Permit Application Status

PRRES20131169


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20131169
Building Permit - Residential
Certificate of Occupancy
JOHN KNOX VILLAGE
NEW 3 OR 4 FAMILY
3PLEX
06/12/2013
06/28/2013
05/23/2014
Locations
Contacts
LARRY HARKRADER CONSTRUCTION, Address:401 NW MURRAY RD, Phone:(816) 607-7191  
AFC HEATING AND COOLING, Address:824 NW MAIN ST , Phone:(816) 347-8388  
S & L ELECTRIC INC, Address:1301 S POWELL, Phone:(816) 796-6859  
CENTURY PLUMBING, Address:14001 CENTURY LN, Phone:(816) 765-6066  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 06/14/2013 06/21/2013
Codes Admin
Plot Plan Review Approved 06/14/2013 06/13/2013
Gene Williams, P.E.
Plot Plan Review (P&D) Approved 06/14/2013 06/13/2013
Jennifer Thompson
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New 3 or 4 Family $1,416.72 $1,416.72 Paid 06/28/2013
$1,416.72
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 7/31/2013 (3:30) 7/31/2013 at 12:00 AM 07/31/2013
Underslab Plumbing Inspection - Residential Not Ready 8/23/2013 8/23/2013 at 12:00 AM 08/23/2013
Misc
Corrective Action Required
08/23/2013
LSCO SEC 7-142; IBC 106: PERMIT DRAWINGS NOT FOUND ON SITE. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT PRINTS.
Underslab Plumbing Inspection - Residential Not Ready 8/27/2013 8/27/2013 at 12:00 AM 08/27/2013
Misc
Corrective Action Required
08/23/2013
LSCO SEC 7-142; IBC 106: PERMIT DRAWING SET DOES NOT INCLUDE A PLUMBING PLAN. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT PRINTS.
Underslab Plumbing Inspection - Residential Passed 8/27/2013 at 12:00 AM 08/27/2013
Misc
Resolved
08/27/2013
LSCO SEC 7-142; IBC 106: PERMIT DRAWING SET DOES NOT INCLUDE A PLUMBING PLAN. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT PRINTS.
Sewer Service Inspection - R Not Ready 9/3/2013 (3:00) 9/3/2013 at 12:00 AM 09/03/2013
Misc
Corrective Action Required
09/03/2013
LSCO SEC 7-142; IBC 106: PERMIT DRAWINGS NOT FOUND ON SITE. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT PRINTS.
Sewer Service Inspection - R Partial 9/4/2013 (9:30) 9/4/2013 at 12:00 AM 09/04/2013
Misc
Resolved
09/04/2013
LSCO SEC 7-142; IBC 106: PERMIT DRAWINGS NOT FOUND ON SITE. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT PRINTS.
Misc
Partial Correction
09/04/2013
OK TO COVER WHEN READY SANITARY SEWER SERVICE INSTALLATION FROM BUILDING ENTRY TO CONNECTION TO STUB AT UNIT B;
Water Service Inspection - R Not Ready 9/4/2013 (1:45) 9/4/2013 at 12:00 AM 09/04/2013
Sewer Service Inspection - R Passed 9/4/2013 (1:45) 9/4/2013 at 12:00 AM 09/04/2013
Misc
Resolved
09/04/2013
OK TO COVER WHEN READY SANITARY SEWER SERVICE INSTALLATION FROM BUILDING ENTRY TO CONNECTION TO STUB AT UNITS A(NO), B(CTR) AND C(SO)
Water Service Inspection - R Passed 9/5/2013 9/5/2013 at 12:00 AM 09/05/2013
Misc
Resolved
09/05/2013
OK TO COVER WHEN READY WATER SERVICE INSTALLATION: UNIT "A" FROM TAP TO METER WELL SET TO ELEVATION TO BUILDING ENTRY; UNITS "B" & "C" FROM BUILDING ENTRY TO COUPLING TO EXSTG SERVICE LINE EXITING RE-USED EXSTG METER/WELL
All Rough Inspection - Residential Partial 9/27/2013 9/27/2013 at 12:00 AM 09/27/2013
Misc
Partial Correction
09/27/2013
INSPECTED LOCATIONS OF ANCHOR BOLTS @: 9/27/13 SOUTH TRIPLEX UNIT;
All Rough Inspection - Residential Not Ready 9/30/2013 at 12:00 AM 09/30/2013
Misc
Partial Correction
09/27/2013
INSPECTED LOCATIONS OF ANCHOR BOLTS @: 9/27/13 SOUTH TRIPLEX UNIT; 9/30/13 INFORMAL OBSERVATIONS OF FRAMING IN PROGRESS;
Rough Framing Inspection - Residential Partial 10/4/2013 at 12:00 AM 10/04/2013
Misc
Partial Correction
10/04/2013
10/4/13 INTERIM OBSERVATION OF FRAMING;
All Rough Inspection - Residential Failed 12/20/2013 12/20/2013 at 12:00 AM 12/20/2013
Misc
Partial Correction
09/30/2013
INSPECTED LOCATIONS OF ANCHOR BOLTS @: 9/27/13 SOUTH TRIPLEX UNIT; 9/30/13 INFORMAL OBSERVATIONS OF FRAMING IN PROGRESS;
Misc
Corrective Action Required
12/20/2013
UNIT "A": 1) COMPLETE LEVEL-TO-LEVEL FIRE-BLOCKING ABOVE LAUNDRY AREA ADJACENT TO DRYER VENT 2) IPC 604.9 & IRC P2903.5 REQUIRE WATER HAMMER ARRESTORS AT QUICK-CLOSING VALVES WITH NO EXCEPTION FOR PEX SYSTEMS.
