Permit Application Status

PRCOM20212831


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20212831
Building Permit - Commercial
Certificate of Occupancy
2 COMBS ENTERPRISES INC
ALTERATION COMMERCIAL
INTERIOR ALTERATIONS TO EXISTING GYM - INCREASING SIZE OF LOCKER ROOMS - ADDING OFFICES AND LAUNDRY ROOM - RECONFIGURE RECEPTION AREA
06/02/2021
10/28/2021
12/04/2021
05/16/2022
Locations
Contacts
EXCEL CONSTRUCTORS, INC, Address:8041 W 47TH ST, Phone:(913) 261-1000  
Kerry.Winter@ExcelConstructors.com, Address:Kerry.Winter@ExcelConstructors.com  
SALADINO PLUMBING & HEATING COMPANY, Address:2210 TELEVISION PL, Phone:(816) 833-9900  
BROOKS ELECTRICAL, Address:1107 N 1712 RD, Phone:(785) 838-9040  
MYERS FURNACE CO, Address:534 N SCOTT AVE, Phone:(816) 331-8282  
HANNEY & ASSOCIATES ARCHITECTS, Address:1726 SOUTH HILLSIDE, Phone:(316) 683-8965  
2 COMBS ENTERPRISES INC, Address:2054 HILL HAVEN RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 06/21/2021 10/28/2021
Development Center
LC - MEP Subs
Corrective Action Required
06/14/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Plumbing contractor. 6/14/21 - acknowledged in letter
Building Plan Review Approved with Conditions 06/21/2021 09/07/2021
Joe Frogge
Miscellaneous Correction
Resolved
06/14/2021

There are two "Code 2" plans with conflicting information. Action required: Clarify.
Health Dept Review
Resolved
09/07/2021

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. (food/drink service at reception desk) 6/14/21 - acknowledged in letter
Health Dept Inspection
Corrective Action Required
06/14/2021

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 6/14/21 - acknowledged in letter
ICC A117.1 604.3.1 Water closet width
Resolved
06/14/2021

ICC A117.1 Section 604.3.1 Clearance Width. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall. Action required: Provide minimum 60" clearance behind toilet in Toilet Room 123.
IBC 1606.2 Design dead load - structural
Resolved
06/14/2021

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that either the weight of replacement roof top equipment (RTU-12) is less than or equal to original equipment or provide engineer’s report to verify that existing roof structure will support additional load. Also provide verification that roof is capable of supporting new equipment. (RTU-13)
NEC Article 210.8 (B) Other than dwelling units GFCI
Resolved
06/14/2021

2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected.
Health Department Review Approved 09/07/2021
Joe Frogge
Fire Plan Review Approved with Conditions 06/21/2021 06/14/2021
Michael Weissenbach
Posting of occupant load
Corrective Action Required
06/14/2021

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load signage in all assembly spaces.
Construction documents for fire alarm systems
Corrective Action Required
06/14/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Construction documents - Fire protection systems
Corrective Action Required
06/14/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
06/14/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Misc
Resolved
06/14/2021

(Informational Purposes) All existing emergency/exit lighting to be fully operational during the occupancy inspection. Fire extinguishers need to have a current annual inspection tag.
Panic and fire exit hardware
Corrective Action Required
06/14/2021

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. (Verified At Inspection) Provide Panic hardware for Studio A and the Cardio room.
Building Plan Review Rejected 06/14/2021 06/03/2021
Joe Frogge
Miscellaneous Correction
Corrective Action Required
06/03/2021

There are two "Code 2" plans with conflicting information. Action required: Clarify.
Health Dept Review
Corrective Action Required
06/03/2021

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. (food/drink service at reception desk)
Health Dept Inspection
Corrective Action Required
06/03/2021

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
ICC A117.1 604.3.1 Water closet width
Corrective Action Required
06/03/2021

