Permit Application Status

PRCOM20172339


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20172339
Building Permit - Commercial
Certificate of Occupancy
NSI INVESTMENTS LLC
CHANGE OF TENANT
TENANT FINISH FOR NEW GYM **invite planner to final to verify rtu screening
07/12/2017
08/30/2017
02/26/2018
04/30/2018
Locations
Contacts
THOLEN-WOLFE CONTRACTORS INC, Address:516 NE TOPAZ DR, Phone:(816) 215-0029  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
SUNRISE ELECTRIC INC., Address:4922 PHELPS RD, Phone:(816) 728-2789  
FIVE STAR MECHANICAL CONTRACT INC, Address:P O BOX 11964, Phone:(816) 358-4444  
DK MULLIN ARCHITECTS, Address:512 1/2 SOUTH MAIN STREET, Phone:(208) 892-8433  
NSI INVESTMENTS LLC, Address:1851 MADISON AVE STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 10/27/2017
Joe Dir
Installation acceptance testing
Corrective Action Required
10/27/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: An acceptance test of the system will be required prior to the final occupancy inspection. Contact the fire departmentto schedule testing. (816)969-1300
Misc
Corrective Action Required
10/27/2017

Plan revision ACTION REQUIRED: A revision has been made from the original submitted plan. Please notice on the attached sheet the revision made to the restrooms. Horn/strobes were moved from the restrooms to the locker rooms. Strobe only to be installed in the restrooms.
Sprinkler Plan Review Released for Construction 10/02/2017
Joe Dir
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
10/02/2017

2012 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. ACTION REQUIRED:(veriifed at inspection) The existing fire sprinkler system riser shall be current with all required service and maintenance. A current service tag shall be posted on the systems risers.
Installation acceptance testing
Corrective Action Required
10/31/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Acceptance testing of the modifications to the fire sprinkler system and FDC will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300.
Building Plan Review Approved with Conditions 08/30/2017 08/30/2017
Joe Frogge
Misc
Resolved
08/30/2017

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Provide UL numbers and complete construction details for fire rated assemblies including nail/screw patterns and penetration details.
Code analysis required
Resolved
08/30/2017

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Remove multiple references to VB construction. (T1.0 & EG1.0)
Misc
Corrective Action Required
08/23/2017

Massage facilities shall comply with all provisions of Lee's Summit Code of Ordinances Chapter 28, Division 2. Action required: Comment is for informational purposes. 8/30/17 - acknowledged
Gen - Submittal documents 7-137
Resolved
08/30/2017

Wet seal required by design professional. Action required: Copies of sealed drawings are only allowed when we have the original sealed set also. Provide a complete set of wet sealed drawings.
Bldg - Accessibility - Kitchens and kitchenettes 1109.4
Resolved
08/30/2017

2012 IBC 1109.4 – Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible. Action required: Revise drawings to show that sink in Office #117 is accessible. i.e. mounted no higher than 34".
Bldg - Toilet room wall finish 1210.2.2
Resolved
08/30/2017

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant finish material at mop sinks.
Screening - Rooftop equipment
Corrective Action Required
08/23/2017

Unified Development Ordinance Article 7, Section 7.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section. 8/30/17 - acknowledged - to be field verified
Misc
Resolved
08/30/2017

2012 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer's report for verification that roof structure is capable of supporting load imposed by new roof mounted equipment. 8/30/17 - Not included in submittal.
Misc
Resolved
08/30/2017

2012 IBC 1006.3 – Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply illuminate all of the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that required two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1027.1, in buildings required to have two or more exits. 5. Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required: Provide emergency light at exterior side of NW exit door. 8/30/17 - Electrical lighting plan must be updated.
Licensed Contractors Approved 08/23/2017 08/29/2017
Joe Frogge
LC - MEP Subs
Resolved
08/30/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 08/30/2017 08/28/2017
Joe Dir
Posting of occupant load
Corrective Action Required
08/23/2017