All Rough Inspection - Residential Partial 12/30/2013 12/30/2013 at 12:00 AM 12/30/2013
Misc
Partial Correction
12/20/2013
INSPECTED LOCATIONS OF ANCHOR BOLTS @: 9/27/13 SOUTH TRIPLEX UNIT; 9/30/13 INFORMAL OBSERVATIONS OF FRAMING IN PROGRESS;
Misc
Resolved
12/30/2013
UNIT "A": 2) IPC 604.9 & IRC P2903.5 REQUIRE WATER HAMMER ARRESTORS AT QUICK-CLOSING VALVES WITH NO EXCEPTION FOR PEX SYSTEMS.
All Rough Inspection - Residential Partial 12/30/2013 at 12:00 AM 12/30/2013
Misc
Partial Correction
12/30/2013
INSPECTED LOCATIONS OF ANCHOR BOLTS @: 9/27/13 SOUTH TRIPLEX UNIT; 9/30/13 INFORMAL OBSERVATIONS OF FRAMING IN PROGRESS;
Misc
Partial Correction
12/30/2013
OK TO COVER WHEN READY WALLS AND CEILINGS AT: UNIT "A"
Gas Service Inspection - Residential Partial 1/13/2014 1/13/2014 at 12:00 AM 01/13/2014
Misc
Partial Correction
01/13/2014
GAS PIPING PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN. RELEASE GAS SERVICE FOLLOWING UNIT: A;
Gas Piping Inspection - Residential Partial 1/13/2014 at 12:00 AM 01/13/2014
Misc
Partial Correction
01/13/2014
NO ISSUES FOUND ON GAS PIPING MATERIAL AND WORKMANSHIP AT UNIT(S): A;
Gas Piping Inspection - Residential Partial 1/16/2014 at 12:00 AM 01/16/2014
Misc
Partial Correction
01/13/2014
NO ISSUES FOUND ON GAS PIPING MATERIAL AND WORKMANSHIP. GAS PIPING PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN. AT UNIT(S): A; B; CENTRAL METERING. GAS SERVICE RELEASE NOT REQUIRED.
All Rough Inspection - Residential Failed 1/16/2014 at 12:00 AM 01/16/2014
Misc
Resolved
01/16/2014
INSPECTED LOCATIONS OF ANCHOR BOLTS @: 9/27/13 SOUTH TRIPLEX UNIT; 9/30/13 INFORMAL OBSERVATIONS OF FRAMING IN PROGRESS;
Misc
Partial Correction
12/30/2013
OK TO COVER WHEN READY WALLS AND CEILINGS AT: UNIT "A";
Misc
Corrective Action Required
01/16/2014
AT UNIT B: IPC 905.2; IRC P3104.2 GRADING OF VENT PIPING TO DRAIN
All Rough Inspection - Residential Partial 1/17/2014 1/17/2014 at 12:00 AM 01/17/2014
Misc
Partial Correction
01/16/2014
OK TO COVER WHEN READY WALLS AND CEILINGS AT: UNIT "A"; UNIT "B";
Misc
Resolved
01/17/2014
AT UNIT B: IPC 905.2; IRC P3104.2 GRADING OF VENT PIPING TO DRAIN
All Rough Inspection - Residential Not Ready 1/24/2014 1/24/2014 at 12:00 AM 01/24/2014
Misc
Partial Correction
01/17/2014
OK TO COVER WHEN READY WALLS AND CEILINGS AT: UNIT "A"; UNIT "B";
All Rough Inspection - Residential Failed 1/27/2014 1/27/2014 at 12:00 AM 01/27/2014
Misc
Partial Correction
01/24/2014
OK TO COVER WHEN READY WALLS AND CEILINGS AT: UNIT "A"; UNIT "B";
Misc
Corrective Action Required
01/27/2014
AT UNIT "C": FRE-BLOCKING -- ENSURE NO GAPS IN FRAMING ABOVE LAUNDRY RECESS WALL.