ICC A117.1 Section 604.3.1 Clearance Width. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall. Action required: Provide minimum 60" clearance behind toilet in Toilet Room 123.
IBC 1606.2 Design dead load - structural
Corrective Action Required
06/03/2021

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that either the weight of replacement roof top equipment (RTU-12) is less than or equal to original equipment or provide engineer’s report to verify that existing roof structure will support additional load. Also provide verification that roof is capable of supporting new equipment. (RTU-13)
NEC Article 210.8 (B) Other than dwelling units GFCI
Corrective Action Required
06/03/2021

2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected.
Fire Plan Review Approved with Conditions 06/14/2021 06/03/2021
Michael Weissenbach
Posting of occupant load
Corrective Action Required
06/03/2021

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load signage in all assembly spaces.
Construction documents for fire alarm systems
Corrective Action Required
06/03/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Construction documents - Fire protection systems
Corrective Action Required
06/03/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
06/03/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Misc
Corrective Action Required
06/03/2021

(Informational Purposes) All existing emergency/exit lighting to be fully operational during the occupancy inspection. Fire extinguishers need to have a current annual inspection tag.
Panic and fire exit hardware
Corrective Action Required
06/03/2021

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. (Verified At Inspection) Provide Panic hardware for Studio A and the Cardio room.
Licensed Contractors Rejected 06/14/2021 06/03/2021
Joe Frogge
LC - MEP Subs
Corrective Action Required
06/03/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Plumbing contractor.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $1,120.00 $1,120.00 Paid 10/28/2021
$316,372.50
7232302-Commercial License Tax Fee $105,457.50 $105,457.50 Paid 06/03/2021
$105,457.50
8331507-Sewer Connection Fee $240.00 $240.00 Paid 10/28/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 11/24/2021 11/24/2021
Misc
Informational
11/24/2021
MEN'S LOCKER ROOM-UNDERSLAB PLUMBING FROM MEN RESTROOM LAVATORY DRAIN-OK TO COVER
In-wall Inspection Partial 12/13/2021 12/13/2021 12/13/2021
Misc
Informational
12/13/2021
IN-WALL OK TO COVER BELOW: -YOGA RM206
In-wall Inspection Partial 12/21/2021 12/21/2021 12/21/2021
Misc
Informational
12/13/2021
IN-WALL OK TO COVER BELOW: -YOGA RM206; STORAGE&AAT RM 104/105
Underslab Plumbing Inspection - Commercial Partial 1/28/2022 1/28/2022 01/28/2022
Misc
Informational
11/24/2021
MEN'S LOCKER ROOM-UNDERSLAB PLUMBING FROM MEN RESTROOM LAVATORY DRAIN-OK TO COVER - LAUNDRY, WOMEN'S LOCKER ROOM, CHILDCARE AREA OK TO COVER -
In-wall Inspection Failed 2/10/2022 2/10/2022 02/10/2022
Misc
Informational
12/21/2021