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(verified at inspection) post the occupant load (345) around the front entrance
Construction documents for fire alarm systems
Corrective Action Required
08/23/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of the fire alarm system to be installed.
Address numbers required
Corrective Action Required
08/23/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Post the numeric or albetic suite designation on each door leading into the suite front, rear side doors.
Construction documents - Fire protection systems
Corrective Action Required
08/23/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings for the fire sprinkler system to be installed.
Installation acceptance testing
Corrective Action Required
08/23/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: (information purposes) Acceptance testing of the fire sprinkler and alarm systems will be required prior to the final occupancy inspection.. to schedule testing contact the fire dpeartment at 816-969-1300.
Portable fire extinguishers - general
Corrective Action Required
08/23/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Install 2A-10BC fire extinguishers according to the plan sheet A3.0
Misc
Corrective Action Required
08/23/2017

Door operation ACTION REQUIRED: No keyed locks on the egress side of a marked exit. B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Panic hardware [B] 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. ACTION REQUIRED:
Misc
Resolved
08/28/2017

EXIT-3 Exit 3 is obstructed by the swing of an exit in the adjoining space.
Misc
Resolved
08/28/2017

Duct detection ACTION REQUIRED:wire duct detection into the FACP. 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building’s fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Fire Plan Review Rejected 07/24/2017 07/17/2017
Joe Dir
Posting of occupant load
Corrective Action Required
07/17/2017

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. ACTION REQUIRED:(verified at inspection) post the occupant load (345) around the front entrance
Construction documents for fire alarm systems
Corrective Action Required
07/17/2017

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. ACTION REQUIRED:(information purposes) Have the fire alarm system contractor provide shop drawings of the fire alarm system to be installed.
Address numbers required
Corrective Action Required
07/17/2017

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED:(verified at inspection) Post the numeric or albetic suite designation on each door leading into the suite front, rear side doors.
Construction documents - Fire protection systems
Corrective Action Required
07/17/2017

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED:(information purposes) Have the fire sprinkler system contractor provide shop drawings for the fire sprinkler system to be installed.
Installation acceptance testing
Corrective Action Required
07/17/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: (information purposes) Acceptance testing of the fire sprinkler and alarm systems will be required prior to the final occupancy inspection.. to schedule testing contact the fire dpeartment at 816-969-1300.
Portable fire extinguishers - general
Corrective Action Required
07/17/2017

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED:(verified at inspection) Install 2A-10BC fire extinguishers according to the plan sheet A3.0
Misc
Corrective Action Required
07/17/2017

Door operation ACTION REQUIRED: No keyed locks on the egress side of a marked exit. B] 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Panic hardware [B] 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. ACTION REQUIRED:
Misc
Corrective Action Required
07/17/2017

EXIT-3 Exit 3 is obstructed by the swing of an exit in the adjoining space.
Misc
Corrective Action Required
07/17/2017

Duct detection ACTION REQUIRED:wire duct detection into the FACP. 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building’s fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building’s alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
Building Plan Review Rejected 07/24/2017 07/17/2017
Joe Frogge
Misc
Corrective Action Required
07/17/2017

2012 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. Where materials, systems or devices that have not been tested as part of a fire-resistance-rated assembly are incorporated into the building element, component or assembly, sufficient data shall be made available to the building official to show that the required fire-resistance rating is not reduced. Materials and methods of construction used to protect joints and penetrations in fire resistance-rated building elements, components or assemblies shall not reduce the required fire-resistance rating. Action required: Provide UL numbers and complete construction details for fire rated assemblies including nail/screw patterns and penetration details.
Code analysis required
Corrective Action Required
07/17/2017

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Remove multiple references to VB construction. (T1.0 & EG1.0)
Misc
Corrective Action Required
07/17/2017

Massage facilities shall comply with all provisions of Lee's Summit Code of Ordinances Chapter 28, Division 2. Action required: Comment is for informational purposes.
Gen - Submittal documents 7-137
Corrective Action Required
07/17/2017

