Permit Application Status

PRCOM20200707


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20200707
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
CHANGE OF TENANT
TENANT FINISH FOR RETAIL CLOTHING STORE WITH BAR
03/17/2020
06/02/2020
09/15/2020
09/18/2020
Locations
Contacts
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
[K] WARMAN ARCHITECTS, Address:1828 SWIFT, SUITE 101, Phone:(816) 474-2233  
TRADEMARK ELECTRIC INC, Address:8200 NE US 69 HWY, Phone:(816) 442-8101  
SLOCUM & SONS PLUMBING, Address:3804 S MARSHALL CT, Phone:(816) 373-4817  
BGS CONSTRUCTION, Address:34607 E COLBERN RD, Phone:(816) 566-0351  
PRO PLATINUM LLC, Address:6116 ALDEN RD, Phone:(913) 908-3512  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 07/15/2020
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
07/15/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Sprinkler Plan Review Released for Construction 06/30/2020
Michael Weissenbach
Misc
Corrective Action Required
06/30/2020

(Informational Purposes) Update records showing NFPA 13 2016 Edition
Building Plan Review Approved with Conditions 05/13/2020 05/29/2020
Joe Frogge
Health Dept Review
Resolved
05/29/2020

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 5/7/20 - acknowledged in letter.
Health Dept Inspection
Corrective Action Required
05/06/2020

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 5/7/20 - acknowledged in letter.
CORRIDORS
Corrective Action Required
05/06/2020

Inadequate information to complete review. Action required: Provide complete MEP design. 5/7/20 - Provide the following: - Emergency lighting at exterior side of exits to be field verified.
Code analysis required
Corrective Action Required
05/06/2020

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Update code analysis to show 1:15 in seating area and 1:60 in mercantile. 5/7/20 - 1:30 still used at mercantile but elevated occ load will not affect plan review.
Health Department Review Approved 05/29/2020
Joe Frogge
Licensed Contractors Approved 05/13/2020 05/07/2020
Joe Frogge
LC - General Contractor
Corrective Action Required
05/06/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. (BGS Constr. not licensed)
LC - MEP Subs
Corrective Action Required
05/06/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. (Mechanical contractor required)
Fire Plan Review Approved with Conditions 05/13/2020 05/06/2020
Michael Weissenbach
Posting of occupant load
Corrective Action Required
05/06/2020

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load at 139
Construction documents for fire alarm systems
Corrective Action Required
05/06/2020

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm, provide three sets of PE stamped shop drawings.
Construction documents - Fire protection systems
Corrective Action Required
05/06/2020

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide three sets of PE stamped shop drawings. Note: Walk in cooler will need to be sprinklered. Also, overhead door will need coverage underneath.
Installation acceptance testing
Corrective Action Required
05/06/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Building Plan Review Rejected 03/27/2020 03/19/2020
Joe Frogge
Health Dept Review
Corrective Action Required
03/19/2020

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
03/19/2020

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
CORRIDORS
Corrective Action Required
03/19/2020

Inadequate information to complete review. Action required: Provide complete MEP design.
Code analysis required
Corrective Action Required
03/19/2020

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Update code analysis to show 1:15 in seating area and 1:60 in mercantile.
Licensed Contractors Rejected 03/27/2020 03/19/2020
Joe Frogge
LC - General Contractor
Corrective Action Required
03/19/2020

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor. (BGS Constr. not licensed)
LC - MEP Subs
Corrective Action Required
03/19/2020

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. (Mechanical contractor required)
Fire Plan Review Approved with Conditions 03/27/2020 03/18/2020
Michael Weissenbach
Posting of occupant load
Corrective Action Required
03/18/2020

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load at 139
Construction documents for fire alarm systems
Corrective Action Required
03/18/2020

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm, provide three sets of PE stamped shop drawings.
Construction documents - Fire protection systems
Corrective Action Required
03/18/2020