IN-WALL OK TO COVER BELOW: -YOGA RM206; STORAGE&AAT RM 104/105 OFFICE/GM/OM/SALES/LAUNDRY/TOILET AREA-CORRECTIONS AT REQUIRED: -PROTECT PLUMBING PER CODE
In-wall Inspection Partial 2/11/2022 2/11/2022 02/11/2022
Misc
Informational
02/10/2022
IN-WALL OK TO COVER BELOW: -YOGA RM206; STORAGE&AAT RM 104/105; OFFICE/GM/OM/SALES/LAUNDRY/TOILET AREA
Underslab Plumbing Inspection - Commercial Partial 2/24/2022 2/24/2022 02/24/2022
Misc
Informational
01/28/2022
UNDERSLAB PLUMBING OK BELOW: -MEN'S LOCKER ROOM, MEN RESTROOM LAVATORY DRAIN - LAUNDRY, WOMEN'S LOCKER ROOM, CHILDCARE AREA, FRONT DESK COUNTER
Above Ceiling Inspection Partial 3/23/2022 3/23/2022 03/23/2022
Misc
Informational
03/23/2022
ABOVE-CEILING OK BELOW: -MEN'S LOCKER & RESTROOM
Above Ceiling Inspection Partial 3/28/2022 3/28/2022 03/28/2022
Misc
Informational
03/23/2022
ABOVE-CEILING OK BELOW: -MEN'S LOCKER & RESTROOM WOMEN'S LOCKER ROOM: SUPPORT LOW VOLTAGE CABLES OFF CEILING GRIDS IN A NEAT AND WORKMAN-LIKE MANNER
Above Ceiling Inspection Partial 4/6/2022 4/6/2022 04/06/2022
Misc
Informational
03/28/2022
ABOVE-CEILING OK BELOW: -MEN'S LOCKER & RESTROOM, YOGA RM, OFFICES, CORRIDOR OUTSIDE OFFICES WOMEN'S LOCKER ROOM: SUPPORT LOW VOLTAGE CABLES OFF CEILING GRIDS IN A NEAT AND WORKMAN-LIKE MANNER
Gas Piping Inspection - Commercial Passed 4/8/2022 4/8/2022 04/08/2022
Informational
04/08/2022
Gas piping to heaters above yoga and to laundry-OK
Above Ceiling Inspection Partial 4/11/2022 4/11/2022 04/11/2022
Misc
Informational
04/06/2022
ABOVE-CEILING OK BELOW: -MEN'S LOCKER & RESTROOM, YOGA RM, OFFICES, CORRIDOR OUTSIDE OFFICES, TRAINER OFFICES WOMEN'S LOCKER ROOM: SUPPORT LOW VOLTAGE CABLES OFF CEILING GRIDS IN A NEAT AND WORKMAN-LIKE MANNER
Above Ceiling Inspection Partial 4/12/2022 4/12/2022 04/12/2022
Misc
Informational
04/11/2022
ABOVE-CEILING OK BELOW: -MEN'S LOCKER & RESTROOM, YOGA RM, OFFICES, CORRIDOR OUTSIDE OFFICES, TRAINER OFFICES, AMERICAN TRAINING RM
Above Ceiling Inspection Partial 5/5/2022 05/05/2022
Misc
Informational
04/12/2022
ABOVE-CEILING OK BELOW: -MEN'S LOCKER & RESTROOM, YOGA RM, OFFICES, CORRIDOR OUTSIDE OFFICES, TRAINER OFFICES, AMERICAN TRAINING RM **REMAINING AREA: SUPPORT MC EVERY 6 FT; TAG/COLOR/IDENTIFY INDEPENDENT SUPPORT WIRES
Underslab Plumbing Inspection - Commercial Passed 05/05/2022
Misc
Informational
02/24/2022
UNDERSLAB PLUMBING OK BELOW: -MEN'S LOCKER ROOM, MEN RESTROOM LAVATORY DRAIN - LAUNDRY, WOMEN'S LOCKER ROOM, CHILDCARE AREA, FRONT DESK COUNTER
In-wall Inspection Passed 3/23/2022 05/05/2022
Misc
Informational
02/11/2022
IN-WALL OK TO COVER BELOW: -YOGA RM206; STORAGE&AAT RM 104/105; OFFICE/GM/OM/SALES/LAUNDRY/TOILET AREA
Above Ceiling Inspection Passed 5/6/2022 5/6/2022 05/06/2022
Misc
Resolved
05/06/2022
ABOVE-CEILING OK BELOW: -MEN'S LOCKER & RESTROOM, YOGA RM, OFFICES, CORRIDOR OUTSIDE OFFICES, TRAINER OFFICES, AMERICAN TRAINING RM **REMAINING AREA: SUPPORT MC EVERY 6 FT; TAG/COLOR/IDENTIFY INDEPENDENT SUPPORT WIRES
Alarm Test Passed 5/10/2022 05/12/2022
Occupancy Inspection - Codes Commercial Failed 5/12/2022 5/12/2022 05/12/2022