Wet seal required by design professional. Action required: Copies of sealed drawings are only allowed when we have the original sealed set also. Provide a complete set of wet sealed drawings.
Bldg - Accessibility - Kitchens and kitchenettes 1109.4
Corrective Action Required
07/17/2017

2012 IBC 1109.4 – Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible. Action required: Revise drawings to show that sink in Office #117 is accessible. i.e. mounted no higher than 34".
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
07/17/2017

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant finish material at mop sinks.
Screening - Rooftop equipment
Corrective Action Required
07/17/2017

Unified Development Ordinance Article 7, Section 7.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Misc
Corrective Action Required
07/17/2017

2012 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer's report for verification that roof structure is capable of supporting load imposed by new roof mounted equipment.
Misc
Corrective Action Required
07/17/2017

2012 IBC 1006.3 – Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply illuminate all of the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that required two or more means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1027.1, in buildings required to have two or more exits. 5. Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required: Provide emergency light at exterior side of NW exit door.
Licensed Contractors Rejected 07/12/2017 07/14/2017
Joe Frogge
LC - MEP Subs
Corrective Action Required
07/14/2017

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $2,655.25 $2,655.25 Paid 08/30/2017
8331507-Sewer Connection Fee $750.00 $750.00 Paid 08/30/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Not Ready 8/31/2017 8/31/2017 at 4:35 AM 08/31/2017
Misc
Corrective Action Required
08/31/2017
EXPOSE ALL PIPING AND CONNECTIONS FOR INSPECTION.
Underslab Electrical Inspection - Commercial Passed 8/31/2017 8/31/2017 at 8:45 AM 08/31/2017
In-wall Inspection Not Ready 8/31/2017 at 9:05 AM 08/31/2017
Misc
Corrective Action Required
08/31/2017
FALSE WALL AT PERIMETER NOT COMPLETED FOR INSPECTION. STUDS NOT BRACED TO STRUCTURE AT MID-HEIGHT.
Misc
Corrective Action Required
08/31/2017
DEMISING WALL AT EAST NOT COMPLETED FOR INSPECTION. HORIZONTAL BRIDGING IS INCOMPLETE AND NOT ENGAGED WITH STUDS.
Underslab Plumbing Inspection - Commercial Passed 9/1/2017 9/1/2017 at 9:30 AM 09/01/2017
Misc
Resolved
09/01/2017
EXPOSE ALL PIPING AND CONNECTIONS FOR INSPECTION.
In-wall Inspection Partial 9/7/2017 at 1:35 PM 09/07/2017
Misc
Partial Correction
09/07/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING + ENCLOSED M/E/P SYSTEMS AT: FALSE WALL AT PERIMETER EXCEPT SOUTH WALL PARTIAL PENDING CREATION/MODIFICATION OF OPENINGS; EAST DEMISING WALL EXCEPT NORTH 10' NOT YET FRAMED;
Misc
Resolved
09/07/2017
DEMISING WALL AT EAST NOT COMPLETED FOR INSPECTION. HORIZONTAL BRIDGING IS INCOMPLETE AND NOT ENGAGED WITH STUDS.
In-wall Inspection Partial 9/21/2017 9/21/2017 at 11:35 AM 09/21/2017
Misc
Partial Correction
