Review Type |
Outcome |
Est. Completion Date |
Completed |
Licensed Contractors
|
Approved
|
10/28/2020
|
02/22/2021
|
|
Joe Frogge
|
|
LC - General Contractor
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
10/23/20 - acknowledged in letter.
|
|
LC - MEP Subs
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
10/23/20 - acknowledged in letter.
|
|
|
Building Plan Review
|
Approved with Conditions
|
10/28/2020
|
02/22/2021
|
|
Joe Frogge
|
|
Miscellaneous Correction
Incomplete submittal.
Action required: Provide complete MEP designs. "Design Build" is acceptable but must be submitted at the same time. We will not review separately as the trades can and do affect each other.
|
|
Misc
A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Action required: Comment is for informational purposes.
10/23/20 - acknowledged in letter.
|
|
Miscellaneous Correction
Corrective Action Required
This tenant finish permit is associated with an incomplete shell permit.
Action required: Comment is for informational purposes. Occupancy will not be granted for the tenant prior to completion of shell permit.
10/23/20 - acknowledged in letter.
|
|
Code analysis required
A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed.
Action required: Update code analysis to show type IIIB construction. (separate types only allowable when separated by fire walls)
|
|
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2.
Action required: Provide minimum 18" clearance at latch side of door out of Mother's Room 117.
|
|
Misc
Corrective Action Required
As a result of CPTED security review our Police Department has suggested that it would be better to switch the office on the north side of the vestibule and the lobby where the vestibule would open and customers would enter straight through, on the north side so everyone in the building could see who was coming in.
Action required: Comment is for informational purposes. Change is not required.
10/29/20 - acknowledged in letter
|
|
Planning - Screening of rooftop equipment
Unified Development Ordinance Article 8, Section 8.180.E
Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director.
Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO section.
10/29/20 - this work is to be performed under permit PRCOM20201911
|
|
IBC 1606.2 Design dead load - structural
2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official.
Action required: Provide engineer’s report to verify that existing roof structure will support additional load or design to compensate.
10/29/20 - this work is to be performed under permit PRCOM20201911
|
|
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
Action required: Provide convenience receptacle within 25' of new roof mounted equipment.
10/29/20 - this work is to be performed under permit PRCOM20201911
|
|
|
Fire Plan Review
|
Approved with Conditions
|
10/28/2020
|
10/21/2020
|
|
Michael Weissenbach
|
|
Address numbers required
Corrective Action Required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
(Verified At Inspection)
|
|
Miscellaneous Correction
|
|
Illumination required
Corrective Action Required
2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied.
(Verified At Inspection)
Provide exterior emergency lighting at exit doors.
|
|
|
CPTED Plan Review
|
Approved
|
07/29/2020
|
07/27/2020
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Rejected
|
07/29/2020
|
07/20/2020
|
|
Michael Weissenbach
|
|
Address numbers required
Corrective Action Required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
(Verified At Inspection)
|
|
Miscellaneous Correction
Corrective Action Required
(Action Required)
1.Provide complete MEP plans to be reviewed.
2. Exterior emergency lighting including exit signage at front entrance.
3. Exit signage for rear exit.
|
|
|
Building Plan Review
|
Rejected
|
07/29/2020
|
07/20/2020
|
|
Joe Frogge
|
|
Miscellaneous Correction
Corrective Action Required
Incomplete submittal.
Action required: Provide complete MEP designs. "Design Build" is acceptable but must be submitted at the same time. We will not review separately as the trades can and do affect each other.
|
|
Misc
Corrective Action Required
A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Action required: Comment is for informational purposes.
|
|
Miscellaneous Correction
Corrective Action Required
This tenant finish permit is associated with an incomplete shell permit.
Action required: Comment is for informational purposes. Occupancy will not be granted for the tenant prior to completion of shell permit.
|
|
Code analysis required
Corrective Action Required
A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed.
Action required: Update code analysis to show type IIIB construction. (separate types only allowable when separated by fire walls)
|
|
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Corrective Action Required
ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2.
Action required: Provide minimum 18" clearance at latch side of door out of Mother's Room 117.
|
|
Misc
Corrective Action Required
As a result of CPTED security review our Police Department has suggested that it would be better to switch the office on the north side of the vestibule and the lobby where the vestibule would open and customers would enter straight through, on the north side so everyone in the building could see who was coming in.
Action required: Comment is for informational purposes. Change is not required.
|
|
|
Zoning Review
|
Approved
|
07/29/2020
|
07/20/2020
|
|
Joe Frogge
|
|
|
Licensed Contractors
|
Rejected
|
07/29/2020
|
07/20/2020
|
|
Joe Frogge
|
|
LC - General Contractor
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
|
|
LC - MEP Subs
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
|
|
|