Summary
PRCOM20204880
Building Permit - Commercial
Certificate of Occupancy
PINE TREE PLAZA LLC
CHANGE OF TENANT
TENANT FINISH FOR RETAIL BBQ STORE WITH DEMO KITCHEN AND NEW DECK
12/22/2020
02/03/2021
07/12/2021
05/03/2021
Locations
Contacts
RENEW RESTORATION, Address:1602 CURTIS DR, Phone:(816) 876-8533  
Michael's Heating And Cooling, Address:1110 NW SAWGRASS DR, Phone:(816) 255-6522  
J AND W ELECTRIC LLC, Address:4468 COUNTRY SQUIRE LANE, Phone:(816) 824-5581  
RESCUE 1 PLUMBING, Address:1413 NE GRAND AVE, Phone:(816) 985-4533  
COLLINS WEBB ARCHITECTURE LLC, Address:307 SW MARKET ST, Unit B, Phone:(816) 249-2270  
CHIP@RENEWRESTORATIONKC.COM  
PINE TREE PLAZA LLC, Address:601 E SOUTH ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 01/06/2021 02/03/2021
Joe Frogge
LC - MEP Subs
Resolved
02/03/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. (air must be provided and returned to all new spaces created - hvac contractor required)
Building Plan Review Approved with Conditions 01/22/2021 02/02/2021
Joe Frogge
Health Dept Review
Resolved
02/02/2021

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
01/12/2021

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
IBC 1209.2 Finish materials
Corrective Action Required
01/12/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Comment is for informational purposes - applies to walls at water closets and mop sinks.
Health Department Review Approved 02/02/2021
Joe Frogge
Zoning Review Approved 01/13/2021
Joe Frogge
see email from Hector Soto
Fire Plan Review Approved with Conditions 01/06/2021 01/12/2021
Joe Frogge
Address numbers required
Corrective Action Required
01/12/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address exterior doors.
Fire Plan Review Approved with Conditions 01/22/2021 01/12/2021
Michael Weissenbach
Address numbers required
Corrective Action Required
01/12/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address exterior doors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $260.00 $260.00 Paid 02/03/2021
8331507-Sewer Connection Fee $180.00 $180.00 Paid 02/03/2021
7232302-Commercial License Tax Fee $6,022.50 $6,022.50 Paid 02/04/2021
$6,022.50
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 2/23/2021 2/23/2021 02/23/2021
Occupancy Inspection - Fire Passed 4/20/2021 04/20/2021
Above Ceiling Inspection Passed 4/20/2021 04/20/2021
Occupancy Inspection - Codes Commercial Failed 4/20/2021 4/20/2021 04/20/2021
Misc
Corrective Action Required
04/20/2021
- PROVIDE HEALTH DEPT APPROVAL - - PROVIDE ADDRESS REAR DOOR - - PROVIDE REAR EXIT SIGN - - PROVIDE 18" VERTICAL GRAB BAR RESTROOM - - PROVIDE INSULATION PLUMBING UNDER SINK - - POS COUNTERTOPS HEIGHT PER PLAN - - PLANS SHOW DECK AT REER DOORS NO DECK WOOD STAIRS NEED BALUSTERS IF DECK NOT REQUIRED -
Occupancy Inspection - Codes Commercial Failed 4/21/2021 04/21/2021
Misc
Corrective Action Required
04/20/2021
- PROVIDE HEALTH DEPT APPROVAL - - PROVIDE ADDRESS REAR DOOR - - PROVIDE REAR EXIT SIGN - - PROVIDE 18" VERTICAL GRAB BAR RESTROOM - - PROVIDE INSULATION PLUMBING UNDER SINK - - POS COUNTERTOPS HEIGHT PER PLAN - - PLANS SHOW DECK AT REAR DOORS NO DECK BUILT - - (LANDING AT OUTSWING DOORS REQUIRED 2018 IBC 1010.1.6 ) - - LANDING SHALL HAVE A WIDTH NOT LESS THAN WIDTH OF STAIRWAY OR DOOR WHICHEVER IS GREATER. LANDINGS SHALL HAVE A LENGTH MEASURED IN DIRECTION OF TRAVEL OF NOT LESS THAN 44" - - 2018 IRC 1010.1.7 THRESHOLDS -
Piers/Caissons Inspection - Commercial Passed 4/29/2021 04/29/2021
Occupancy Inspection - Codes Commercial Failed 4/29/2021 4/29/2021 04/29/2021
Misc
Corrective Action Required
04/21/2021
- PROVIDE HEALTH DEPT APPROVAL -
Deck Final Inspection - Commercial Passed 5/3/2021 05/03/2021
Occupancy Inspection - Codes Commercial Full C of O 5/3/2021 05/03/2021
Misc
Corrective Action Required
04/29/2021
- PROVIDE HEALTH DEPT APPROVAL -
Documents & Images
Date Uploaded File Type Document Name
12/22/2020 Application Form BBQ Store Permit Application
12/22/2020 Drawing CA American BBQ Build Out Plan
12/28/2020 Email RE American BBQ submittal
12/28/2020 Letter prelim comments - incomplete
01/12/2021 Plans 21011_210112_American BBQ Store_Tenant Improvements
01/12/2021 Letter Fire Building Plan Review
01/12/2021 Email address info
01/12/2021 Letter License Tax Bill
01/13/2021 Email planning approval
01/13/2021 Letter DS P/R Corrections Document
02/02/2021 Email New Food Establishment Plan Review - Approved FTG 0001146
02/02/2021 Approved Plans approved - 21011_210112_American BBQ Store_Tenant Improvements
02/03/2021 Receipt Receipt for transaction:2021-000544
02/03/2021 Letter DS Building Permit
02/23/2021 Letter INSPECTION SUMMARY
02/23/2021 Letter INSPECTION SUMMARY
04/20/2021 Letter Fire Loss Reduction Form
04/20/2021 Letter INSPECTION SUMMARY
04/20/2021 Letter INSPECTION SUMMARY
04/21/2021 Letter INSPECTION SUMMARY
04/23/2021 Approved Plans approved - American BBQ_210423_INSPECTION REVISIONS
04/29/2021 Letter INSPECTION SUMMARY
04/29/2021 Letter INSPECTION SUMMARY
04/29/2021 Letter INSPECTION SUMMARY
05/03/2021 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home