Permit Application Status

PRCOM20214650


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20214650
Building Permit - Commercial
Certificate of Occupancy
BURCH TINA
ALTERATION COMMERCIAL
INTERIOR ALTERATIONS TO EXISTING BUSINESS - LOWER LEVEL CONFERENCE SPACE
09/03/2021
02/01/2022
03/06/2022
07/20/2022
Locations
Contacts
DIVERSIFIED INC, Address:22052 W 66TH ST SUITE 205, Phone:(913) 735-3776  
SALES@WEDOTHATKC.COM  
PRO PLATINUM LLC, Address:6116 ALDEN RD, Phone:(913) 908-3512  
J & S PLUMBING PROS LLC, Address:116 S WESTGLEN DR, Phone:(816) 215-5306  
H | D Architecture, Address:15225 Broadmoor St  
BURCH TINA, Address:12300 CRYSTAL AVE  
ASAP ELECTRIC INC, Address:P O BOX 860225, Phone:(913) 745-5558  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 09/16/2021 02/01/2022
Joe Frogge
LC - General Contractor
Resolved
02/01/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact. 9/9/21 - acknowledged in letter
LC - MEP Subs
Resolved
02/01/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 9/9/21 - acknowledged in letter
Fire Plan Review Approved with Conditions 09/16/2021 09/09/2021
Michael Weissenbach
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/09/2021

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC Fire Extinguisher.
Building Plan Review Approved 09/16/2021 09/09/2021
Joe Frogge
IBC 1209.2 Finish materials
Resolved
09/09/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant paint at toilet. If paint is used it must be epoxy based.
ICC A117.1 604.2 Water closet location
Resolved
09/09/2021

ICC A117.1 604.2 Location. The water closet shall be located with a wall or partition to the rear and to one side. The centerline of the water closet shall be 16 inches minimum and 18 inches maximum from the side wall or partition. Water closets located in ambulatory accessible toilet compartments specified in Section 604.10 shall have the centerline of the water closet 17 inches minimum and 19 inches maximum from the side wall or partition. Action required: Relocate toilet to comply.
ICC A117.1 603.2.1 Turning Space in rooms
Resolved
09/09/2021

ICC A117.1 Section 603.2.1 Turning Space. A turning space shall be provided within the room. The required turning space shall not be provided within a toilet compartment. 603.2.2 Door Swing. Doors shall not swing into the clear floor space or clearance for any fixture. (see code for exceptions) Action required: Modify toilet room design to comply.
ICC A117.1 606.2 lavatory clear space
Resolved
09/09/2021

ICC A117.1 606.2 Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code section for exceptions.) Action required: Modify toilet room design to comply.
ICC A117.1 604.5.1 Fixed side wall grab bars
Resolved
09/09/2021

ICC A117.1-2009 Section 604.5 Grab Bars. Grab bars for water closets shall comply with Section 609 and shall be provided in accordance with Sections 604.5.1 and 604.5.2. Grab bars shall be provided on the rear wall and on the side wall closest to the water closet. (see code for exceptions.) Action required: Modify drawings to demonstrate compliance.
IMC 801.2 Combustion air required
Resolved
09/09/2021

2018 IMC 801.2 General. Every fuel-burning appliance shall discharge the products of combustion to a vent, factory-built chimney or masonry chimney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being ventilated. (see code for exception) Action required: Furnace and water heater are in newly confined space. Provide designs for combustion air delivery and discharge. 9/9/21 - all electric per arch
Building Plan Review Rejected 09/16/2021 09/07/2021
Joe Frogge
IBC 1209.2 Finish materials
Corrective Action Required
09/07/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant paint at toilet. If paint is used it must be epoxy based.
ICC A117.1 604.2 Water closet location
Corrective Action Required
09/07/2021

ICC A117.1 604.2 Location. The water closet shall be located with a wall or partition to the rear and to one side. The centerline of the water closet shall be 16 inches minimum and 18 inches maximum from the side wall or partition. Water closets located in ambulatory accessible toilet compartments specified in Section 604.10 shall have the centerline of the water closet 17 inches minimum and 19 inches maximum from the side wall or partition. Action required: Relocate toilet to comply.
ICC A117.1 603.2.1 Turning Space in rooms
Corrective Action Required
09/07/2021

ICC A117.1 Section 603.2.1 Turning Space. A turning space shall be provided within the room. The required turning space shall not be provided within a toilet compartment. 603.2.2 Door Swing. Doors shall not swing into the clear floor space or clearance for any fixture. (see code for exceptions) Action required: Modify toilet room design to comply.
ICC A117.1 606.2 lavatory clear space
Corrective Action Required
09/07/2021

ICC A117.1 606.2 Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code section for exceptions.) Action required: Modify toilet room design to comply.
ICC A117.1 604.5.1 Fixed side wall grab bars
Corrective Action Required
09/07/2021