Misc
Corrective Action Required
01/27/2014
AT UNIT "C": AT VANITY LOCATION AT NORTH WALL BEARING WALL STUDS ARE BORED ~ 1-7/8". 40% MAX ALLOWABLE IS 1-3/8". LISTED STUD SHOE IS APPROVABLE TO CORRECT.
Misc
Corrective Action Required
01/27/2014
AT UNIT "C": NM ELECT CABLE BORED THRU CORNER STUDS @ KIT SE REQUIRE SHIELD PLATE PROTECTION.
All Rough Inspection - Residential Passed 1/28/2014 1/28/2014 at 12:00 AM 01/28/2014
Misc
Resolved
01/28/2014
OK TO COVER WHEN READY WALLS AND CEILINGS AT: UNIT "A"; UNIT "B"; UNIT "C"
Misc
Resolved
01/28/2014
AT UNIT "C": FRE-BLOCKING -- ENSURE NO GAPS IN FRAMING ABOVE LAUNDRY RECESS WALL.
Misc
Resolved
01/28/2014
AT UNIT "C": AT VANITY LOCATION AT NORTH WALL BEARING WALL STUDS ARE BORED ~ 1-7/8". 40% MAX ALLOWABLE IS 1-3/8". LISTED STUD SHOE IS APPROVABLE TO CORRECT.
Misc
Resolved
01/28/2014
AT UNIT "C": NM ELECT CABLE BORED THRU CORNER STUDS @ KIT SE REQUIRE SHIELD PLATE PROTECTION.
Gas Piping Inspection - Residential Not Ready 1/29/2014 1/29/2014 at 12:00 AM 01/29/2014
Misc
Partial Correction
01/16/2014
NO ISSUES FOUND ON GAS PIPING MATERIAL AND WORKMANSHIP. GAS PIPING PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN. AT UNIT(S): A; B; CENTRAL METERING. GAS SERVICE RELEASE NOT REQUIRED.
Misc
Corrective Action Required
01/29/2014
LSCO 7-608: GAS PIPING PRESSURE TEST BELOW LEE'S SUMMIT 10 PSI REQUIRED MINIMUM. GAUGE READS 3.5 PSI.
Gas Piping Inspection - Residential Partial 1/30/2014 1/30/2014 at 12:00 AM 01/30/2014
Misc
Partial Correction
01/29/2014
GAS PIPING PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN. AT UNIT(S): A; B; C CENTRAL METERING. GAS SERVICE RELEASE NOT REQUIRED. CRAWL SPACE PIPING SUBJECT TO INSPECTION WHEN ALL UNDER-FLOOR SYSTEMS ARE READY.
Misc
Resolved
01/30/2014
LSCO 7-608: GAS PIPING PRESSURE TEST BELOW LEE'S SUMMIT 10 PSI REQUIRED MINIMUM. GAUGE READS 3.5 PSI.
Electrical Service Inspection Not Ready 2/27/2014 at 12:00 AM 02/27/2014
Misc
Corrective Action Required
02/27/2014
UFER GROUND NOT FOUND
Electrical Service Inspection Partial 2/28/2014 at 12:00 AM 02/28/2014
Misc
Corrective Action Required
02/27/2014
UFER GROUND TERMINATION NOT FOUND
Rough Framing Inspection - Residential Passed 10/4/2013 at 12:00 AM 03/13/2014
Misc
Resolved
03/13/2014
10/4/13 INTERIM OBSERVATION OF FRAMING;
Occupancy Inspection - Codes Residential Failed 3/13/2014 3/13/2014 at 12:00 AM 03/13/2014
Misc
Partial Correction
03/13/2014
FIRE/SECURITY SYSTEM SET-UP AND TESTING IN PROGRESS BY SPECIALTY CONTRACTOR.
Misc
Corrective Action Required
03/13/2014
SECURE PEX TUBING AT: - WATER SERIVCE RISER IN MECHANICAL ROOM - AT VALVES UNDER VANITY @ NORTH WALL
Misc
Corrective Action Required
03/13/2014
UFER G.E.C. TERMINATION TO BE ACCESSIBLE AND LOCATED.