Misc
Corrective Action Required
05/12/2022
-Receptacles located within six ft of laundry room sinks must be gfci-protected -Tamper resistant receptacles are required in childcare facility, including receptacle in bathroom and at sink
Occupancy Inspection - Fire Passed 5/12/2022 5/12/2022 05/12/2022
Corrective Action Required
05/12/2022
All life safety was appropriate. Okay to occupy with approval form codes.
Occupancy Inspection - Codes Commercial Failed 5/13/2022 5/13/2022 05/13/2022
Misc
Corrective Action Required
05/12/2022
-Receptacles located within six ft of laundry room sinks must be gfci-protected **NEC 210.8(B)(5) requires gfci protection for receptacles located within 6 ft of the basin of the sink. The laundry room receptacles do not meet either of the 2 exceptions allowed that will omit gfci requirement
Occupancy Inspection - Codes Commercial Full C of O 5/16/2022 5/16/2022 05/16/2022
Misc
Resolved
05/16/2022
-Receptacles located within six ft of laundry room sinks must be gfci-protected **NEC 210.8(B)(5) requires gfci protection for receptacles located within 6 ft of the basin of the sink. The laundry room receptacles do not meet either of the 2 exceptions allowed that will omit gfci requirement
Documents & Images
Date Uploaded File Type Document Name
06/02/2021 Application Form GENESIS_LEES_SUMMIT_PERMIT_APP
06/02/2021 Plans GLS_Combined_060121
06/03/2021 Letter Fire Building Plan Review
06/07/2021 Letter DS P/R Corrections Document
06/14/2021 Letter CODE_01_061121
06/14/2021 Drawing 004_GLS_CODE 2
06/14/2021 Drawing GLS_A301_061121
06/14/2021 Drawing GLS_A201_061121
06/14/2021 Drawing GLS_ELEC_REVISIONS_061121
06/14/2021 Drawing GLS_A104_061121
06/14/2021 Engineer Report/Study 21.236.Genesis.RTU.Renovation.Calcs.2021.06.11
06/14/2021 Letter Fire Building Plan Review
09/07/2021 Email New Food Establishment Plan Review - Approved FTG_0001193
10/21/2021 Approved Plans APPROVED - GLS_Combined_060121
10/28/2021 Receipt Receipt for transaction: 2021-008331
10/28/2021 Letter DS Building Permit
11/24/2021 Letter INSPECTION SUMMARY
12/13/2021 Letter INSPECTION SUMMARY
12/21/2021 Letter INSPECTION SUMMARY
01/28/2022 Letter INSPECTION SUMMARY
02/10/2022 Letter INSPECTION SUMMARY
02/11/2022 Letter INSPECTION SUMMARY
02/24/2022 Letter INSPECTION SUMMARY
03/23/2022 Letter INSPECTION SUMMARY
03/28/2022 Letter INSPECTION SUMMARY
04/06/2022 Letter INSPECTION SUMMARY
04/08/2022 Letter INSPECTION SUMMARY
04/11/2022 Letter INSPECTION SUMMARY
04/12/2022 Letter INSPECTION SUMMARY
05/05/2022 Letter INSPECTION SUMMARY
05/05/2022 Letter INSPECTION SUMMARY
05/05/2022 Letter INSPECTION SUMMARY
05/06/2022 Letter INSPECTION SUMMARY
05/12/2022 Letter Fire Loss Reduction Form
05/12/2022 Letter INSPECTION SUMMARY
05/12/2022 Letter Fire Loss Reduction Form
05/12/2022 Letter Fire Loss Reduction Form
05/13/2022 Letter INSPECTION SUMMARY
05/16/2022 Letter Codes Final Certificate of Occupancy
05/16/2022 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home