summary
05/22/2018 Letter Inspection Summary
06/12/2018 Letter DE-Daily Inspection Summary
06/18/2018 Letter DE-Daily Inspection Summary
07/27/2018 Letter Inspection Summary
07/31/2018 Receipt Receipt for transaction: 2018-005363
08/01/2018 Letter Codes Temporary Certificate of Occupancy
09/05/2018 Letter Codes 10 Day Letter
09/12/2018 Letter Field Certificate of Occupancy
09/13/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home