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide three sets of PE stamped shop drawings. Note: Walk in cooler will need to be sprinklered. Also, overhead door will need coverage underneath.
Installation acceptance testing
Corrective Action Required
03/18/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Fees
Paid Fees Amount Paid Owing Date Paid
7232302-Commercial License Tax Fee $10,357.50 $10,357.50 Paid 03/19/2020
$10,357.50
9110078-Valuation Fee for Change of Tenant $600.00 $600.00 Paid 06/02/2020
8331507-Sewer Connection Fee $60.00 $60.00 Paid 06/02/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Partial 6/9/2020 6/9/2020 06/09/2020
FRAMING/STRUCTURE
Corrective Action Required
06/09/2020
ROUGH FRAMING AND ELECTRICAL WALLS ONLY: WALLS WITH FRAMING AND ELECTRICAL ONLY, DO NOT COVER WALLS OR CEILING WERE PLUBMING IS NOT INSTALLED. NO ABOVE CEILING APPROVED AT THIS INSPECTION. HARD OR TILE CEILING. UNDERSLAB PLUBING NOT INSTALLED AT THIS TIME.
Underslab Plumbing Inspection - Commercial Passed 6/12/2020 6/12/2020 06/12/2020
Above Ceiling Inspection Failed 6/18/2020 6/18/2020 06/18/2020
Misc
Corrective Action Required
06/18/2020
--SUPPORT PEX WATER PIPE 32" HORIZONTAL . --SUPPORT DWV 48"O.C FOR WALL ROUGH-- INSTALL PLUMBING PROTECTION PLATES AT BOTTOM PLATE OF WALLS.
Above Ceiling Inspection Passed 6/19/2020 6/19/2020 06/19/2020
Misc
Resolved
06/19/2020
--SUPPORT PEX WATER PIPE 32" HORIZONTAL . --SUPPORT DWV 48"O.C FOR WALL ROUGH-- INSTALL PLUMBING PROTECTION PLATES AT BOTTOM PLATE OF WALLS.
Alarm Test Passed 8/31/2020 08/31/2020
All Rough Inspection - Commercial Passed 09/11/2020
Occupancy Inspection - Fire Failed 9/11/2020 9/11/2020 09/11/2020
Occupancy Inspection - Codes Commercial Failed 9/11/2020 9/11/2020 09/11/2020
Misc
Corrective Action Required
09/11/2020
- PROVIDE COVER PLATES RECRECEPTACLES AT SINK & CHECKOUT - - PROVIDE BACKFLOW DEVICE AT BEVERAGE DISPENSERS - - PROVIDE AIR GAP AT COFFEE, DISHWASHER & ICE MACHINE - - PROVIDE ( DOOR SHALL REMAIN UNLOCKED DURING BUSINESS HOURS SIGN ) - - PROVIDE 36" OUTSWING DOOR FOR DRESSING ROOM PER PLAN - - ADDRESS CONDUIT ABOVE FLOOR AT CHECKOUT ( TRIP HAZZARD) -
Occupancy Inspection - Fire Passed 9/16/2020 9/16/2020 09/16/2020
Occupancy Inspection - Codes Commercial Failed 9/16/2020 9/16/2020 09/16/2020
Misc
Resolved
09/16/2020
Occupancy Inspection - Codes Commercial Full C of O 9/18/2020 09/18/2020
Documents & Images
Date Uploaded File Type Document Name
03/17/2020 Email RE lt question - prcom20200707
03/18/2020 Letter Fire Building Plan Review
03/19/2020 Letter DS P/R Corrections Document
05/06/2020 Letter CODE RESPONSE PRCOM20200707-4_24_20-SEALED
05/06/2020 Engineer Report/Study Made in KC -Mechanical Project Narrative 4_23_20
05/06/2020 Plans SEALED_Made in KC Lees Summit PERMIT CDs UPDATED 4_23_20
05/06/2020 Letter Fire Building Plan Review
05/07/2020 Application Form Application and LT forms
05/29/2020 Letter License Tax Bill
05/29/2020 Email New Food Establishment Plan Review - Approved FTG 0001373
05/29/2020 Approved Plans Approved - SEALED_Made in KC Lees Summit PERMIT CDs UPDATED 4_23_20
06/02/2020 Receipt Receipt for transaction:2020-002571
06/02/2020 Letter DS Building Permit
06/09/2020 Letter INSPECTION SUMMARY
06/12/2020 Letter INSPECTION SUMMARY
06/18/2020 Letter INSPECTION SUMMARY
06/19/2020 Letter INSPECTION SUMMARY
06/19/2020 Letter Codes Plan Review Conditions
06/30/2020 Letter Fire (Sprinkler) Plan Review
07/15/2020 Letter Fire (Alarm) Plan Review Notice
09/11/2020 Letter INSPECTION SUMMARY
09/16/2020 Letter INSPECTION SUMMARY
09/17/2020 Email New Food Establishment Plan Review - Approved FTG 0001847
09/18/2020 Letter Codes Final Certificate of Occupancy
09/18/2020 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home