Misc
Corrective Action Required
03/13/2014
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. SEE ALL AT KITCHEN BACKSPLASH.
Misc
Corrective Action Required
03/13/2014
NEC 422.31B CIRCUIT BREAKERS FOR APPLIANCES RATED OVER 300 VOLT AMPS OR 1/8 HORSEPOWER: IF TO SERVE AS DISCONNECT MUST BE LOCKABLE IF NOT WITHIN SIGHT OF PANELBOARD.
Misc
Corrective Action Required
03/13/2014
IRC P2717.3 BACKFLOW PREVENTION AT DISHWASHER: DRAIN DISCHARGE LINE MUST RISE TO UNDERSIDE OF COUNTER AND BE SECURELY FASTENED (OR APPROVED ALTERNATE MEANS TO MAINTAIN HIGH POINT IN DISCHARGE LINE.)
Misc
Corrective Action Required
03/13/2014
AC CONDENSER CIRCUIT IS OVER-AMPED PER STICKER ON UNIT: 30A VS 25A
Misc
Corrective Action Required
03/13/2014
AT CRAWLSPACE SW TWO COPPER WATER PIPE RUNS HAVE STRAPS DETACHED FROM STRUCTURE.
Occupancy Inspection - Codes Residential Not Ready 3/14/2014 3/14/2014 at 12:00 AM 03/14/2014
Misc
Partial Correction
03/13/2014
FIRE/SECURITY SYSTEM SET-UP AND TESTING IN PROGRESS BY SPECIALTY CONTRACTOR.
Misc
Resolved
03/14/2014
SECURE PEX TUBING AT: - WATER SERIVCE RISER IN MECHANICAL ROOM - AT VALVES UNDER VANITY @ NORTH WALL
Misc
Resolved
03/14/2014
UFER G.E.C. TERMINATION TO BE ACCESSIBLE AND LOCATED.
Misc
Resolved
03/14/2014
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. SEE ALL AT KITCHEN BACKSPLASH.
Misc
Resolved
03/14/2014
NEC 422.31B CIRCUIT BREAKERS FOR APPLIANCES RATED OVER 300 VOLT AMPS OR 1/8 HORSEPOWER: IF TO SERVE AS DISCONNECT MUST BE LOCKABLE IF NOT WITHIN SIGHT OF PANELBOARD.
Misc
Resolved
03/14/2014
IRC P2717.3 BACKFLOW PREVENTION AT DISHWASHER: DRAIN DISCHARGE LINE MUST RISE TO UNDERSIDE OF COUNTER AND BE SECURELY FASTENED (OR APPROVED ALTERNATE MEANS TO MAINTAIN HIGH POINT IN DISCHARGE LINE.)
Misc
Resolved
03/14/2014
AC CONDENSER CIRCUIT IS OVER-AMPED PER STICKER ON UNIT: 30A VS 25A
Misc
Resolved
03/14/2014
AT CRAWLSPACE SW TWO COPPER WATER PIPE RUNS HAVE STRAPS DETACHED FROM STRUCTURE.
Misc
Partial Correction
03/14/2014
OCCUPANCY STATUS: UNIT A OK FOR OCCUPANCY CONTINGENT ON: - SECURE PEX TO STRUCTURE OR CABINET NEAR VALVE UNDER VANITY @ NORTH WALL - ADDRESS IDENTIFICATION TO BE RE-AFFIXED AFTER EXTERIOR PAINTING IS COMPLETED - FINISH SITEWORK TO BE COMPLETED - EROSION CONTROL TO BE MAINTAINED AND STREET TO BE KEPT CONSTRUCTION CLEAN
Occupancy Inspection - Codes Residential Not Ready 4/9/2014 4/9/2014 at 12:00 AM 04/09/2014
Misc
Partial Correction
03/14/2014
FIRE/SECURITY SYSTEM SET-UP AND TESTING IS RESPONSIBILITY OF GENERAL CONTRACTOR AND JKV BY SPECIALTY CONTRACTOR.
Misc
Partial Correction
03/14/2014
FOLLOWING UNITS OK FOR OCCUPANCY: UNIT A; UNIT B AFTER ELECT RECPT AT CLOTHES DRYER IS INSTALLED; CONTINGENT ON: - FINISH SITEWORK TO BE COMPLETED - EROSION CONTROL TO BE MAINTAINED AND STREET TO BE KEPT CONSTRUCTION CLEAN
Occupancy Inspection - Codes Residential Failed 4/24/2014 4/24/2014 at 12:00 AM 04/24/2014
Misc
Partial Correction
04/09/2014
FIRE/SECURITY SYSTEM SET-UP AND TESTING IS RESPONSIBILITY OF GENERAL CONTRACTOR AND JKV BY SPECIALTY CONTRACTOR.