ICC A117.1-2009 Section 604.5 Grab Bars. Grab bars for water closets shall comply with Section 609 and shall be provided in accordance with Sections 604.5.1 and 604.5.2. Grab bars shall be provided on the rear wall and on the side wall closest to the water closet. (see code for exceptions.) Action required: Modify drawings to demonstrate compliance.
IMC 801.2 Combustion air required
Corrective Action Required
09/07/2021

2018 IMC 801.2 General. Every fuel-burning appliance shall discharge the products of combustion to a vent, factory-built chimney or masonry chimney, except for appliances vented in accordance with Section 804. The chimney or vent shall be designed for the type of appliance being ventilated. (see code for exception) Action required: Furnace and water heater are in newly confined space. Provide designs for combustion air delivery and discharge.
Licensed Contractors Rejected 09/16/2021 09/07/2021
Joe Frogge
LC - General Contractor
Corrective Action Required
09/07/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact.
LC - MEP Subs
Corrective Action Required
09/07/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 09/16/2021 09/07/2021
Michael Weissenbach
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/07/2021

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide one 2A10BC Fire Extinguisher.
Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $60.00 $60.00 Paid 02/01/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Failed 2/2/2022 02/02/2022
Misc
Corrective Action Required
02/02/2022
NO ACCESS, NO INSPECTION LEFT MESSAGE FOR ERIC 10:18 ARRIVED 10:28 DEPARTED 10:48
In-wall Inspection Not Ready 2/4/2022 2/4/2022 02/04/2022
Miscellaneous Correction
Corrective Action Required
02/04/2022
NO CITY STAMPED/APPROVED PLANS ON SITE BASEMENT FINISH IS COMPLETE NO UNDERSLAB PLUMBING INSPECTION ON RECORD NO IN WALL INSPECTION ON RECORD NO ABOVE CEILING INSPECTION ON RECORD OPEN J BOXES STORAGE ROOM, MECH ROOM NM CABLES SHALL NOT BE PERMITTED AS FOLLOWS (2) EXPOSED WITHIN A DROPPED OR SUSPENDED CEILING CAVITY IN OTHER THAN ONE-AND TWO FAMILY AND MULITIFAMILY DWELLINGS ( 2017 NEC 334.12 (A) (2) )
In-wall Inspection Failed 4/7/2022 4/7/2022 04/07/2022
Miscellaneous Correction
Corrective Action Required
02/04/2022
NO CITY STAMPED/APPROVED PLANS ON SITE BASEMENT FINISH IS COMPLETE NO UNDERSLAB PLUMBING INSPECTION ON RECORD NO IN WALL INSPECTION ON RECORD NO ABOVE CEILING INSPECTION ON RECORD OPEN J BOXES STORAGE ROOM, MECH ROOM NM CABLES SHALL NOT BE PERMITTED AS FOLLOWS (2) EXPOSED WITHIN A DROPPED OR SUSPENDED CEILING CAVITY IN OTHER THAN ONE-AND TWO FAMILY AND MULITIFAMILY DWELLINGS ( 2017 NEC 334.12 (A) (2) )
Miscellaneous Inspection Failed 4/14/2022 04/14/2022
Misc
Corrective Action Required
04/14/2022
913-424-0244 Eric called, will provide letter on underslab plumbing to toilet. pictures of wall that was rocked without inspection. look at previous permit to see what was finished in the basement. will touch base the folling week after submitals. MARK HARDING 04/14/2022 9:46 AM
Miscellaneous Inspection Failed 4/20/2022 04/20/2022
Misc
Corrective Action Required
04/14/2022
913-424-0244 Eric called, will provide letter on underslab plumbing to toilet. pictures of wall that was rocked without inspection. look at previous permit to see what was finished in the basement. will touch base the folling week after submitals. MARK HARDING 04/14/2022 9:46 AM Eric is working on it. Michael Harkins 04/20/2022 3:25 PM
Miscellaneous Inspection Failed 5/17/2022 05/17/2022
Misc
Corrective Action Required
05/17/2022
913-424-0244 Eric called, will provide letter on underslab plumbing to toilet. pictures of wall that was rocked without inspection. look at previous permit to see what was finished in the basement. will touch base the folling week after submitals. MARK HARDING 04/14/2022 9:46 AM Eric is working on it. Michael Harkins 04/20/2022 3:25 PM
Misc
Corrective Action Required
05/17/2022
- Items that need addressed : -remove NM to basement bath vanity light. no box was provided open wires above ceiling. -condensate drain for furnace was in a trash can. extend the condensate to the floor drain. - label main panel. -remove NM from box in storage area from switch to both felling lights. -- provide approved air admittance vent for bathroom. - provide a letter from the plumbing contractor on the underslab plumbing that was not inspected. -provide letter from GC that all portions of the construction that was not inspected was installed per code and future work covered without inspection will be uncovered or removed.
