Permit Application Status

PRCOM20201707


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20201707
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW TENANT FINISH
TENANT FINISH FOR COFFEE SHOP WITH DRIVE-THRU AND PATIO SEATING
06/23/2020
11/24/2020
12/21/2020
02/04/2021
Locations
Contacts
HENTZEN CONSTRUCTION SERVICES INC, Address:3711 N HILLSIDE, Phone:(316) 267-3321  
HEART OF AMERICA SERVICE CO LLC, Address:8347 MONTICELLO RD, Phone:(913) 441-2772  
KENDREK ELECTRIC INC, Address:P O BOX 9411, Phone:(316) 204-3029  
J-HAWK PLUMBING INC, Address:3615 W MAPLE ST, Phone:(316) 942-7279  
NORR Architects, Address:325 Norht Lasalle Street - Suite 500, Phone:(312) 424-2400  
chris@hentzenservices.com  
CITY OF LEES SUMMIT, Address:220 SE GREEN ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 07/15/2020 11/24/2020
Joe Frogge
Posting of occupant load
Corrective Action Required
11/23/2020

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load sign in the structure at 73. Post occupant load sign for the patio at 26.
Address numbers required
Corrective Action Required
11/23/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address exit doors.
Building Plan Review Approved with Conditions 07/15/2020 11/24/2020
Joe Frogge
Miscellaneous Correction
Resolved
11/24/2020

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 7/13/20 - acknowledged in letter
Misc
Corrective Action Required
11/23/2020

This tenant finish permit is associated with an incomplete shell permit. Action required: Comment is for informational purposes. Occupancy will not be granted for the tenant prior to completion of shell permit. 7/13/20 - acknowledged in letter
Health Dept Inspection
Corrective Action Required
11/23/2020

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 7/13/20 - acknowledged in letter
Miscellaneous Correction
Corrective Action Required
11/23/2020

Structure over 6' tall require frost protected foundation. Action required: Provide foundation design for monument sign or request deferral. Approved design required prior to inspections. 7/13/20 - acknowledged in letter which refers to shell permit with incorrect reference number, correct number is PRCOM20200763. Deferred to sign permit process.
Licensed Contractors Approved 07/15/2020 11/18/2020
Joe Frogge
LC - General Contractor
Resolved
11/18/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. 7/13/20 - acknowledged in letter
LC - MEP Subs
Resolved
11/18/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 7/13/20 - acknowledged in letter
Building Plan Review Approved with Conditions 07/15/2020 07/13/2020
Joe Frogge
Miscellaneous Correction
Resolved
11/24/2020

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 7/13/20 - acknowledged in letter
Misc
Corrective Action Required
07/08/2020

This tenant finish permit is associated with an incomplete shell permit. Action required: Comment is for informational purposes. Occupancy will not be granted for the tenant prior to completion of shell permit. 7/13/20 - acknowledged in letter
Health Dept Inspection
Corrective Action Required
07/08/2020

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 7/13/20 - acknowledged in letter
Miscellaneous Correction
Corrective Action Required
07/13/2020

Structure over 6' tall require frost protected foundation. Action required: Provide foundation design for monument sign or request deferral. Approved design required prior to inspections. 7/13/20 - acknowledged in letter which refers to shell permit with incorrect reference number, correct number is PRCOM20200763. Deferred to sign permit process.
Fire Plan Review Approved with Conditions 07/15/2020 07/10/2020
Michael Weissenbach
Posting of occupant load
Corrective Action Required
07/08/2020

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load sign in the structure at 73. Post occupant load sign for the patio at 26.
Address numbers required
Corrective Action Required
07/08/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address exit doors.
Health Department Review Approved 07/06/2020
Joe Frogge
Building Plan Review Rejected 07/08/2020 06/24/2020
Joe Frogge
Miscellaneous Correction
Corrective Action Required
06/24/2020

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
06/24/2020

This tenant finish permit is associated with an incomplete shell permit. Action required: Comment is for informational purposes. Occupancy will not be granted for the tenant prior to completion of shell permit.
Health Dept Review
Resolved
07/06/2020

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
06/24/2020

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Miscellaneous Correction
Corrective Action Required
06/24/2020

Structure over 6' tall require frost protected foundation. Action required: Provide foundation design for monument sign or request deferral. Approved design required prior to inspections.
Licensed Contractors Rejected 07/08/2020 06/24/2020
Joe Frogge
LC - General Contractor
Corrective Action Required
06/24/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
06/24/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 07/08/2020 06/24/2020
Michael Weissenbach
Posting of occupant load
Corrective Action Required
06/24/2020

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load sign in the structure at 73. Post occupant load sign for the patio at 26.
Address numbers required
Corrective Action Required
06/24/2020