09/07/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING + ENCLOSED M/E/P SYSTEMS AT: FALSE WALL AT PERIMETER EXCEPT SOUTH WALL PARTIAL PENDING CREATION/MODIFICATION OF OPENINGS; EAST DEMISING WALL EXCEPT NORTH 10' NOT YET FRAMED;
Misc
Partial Correction
09/21/2017
MENS, WOMANS, JANITOR ROOMS: INSTALL BOCA PLATE JANITOR ROOM, COMPLETE SHOWER WATER SUPPLY INSTALLATION IN BOTH LOCKER ROOMS. OKAY TO COVER OTHER AREAS.
In-wall Inspection Partial 9/25/2017 9/25/2017 at 8:05 AM 09/25/2017
Misc
Partial Correction
09/21/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING + ENCLOSED M/E/P SYSTEMS AT: FALSE WALL AT PERIMETER EXCEPT SOUTH WALL PARTIAL PENDING CREATION/MODIFICATION OF OPENINGS; EAST DEMISING WALL EXCEPT NORTH 10' NOT YET FRAMED;
Misc
Partial Correction
09/21/2017
LOCKER ROOMS, MENS, WOMANS, SHOWERS, JANITOR ROOMS;
Miscellaneous Inspection Partial 9/26/2017 09/26/2017
Rated Assembly Inspection Partial 9/27/2017 9/27/2017 at 10:05 AM 09/27/2017
Misc
Partial Correction
09/27/2017
EAST 1 HOUR WALL DIVIDING THIS SPACE FROM ADJOINING SPACE: PLAN CALLS FOR 5/8THS X GYP ON EACH SIDE. WEST SIDE OF WALL LAYER IS APPROVED. EAST SIDE OF WALL YET TO BE INSTALLED.
In-wall Inspection Partial 10/3/2017 at 4:00 PM 10/03/2017
Misc
Partial Correction
09/25/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING + ENCLOSED M/E/P SYSTEMS AT: FALSE WALL AT PERIMETER EXCEPT SOUTH WALL PARTIAL PENDING CREATION/MODIFICATION OF OPENINGS; EAST DEMISING WALL EXCEPT NORTH 10' NOT YET FRAMED;
Misc
Partial Correction
09/25/2017
LOCKER ROOMS, MENS, WOMANS, SHOWERS, JANITOR ROOMS;111A-H;112A;115 A-E;117;116 RECEPTION GEAR SOFFIT;TANNING LOBBY.
Above Ceiling Inspection Partial 10/11/2017 at 11:05 AM 10/11/2017
Misc
Partial Correction
10/11/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: BULKHEAD @ HIPS/ABS/ STRETCHING E/SW/S;
In-wall Inspection Partial 10/11/2017 10/11/2017 at 10:45 AM 10/11/2017
Misc
Partial Correction
10/03/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING + ENCLOSED M/E/P SYSTEMS AT: FALSE WALL AT PERIMETER EXCEPT SOUTH WALL PARTIAL PENDING CREATION/MODIFICATION OF OPENINGS; EAST DEMISING WALL; WALLS SURROUNDING EGRESS HALL 118; PONY WALLS AT HIPS/ABS/STRETCHING;
Misc
Resolved
10/11/2017
LOCKER ROOMS, MENS, WOMANS, SHOWERS, JANITOR ROOMS;111A-H;112A;115 A-E;117;116 RECEPTION GEAR SOFFIT;TANNING LOBBY.
Rough Framing Inspection - Commercial Passed 10/12/2017 at 2:50 PM 10/12/2017
Rated Assembly Inspection Partial 10/16/2017 10/16/2017 at 10:10 AM 10/16/2017
Misc
Partial Correction
09/27/2017
EAST 1 HOUR WALL DIVIDING THIS SPACE FROM ADJOINING SPACE: PLAN CALLS FOR 5/8THS X GYP ON EACH SIDE. WEST SIDE OF WALL LAYER IS APPROVED. EAST FACE OF WALL OK TO TAPE, MUD AND FIRE-STOP WHEN READY.
In-wall Inspection Partial 11/7/2017 11/7/2017 at 10:20 AM 11/07/2017
Misc
Partial Correction
10/11/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING + ENCLOSED M/E/P SYSTEMS AT: FALSE WALL AT PERIMETER EXCEPT SOUTH WALL PARTIAL PENDING CREATION/MODIFICATION OF OPENINGS; EAST DEMISING WALL; WALLS SURROUNDING EGRESS HALL 118; PONY WALLS AT HIPS/ABS/STRETCHING; REMAINING WALL SECTIONS AT 104 & 109; 112 S WALL; ADDED WALLS CENTERED AT (4.6)/(E.8)-(F) TO ENCLOSE SPACE AT NE "NON-EGRESS" REAR ENTRANCE;