Misc
Partial Correction
04/09/2014
FOLLOWING UNITS OK FOR OCCUPANCY: UNIT A; UNIT B ; CONTINGENT ON: - FINISH SITEWORK TO BE COMPLETED - EROSION CONTROL TO BE MAINTAINED AND STREET TO BE KEPT CONSTRUCTION CLEAN
Misc
Corrective Action Required
04/24/2014
UNIT C: - UNIT ADDRESS NOT AFFIXED - EXTERIOR & CRAWL SPACE DEFERRED DUE TO MUD - LATERALLY SUPPORT COPPER WATER PIPES AT FURN ROOM
Occupancy Inspection - Codes Residential Temporary C of O 5/7/2014 5/7/2014 at 12:00 AM 05/07/2014
Misc
Partial Correction
04/24/2014
FIRE/SECURITY SYSTEM SET-UP AND TESTING IS RESPONSIBILITY OF GENERAL CONTRACTOR AND JKV BY SPECIALTY CONTRACTOR.
Misc
Partial Correction
04/24/2014
FOLLOWING UNITS OK FOR OCCUPANCY: UNIT A; UNIT B ; C CONTINGENT ON: - FINISH SITEWORK TO BE COMPLETED - EROSION CONTROL TO BE MAINTAINED AND STREET TO BE KEPT CONSTRUCTION CLEAN
Misc
Resolved
05/07/2014
UNIT C: - UNIT ADDRESS NOT AFFIXED - EXTERIOR & CRAWL SPACE DEFERRED DUE TO MUD - LATERALLY SUPPORT COPPER WATER PIPES AT FURN ROOM
Plot Plan Inspection Passed 5/23/2014 at 12:00 AM 05/23/2014
Occupancy Inspection - Codes Residential Full C of O 5/23/2014 at 12:00 AM 05/23/2014
Misc
Resolved
05/23/2014
FIRE/SECURITY SYSTEM SET-UP AND TESTING IS RESPONSIBILITY OF GENERAL CONTRACTOR AND JKV BY SPECIALTY CONTRACTOR.
Misc
Resolved
05/23/2014
FOLLOWING UNITS OK FOR OCCUPANCY: UNIT A; UNIT B ; C CONTINGENT ON: - FINISH SITEWORK TO BE COMPLETED - EROSION CONTROL TO BE MAINTAINED AND STREET TO BE KEPT CONSTRUCTION CLEAN
Electrical Service Inspection Passed 5/23/2014 at 12:00 AM 05/23/2014
Misc
Resolved
05/23/2014
UFER GROUND TERMINATION NOT FOUND
Gas Piping Inspection - Residential Passed 5/23/2014 at 12:00 AM 05/23/2014
Misc
Partial Correction
01/30/2014
GAS PIPING PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN. AT UNIT(S): A; B; C CENTRAL METERING. GAS SERVICE RELEASE NOT REQUIRED. CRAWL SPACE PIPING SUBJECT TO INSPECTION WHEN ALL UNDER-FLOOR SYSTEMS ARE READY.
Miscellaneous Inspection Passed 5/23/2014 at 12:00 AM 05/27/2014
Documents & Images
Date Uploaded File Type Document Name
06/28/2013 Letter Building Permit
07/31/2013 Letter Inspection Summary
08/23/2013 Letter Inspection Summary
08/27/2013 Letter Inspection Summary
09/03/2013 Letter Inspection Summary
09/04/2013 Letter Inspection Summary
09/05/2013 Letter Inspection Summary
12/20/2013 Letter Inspection Summary
12/30/2013 Letter Inspection Summary
12/31/2013 Letter Inspection Summary
01/13/2014 Letter Inspection Summary
01/16/2014 Letter Inspection Summary
01/17/2014 Letter Inspection Summary
01/27/2014 Letter Inspection Summary
01/28/2014 Letter Inspection Summary
01/29/2014 Letter Inspection Summary
01/30/2014 Letter Inspection Summary
02/28/2014 Letter Inspection Summary
03/13/2014 Letter Inspection Summary
03/14/2014 Letter Inspection Summary
04/09/2014 Letter Inspection Summary
04/24/2014 Letter Inspection Summary
05/07/2014 Letter Codes Temporary Certificate of Occupancy
05/23/2014 Letter Field Certificate of Occupancy
05/27/2014 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home