Occupancy Inspection - Codes Commercial Failed 6/29/2022 6/29/2022 06/29/2022
Misc
Corrective Action Required
06/29/2022
- secure whip to water heater at the ceiling. -remove NM to basement bath vanity light.-no box was provided open wires above ceiling. -remove NM from box in storage area from switch to both celling lights. - provide a letter from the plumbing contractor on the under slab plumbing that was not inspected. -provide letter from GC that all portions of the construction that was not inspected was installed per code and future work covered without inspection will be uncovered or removed. -Complete corrections for Fire Department
Occupancy Inspection - Fire Failed 6/29/2022 6/29/2022 06/30/2022
Resolved
07/21/2022
Move fire extinguisher out of closet. Install so that its top is not more than 5' obove the floor.
Occupancy Inspection - Codes Commercial Failed 7/18/2022 7/18/2022 07/18/2022
Misc
Corrective Action Required
06/29/2022
move to the exit door and max height to 5' to the top of extinguisher. -Complete corrections for Fire Department Eric was going to send picture to Fire or mark
Above Ceiling Inspection Passed 07/20/2022
In-wall Inspection Passed 07/20/2022
Miscellaneous Correction
Resolved
07/20/2022
NO CITY STAMPED/APPROVED PLANS ON SITE BASEMENT FINISH IS COMPLETE NO UNDERSLAB PLUMBING INSPECTION ON RECORD NO IN WALL INSPECTION ON RECORD NO ABOVE CEILING INSPECTION ON RECORD OPEN J BOXES STORAGE ROOM, MECH ROOM NM CABLES SHALL NOT BE PERMITTED AS FOLLOWS (2) EXPOSED WITHIN A DROPPED OR SUSPENDED CEILING CAVITY IN OTHER THAN ONE-AND TWO FAMILY AND MULITIFAMILY DWELLINGS ( 2017 NEC 334.12 (A) (2) )
Miscellaneous Inspection Passed 07/20/2022
Misc
Resolved
07/20/2022
913-424-0244 Eric called, will provide letter on underslab plumbing to toilet. pictures of wall that was rocked without inspection. look at previous permit to see what was finished in the basement. will touch base the folling week after submitals. MARK HARDING 04/14/2022 9:46 AM Eric is working on it. Michael Harkins 04/20/2022 3:25 PM
Misc
Resolved
07/20/2022
- Items that need addressed : -remove NM to basement bath vanity light. no box was provided open wires above ceiling. -condensate drain for furnace was in a trash can. extend the condensate to the floor drain. - label main panel. -remove NM from box in storage area from switch to both felling lights. -- provide approved air admittance vent for bathroom. - provide a letter from the plumbing contractor on the underslab plumbing that was not inspected. -provide letter from GC that all portions of the construction that was not inspected was installed per code and future work covered without inspection will be uncovered or removed.
Occupancy Inspection - Codes Commercial Full C of O 7/20/2022 7/20/2022 07/20/2022
Misc
Resolved
07/20/2022
move to the exit door and max height to 5' to the top of extinguisher. -Complete corrections for Fire Department Eric was going to send picture to Fire or mark
Occupancy Inspection - Fire Passed 7/18/2022 7/20/2022 07/21/2022
Documents & Images
Date Uploaded File Type Document Name
09/03/2021 Application Form Lees Summit Commercial Permit Application
09/03/2021 Application Form Lees Summit License_Tax_Application
09/03/2021 Plans P2021-008-BurchRemodel-PermitSet090321
09/07/2021 Letter Fire Building Plan Review
09/07/2021 Email RE_ 415 SW Jefferson Remodel
09/07/2021 Letter DS P/R Corrections Document
09/09/2021 Letter DS P_R Corrections Document-Responses
09/09/2021 Drawing P2021-008-BurchRemodel-PermitSet090921Rev1
09/09/2021 Letter Fire Building Plan Review
02/01/2022 Approved Plans approved - P2021-008-BurchRemodel-PermitSet090921Rev1
02/01/2022 Receipt Receipt for transaction:2022-000547
02/01/2022 Letter DS Building Permit
02/02/2022 Letter INSPECTION SUMMARY
02/04/2022 Letter INSPECTION SUMMARY
04/07/2022 Letter INSPECTION SUMMARY
04/14/2022 Letter INSPECTION SUMMARY
04/20/2022 Letter INSPECTION SUMMARY
05/17/2022 Letter INSPECTION SUMMARY
06/01/2022 Letter INSPECTION SUMMARY
06/29/2022 Letter INSPECTION SUMMARY
06/30/2022 Letter Fire Loss Reduction Form
07/18/2022 Letter INSPECTION SUMMARY
07/20/2022 Letter Codes Final Certificate of Occupancy
07/20/2022 Letter Field Certificate of Occupancy
07/20/2022 Letter INSPECTION SUMMARY
07/20/2022 Letter INSPECTION SUMMARY
07/20/2022 Letter INSPECTION SUMMARY
12/14/2023 Approved Plans SANITARY - STAMPED CONSTRUCTION PLANS
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home