Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Plan Review
|
Approved
|
06/26/2023
|
06/26/2023
|
|
Jim Eden
|
|
Miscellaneous Correction
Indicate which edition of the IFC you are designing to. The City of Lee's Summit has adopted the 2018 International Fire Code with local amendments.
|
|
Construction documents - Fire protection systems
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide booth specifications and shop drawings for the fire suppression system (not indicated).
|
|
Miscellaneous Correction
Where in the building is the new paaint booth going? The application only stated it is replacing a prep station.
|
|
Miscellaneous Correction
2404.7.6 Termination point. The termination point for
exhaust ducts discharging to the atmosphere shall be not less than the following distances:
1. Ducts conveying explosive or flammable vapors,
fumes or dusts: 30 feet (9144 mm) from the lot line;
10 feet (3048 mm) from openings into the building;
6 feet (1829 mm) from exterior walls and roofs; 30 feet (9144 mm) from combustible walls or openings
into the building that are in the direction of the
exhaust discharge; 10 feet (3048 mm) above adjoining
grade.
Confirm how this requirement will be met.
|
|
|
Building Plan Review
|
Approved
|
06/26/2023
|
06/22/2023
|
|
Joe Frogge
|
|
IMC 510.7 -Hazardous exhaust penetrations
2018 IMC 510.6.7 Ducts. Hazardous exhaust duct systems shall extend directly to the exterior of the building and shall not extend into or through ducts and plenums.
Action required: Comment is informational. HVAC information not provided. If duct is routed through a plenum a chase will have to be constructed. To be field verified.
|
|
IMC 510.8 Hazardous exhaust suppression
2018 IMC 510.8 Suppression required. Ducts shall be protected with an approved automatic fire suppression system installed in accordance with the International Building Code. (see code for exceptions)
Action required: Comment is informational. Reference Fire Plan Review.
|
|
IMC 510.9 Hazardous exhaust duct construction
2018 IMC 510.9 Duct Construction. Ducts used to convey hazardous exhaust shall be constructed of materials approved for installation in such an exhaust system and shall comply with one of the following:
1. Ducts shall be constructed of approved G90 Galvanized sheet steel, with a minimum nominal thickness as specified in Table 510.9.
2. Ducts used in systems exhausting nonflammable corrosive fumes or vapors shall be constructed of nonmetallic materials that exhibit a flame spread index of 25 or less and a smoke-developed index of 50 or less when tested in accordance with ASTM E84 or UL 723 and that are listed and labeled for the application.
---Where the products being exhausted are detrimental to the duct material, the ducts shall be constructed of alternative materials that are compatible with the exhaust.
Action required: Per Table 510.9 exhaust duct must be minimum 16 gage. Revise designs to comply.
|
|
|
Licensed Contractors
|
Approved
|
06/26/2023
|
06/22/2023
|
|
Joe Frogge
|
|
LC - MEP Subs
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
(Dalton Electric not currently licensed with us)
|
|
|
Fire Plan Review
|
Rejected
|
05/18/2023
|
05/21/2023
|
|
Jim Eden
|
|
Miscellaneous Correction
Corrective Action Required
Indicate which edition of the IFC you are designing to. The City of Lee's Summit has adopted the 2018 International Fire Code with local amendments.
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide booth specifications and shop drawings for the fire suppression system (not indicated).
|
|
Miscellaneous Correction
Corrective Action Required
Where in the building is the new paaint booth going? The application only stated it is replacing a prep station.
|
|
Miscellaneous Correction
Corrective Action Required
2404.7.6 Termination point. The termination point for
exhaust ducts discharging to the atmosphere shall be not less than the following distances:
1. Ducts conveying explosive or flammable vapors,
fumes or dusts: 30 feet (9144 mm) from the lot line;
10 feet (3048 mm) from openings into the building;
6 feet (1829 mm) from exterior walls and roofs; 30 feet (9144 mm) from combustible walls or openings
into the building that are in the direction of the
exhaust discharge; 10 feet (3048 mm) above adjoining
grade.
Confirm how this requirement will be met.
|
|
|
Building Plan Review
|
Rejected
|
05/18/2023
|
05/17/2023
|
|
Joe Frogge
|
|
IMC 510.7 -Hazardous exhaust penetrations
Corrective Action Required
2018 IMC 510.6.7 Ducts. Hazardous exhaust duct systems shall extend directly to the exterior of the building and shall not extend into or through ducts and plenums.
Action required: Comment is informational. HVAC information not provided. If duct is routed through a plenum a chase will have to be constructed. To be field verified.
|
|
IMC 510.8 Hazardous exhaust suppression
Corrective Action Required
2018 IMC 510.8 Suppression required. Ducts shall be protected with an approved automatic fire suppression system installed in accordance with the International Building Code. (see code for exceptions)
Action required: Comment is informational. Reference Fire Plan Review.
|
|
IMC 510.9 Hazardous exhaust duct construction
Corrective Action Required
2018 IMC 510.9 Duct Construction. Ducts used to convey hazardous exhaust shall be constructed of materials approved for installation in such an exhaust system and shall comply with one of the following:
1. Ducts shall be constructed of approved G90 Galvanized sheet steel, with a minimum nominal thickness as specified in Table 510.9.
2. Ducts used in systems exhausting nonflammable corrosive fumes or vapors shall be constructed of nonmetallic materials that exhibit a flame spread index of 25 or less and a smoke-developed index of 50 or less when tested in accordance with ASTM E84 or UL 723 and that are listed and labeled for the application.
---Where the products being exhausted are detrimental to the duct material, the ducts shall be constructed of alternative materials that are compatible with the exhaust.
Action required: Per Table 510.9 exhaust duct must be minimum 16 gage. Revise designs to comply.
|
|
|
Licensed Contractors
|
Rejected
|
05/18/2023
|
05/16/2023
|
|
Joe Frogge
|
|
LC - MEP Subs
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
(Dalton Electric not currently licensed with us)
|
|
|