Summary
PRCOM20215285
Building Permit - Commercial
Certificate of Occupancy
CHAPEL RIDGE TOWNHOMES LLC
NEW MULTI-FAMILY
NEW 4PLEX
10/08/2021
01/21/2022
10/07/2022
Locations
Contacts
CAPITAL CONSTRUCTION SERVICES LLC, Address:2642 NE HAGAN RD, Phone:(816) 875-0018  
DROTHFUSS@CAPITALCONST.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
INHOME SYSTEMS LLC, Address:510 MISSION RD SW, Phone:(816) 372-0483  
A BRIGHT PLUMBING LLC, Address:201 NE WOODBURY DR, Phone:(816) 867-4540  
DAVIDSON ARCHITECTURE & ENGINEERING, Address:4301 INDIAN CREEK PKWY, Phone:(913) 451-9390  
CHAPEL RIDGE TOWNHOMES LLC, Address:3701 NE AKIN DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 01/07/2022
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
8331506-EFHB Maybrook, Full $1,874.84 $1,874.84 Paid 01/20/2022
8331507-Sewer Connection Fee $1,320.00 $1,320.00 Paid 01/20/2022
7232302-Residential Excise Tax Fee $2,437.12 $2,437.12 Paid 01/20/2022
9110078-Valuation Fee for New 3 or 4 Family $2,349.12 $2,349.12 Paid 01/20/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Passed 3/2/2022 (3:15) 3/2/2022 03/02/2022
Underslab Plumbing Inspection - Commercial Passed 3/14/2022 3/14/2022 03/14/2022
Rated Assembly Inspection Partial 5/23/2022 5/23/2022 05/23/2022
Misc
Informational
05/23/2022
-Attic firewall-1st layer ok
Rated Assembly Inspection Partial 5/25/2022 5/25/2022 05/25/2022
Misc
Informational
05/23/2022
-Attic firewall-1st layer ok, 2nd layer ok for fire tape
All Rough Inspection - Commercial Failed 6/27/2022 6/27/2022 06/27/2022
Misc
Corrective Action Required
06/27/2022
**RESTORE EROSION CONTROL ALONG THE STREET ALL: -Fire caulk penetration of firewall. No taping at penetrations -Reinstall all studs at firewall -Securely support SE and NM wiring at 4.5 ft oc, not just laying them on framing -Make sure that the kitchen countertop receptacle spacing is per code UNIT A: -Fb half bathroom wall from soffit -Vent all bathroom fans to outdoor -Master shower trap weir is above vent connection -Add more ceiling support above kitchen -Fb holes in floor above kitchen&dining -Protect plumbing at laundry/bathroom wall -Provide furnace condensate drain per code -Provide combustion air openings per code -Complete water heater b-vent -Securely faster wiring at switch box outside master bedroom door -Have engineer address torn out gussets at girder truss above master bedroom -Protect wiring at bottom wall plate in master bathroom -Strap wall top plates lapped less than 24” in hallway bathroom and bedroom closet -Protect AC coolant line at closet top plate with 16 gauge metal plate -Gas piping has no pressure UNIT B: -Fill in gaps at front entry door strike plate side and hinges per security code -Reinstall ceiling light box above dining -Support plumbing at 4 ft or less above dining -Nail corner studs per code near slide door -Support plumbing at 4 ft or less above master bathroom; slope vent piping toward drain -Protect plumbing at master bathroom sink exterior wall -Vent master bathroom fan to outdoor -Provide furnace condensate drain per code -Provide combustion air openings per code -Protect plumbing at laundry/bathroom bottom wall plate; Don’t leave gap between protection plates -Protect AC line with 16 gauge metal plate UNIT C: -Master shower trap weir is above vent connection -Protect plumbing at master bathroom sink exterior wall -Support 3” vent pipe at 4 ft or less -Provide combustion air openings per code -Fb laundry/bathroom top&bottom wall plates -Provide clearance min 1” from b-vent -Protect AC line with 16 gauge metal plate -Vent rear bathroom fan to outdoor -Fb all wall plate penetrations UNIT D: -Wiring above entry door? -Vent all bathroom fans to outdoor -Nail together girder truss above master bedroom -Fb wall plate penetration at master shower -Patch hole at laundry exterior wall -Protect wiring at 2nd fl hallway bottom wall plate -Reinstall studs at bedroom/bathroom wall -Protect AC line with 16 gauge metal plate -Strap wall top plates lapped less than 24” in hallway bathroom and bedroom closet -Provide min ten psi gas piping test pressure **OK TO INSULATE
Gas Service Inspection - Commercial Failed 6/27/2022 06/27/2022
Misc
Corrective Action Required
06/27/2022
-Units A and D fail
Electrical Service Inspection Passed 6/29/2022 6/29/2022 06/29/2022