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address exit doors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $1,000.00 $1,000.00 Paid 11/24/2020
7232302-Commercial Excise Tax Fee $35,722.50 $35,722.50 Paid 01/29/2021
8331507-Sewer Connection Fee $330.00 $330.00 Paid 11/24/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 12/2/2020 at 7:59 AM 12/02/2020
Underslab Electrical Inspection - Commercial Failed 12/3/2020 12/3/2020 at 9:10 AM 12/03/2020
Misc
Corrective Action Required
12/03/2020
- not complete wanted PM inspection -
Underslab Electrical Inspection - Commercial Passed 12/4/2020 12/4/2020 12/04/2020
Misc
Resolved
12/04/2020
In-wall Inspection Partial 12/15/2020 12/15/2020 12/15/2020
Misc
Informational
12/15/2020
- IN WALL ABOVE CEILING PLUMBING ONLY -
Above Ceiling Inspection Partial 12/15/2020 12/15/2020 12/15/2020
THE FOLLOWING AREAS ARE APPROVED
Informational
12/15/2020
- ABOVE CEILING PLUMBING ONLY -
All Rough Inspection - Commercial Partial 12/17/2020 12/17/2020 12/17/2020
Misc
Corrective Action Required
12/17/2020
- PROVIDE 1" CLEARANCE WATER HEATER B VENT - - PARTIAL HARD LID IN DINING AREA HVAC NOT COMPLETE -
Above Ceiling Inspection Partial 12/17/2020 12/17/2020 12/17/2020
THE FOLLOWING AREAS ARE APPROVED
Informational
12/15/2020
- ABOVE CEILING PLUMBING ONLY - - ABOVE CEILING ELECTRICAL - - HARD LID IN DINING AREA INCOMPLETE HVAC -
Above Ceiling Inspection Partial 12/21/2020 12/21/2020 12/21/2020
THE FOLLOWING AREAS ARE APPROVED
Informational
12/17/2020
- ABOVE CEILING PLUMBING ONLY - - ABOVE CEILING ELECTRICAL - - HARD LID IN DINING AREA HVAC -
In-wall Inspection Passed 12/21/2020 12/21/2020 12/21/2020
All Rough Inspection - Commercial Passed 12/21/2020 12/21/2020 12/21/2020
Misc
Resolved
12/21/2020
Above Ceiling Inspection Partial 1/6/2021 1/6/2021 01/06/2021
THE FOLLOWING AREAS ARE APPROVED
Informational
12/21/2020
- ABOVE CEILING PLUMBING ONLY - - ABOVE CEILING ELECTRICAL - - HARD LID IN DINING AREA HVAC -
Misc
Corrective Action Required
01/06/2021
- MARK RATED WALL ABOVE CEILING 703.7 -
Electrical Service Inspection Passed 1/28/2021 01/28/2021
Occupancy Inspection - Fire Passed 1/29/2021 1/29/2021 01/29/2021
Above Ceiling Inspection Passed 1/6/2021 01/29/2021
THE FOLLOWING AREAS ARE APPROVED
Informational
01/06/2021
- ABOVE CEILING PLUMBING ONLY - - ABOVE CEILING ELECTRICAL - - HARD LID IN DINING AREA HVAC -
Misc
Resolved
01/29/2021
Occupancy Inspection - Codes Commercial Failed 1/29/2021 1/29/2021 01/29/2021
Misc
Corrective Action Required
01/29/2021
- LICENSE TAX FEE NOT PAID - - REAR GRAB BARS 6" MAX FROM CORNER - - TEMP SINKS IN RESTROOMS NO SOAP, HAND DRYERS - - PROVIDE HEALTH DEPT INSPECTION REPORT -
Occupancy Inspection - Codes Commercial Temporary C of O 2/4/2021 2/3/2021 02/03/2021
Misc
Corrective Action Required
01/29/2021
- TEMP SINKS IN RESTROOMS NO SOAP, HAND DRYERS -
Occupancy Inspection - Codes Commercial Full C of O 2/4/2021 02/04/2021
Misc
Corrective Action Required
02/03/2021
- TEMP SINKS IN RESTROOMS NO SOAP, HAND DRYERS -
Documents & Images
Date Uploaded File Type Document Name
06/23/2020 Application Form Application - Starbucks
06/23/2020 Plans Permit Set 22x34
06/24/2020 Letter Fire Building Plan Review
06/24/2020 Letter DS P/R Corrections Document
07/06/2020 Email New Food Establishment Plan Review - Approved FTG 0001755
07/08/2020 Letter 8779-001_MO_NW Pryor Rd & Chipman - Rev 1 Response Letter
07/08/2020 Plans 87799-001_MO_NW Pryor Rd & Chipman-Rev 1-22x34
07/10/2020 Letter Fire Building Plan Review
07/13/2020 Plans Approved - Starbucks plans
11/23/2020 Letter License Tax Bill
11/24/2020 Application Form Lee's Summit License Tax Form
11/24/2020 Receipt Receipt for transaction:2020-007708
11/24/2020 Letter DS Building Permit
11/30/2020 Letter Codes Plan Review Conditions
12/02/2020 Letter INSPECTION SUMMARY
12/02/2020 Letter INSPECTION SUMMARY
12/02/2020 Letter INSPECTION SUMMARY
12/03/2020 Letter INSPECTION SUMMARY
12/04/2020 Letter INSPECTION SUMMARY
12/15/2020 Letter INSPECTION SUMMARY
12/17/2020 Letter INSPECTION SUMMARY
12/17/2020 Letter INSPECTION SUMMARY
12/21/2020 Letter INSPECTION SUMMARY
12/21/2020 Letter INSPECTION SUMMARY
12/21/2020 Letter INSPECTION SUMMARY
01/06/2021 Letter INSPECTION SUMMARY
01/28/2021 Letter INSPECTION SUMMARY
01/28/2021 Letter INSPECTION SUMMARY
01/28/2021 Letter INSPECTION SUMMARY
01/29/2021 Letter Fire Loss Reduction Form
01/29/2021 Letter INSPECTION SUMMARY
01/29/2021 Letter INSPECTION SUMMARY
01/29/2021 Letter INSPECTION SUMMARY
01/29/2021 Receipt Receipt for transaction:2021-000476
02/03/2021 Letter INSPECTION SUMMARY
02/03/2021 Letter Codes Temporary Certificate of Occupancy
02/04/2021 Letter Codes Final Certificate of Occupancy
02/04/2021 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home