All Rough Inspection - Commercial Failed 7/7/2022 7/7/2022 07/07/2022
Misc
Corrective Action Required
06/27/2022
ALL: -Fire caulk penetration of firewall. No taping at penetrations -Provide combustion air openings per code Protect dryer duct at wall plate penetration with min 16 gauge thick metal plate UNIT A: -Vent all bathroom fans to outdoor -Provide furnace auxiliary condensate drain pan per code -Complete water heater b-vent **provide min 1” clearance from combustible -Have engineer address torn out gussets at girder truss above master bedroom -Strap wall top plates lapped less than 24” in hallway bathroom and bedroom closet -Protect AC coolant line at closet top plate with 16 gauge metal plate -Fb opening at wall top plate -Gas piping has no pressure UNIT B: -Support plumbing at 4 ft or less above dining -Vent master bathroom fan to outdoor -Provide furnace auxiliary condensate drain pan per code -Protect plumbing at laundry/bathroom bottom wall plate; Don’t leave gap between protection plates UNIT C: -Support 3” vent pipe at 4 ft or less **above laundry -Fb laundry/bathroom top&bottom wall plates -Provide clearance min 1” from b-vent **move the duct away so it’s not touching the b-vent UNIT D: -Fb wall plate penetration at master shower -Protect AC line with 16 gauge metal plate -Strap wall top plates lapped less than 24” in bedroom closet -Provide min ten psi gas piping test pressure **OK TO INSULATE
Rated Assembly Inspection Partial 7/11/2022 7/11/2022 07/11/2022
Misc
Informational
05/25/2022
-Attic firewall-ok -Dwelling firewall-1st layer ok
Gas Service Inspection - Commercial Passed 7/12/2022 07/12/2022
Misc
Resolved
07/12/2022
-Units A and D fail
All Rough Inspection - Commercial Failed 7/12/2022 7/12/2022 07/12/2022
Misc
Corrective Action Required
07/07/2022
-Fire caulk penetration of firewall. No taping at penetrations -Install b-vent shield in attic -Provide furnace auxiliary condensate drain pan per code -Have engineer address torn out gussets at girder truss above master bedroom of unit A **nail per engineer letter -Provide clearance min 1” from b-vent **move the duct away so it’s not touching the b-vent **OK TO INSULATE
All Rough Inspection - Commercial Passed 7/19/2022 7/19/2022 07/19/2022
Misc
Resolved
07/19/2022
-Fire caulk penetration of firewall. No taping at penetrations -Install b-vent shield in attic -Provide furnace auxiliary condensate drain pan per code -Provide clearance min 1” from b-vent **move the duct away so it’s not touching the b-vent **OK TO INSULATE
Rated Assembly Inspection Passed 7/19/2022 7/19/2022 07/19/2022
Misc
Informational
07/11/2022
-Attic firewall-ok -Dwelling firewall-ok
Occupancy Inspection - Codes Commercial Failed 10/5/2022 10/5/2022 10/05/2022
Misc
Corrective Action Required
10/05/2022
OUTDOOR: -Provide tamper-proof caps at AC valves UNIT A: -Provide mean to clean out furnace condensate pipe UNIT B: -Provide mean to clean out furnace condensate pipe -Bend edge of furnace auxiliary drain pan straight up -Extend water heater pan drain to drain receptor UNIT C: -Range anti-tipping device -Provide mean to clean out furnace condensate pipe -Rear bedroom smoke alarm not interconnected UNIT D: -Provide mean to clean out furnace condensate pipe -Bend edge of furnace auxiliary drain pan straight up
Occupancy Inspection - Codes Commercial Full C of O 10/7/2022 10/07/2022
Misc
Resolved
10/07/2022
OUTDOOR: UNIT A: UNIT B: UNIT C: UNIT D:
Documents & Images
Date Uploaded File Type Document Name
01/20/2022 Receipt Receipt for transaction:2022-000334
03/02/2022 Letter INSPECTION SUMMARY
03/14/2022 Letter INSPECTION SUMMARY
05/23/2022 Letter INSPECTION SUMMARY
05/25/2022 Letter INSPECTION SUMMARY
06/27/2022 Letter INSPECTION SUMMARY
06/29/2022 Letter INSPECTION SUMMARY
07/07/2022 Letter INSPECTION SUMMARY
07/07/2022 Letter INSPECTION SUMMARY
07/11/2022 Letter INSPECTION SUMMARY
07/12/2022 Letter INSPECTION SUMMARY
07/12/2022 Letter INSPECTION SUMMARY
07/19/2022 Letter INSPECTION SUMMARY
07/19/2022 Letter INSPECTION SUMMARY
10/05/2022 Letter INSPECTION SUMMARY
10/07/2022 Letter Field Certificate of Occupancy
10/07/2022 Letter Codes Final Certificate of Occupancy
06/23/2023 Letter DS Building Permit
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home