Above Ceiling Inspection Partial 11/7/2017 at 11:15 AM 11/07/2017
Misc
Partial Correction
10/11/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: BULKHEAD @ HIPS/ABS/ STRETCHING E/SW/S; REMAINING NARROW SOFFITS AT SOUTH;
Misc
Partial Correction
11/07/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: CUT BORDER TILE LESS THAN 2' ONLY AT 102; 104; 109;
Above Ceiling Inspection Partial 11/17/2017 11/17/2017 at 1:10 PM 11/17/2017
Misc
Partial Correction
11/07/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: BULKHEAD @ HIPS/ABS/ STRETCHING E/SW/S; REMAINING NARROW SOFFITS AT SOUTH;
Misc
Partial Correction
11/17/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 103A - 103C; 104 - 109; 111A - 111H; 112A; 115A - 115C; 116 FRONT DESK;
In-wall Inspection Partial 12/5/2017 at 4:40 PM 12/05/2017
Misc
Partial Correction
11/07/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING + ENCLOSED M/E/P SYSTEMS AT: FALSE WALL AT PERIMETER EXCEPT SOUTH WALL PARTIAL PENDING CREATION/MODIFICATION OF OPENINGS; EAST DEMISING WALL; WALLS SURROUNDING EGRESS HALL 118; PONY WALLS AT HIPS/ABS/STRETCHING; REMAINING WALL SECTIONS AT 104 & 109; 112 S WALL; ADDED WALLS CENTERED AT (4.6)/(E.8)-(F) TO ENCLOSE SPACE AT NE "NON-EGRESS" REAR ENTRANCE; [AREA 116 SOUTH WALL;
Above Ceiling Inspection Partial 12/7/2017 at 1:10 PM 12/07/2017
Misc
Partial Correction
11/17/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: BULKHEAD @ HIPS/ABS/ STRETCHING E/SW/S; REMAINING NARROW SOFFITS AT SOUTH; [HANGING STRUCTURE AT FRONT VESTIBULE;
Misc
Partial Correction
11/17/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 103A - 103C; 104 - 109; 111A - 111H; 112A; 115A - 115C; 116 FRONT DESK;
Miscellaneous Inspection Partial 12/13/2017 at 3:05 PM 12/13/2017
Electrical Service Inspection Passed 12/18/2017 12/19/2017 at 9:50 AM 12/19/2017
Above Ceiling Inspection Partial 12/19/2017 at 10:01 AM 12/19/2017
Misc
Partial Correction
12/07/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: BULKHEAD @ HIPS/ABS/ STRETCHING E/SW/S; REMAINING NARROW SOFFITS AT SOUTH; [HANGING STRUCTURE AT FRONT VESTIBULE;
Misc
Partial Correction
12/07/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 103A - 103C; 104 - 109; 111A - 111H; 112A; 115A - 115C; 116 FRONT DESK;
Misc
Partial Correction
12/19/2017
JANIOR AREA BETWEEN LOCKER ROOMS, OFFICE, CHECK IN DESK AREA AND ENTRANCE AREAS APPROVED.
Rough Electrical Inspection - Commercial Not Ready 12/22/2017 12/22/2017 at 11:45 AM 12/22/2017
Misc
Corrective Action Required
12/22/2017
WET TILE, NO ACCESS
Alarm Test Passed 12/27/2017 12/27/2017
Misc
Partial Correction
11/07/2017
Rough Electrical Inspection - Commercial Passed 12/27/2017 12/27/2017 at 2:25 PM 12/27/2017
Misc
Resolved
12/27/2017
WET TILE, NO ACCESS
Occupancy Inspection - Codes Commercial Temporary C of O 12/29/2017 12/29/2017 at 8:30 AM 12/29/2017
Misc
Corrective Action Required
12/29/2017
ROOFTOP INSPECTION TO BE REQUESTED AND PERFORMED WHEN READY.
Misc
Corrective Action Required
12/29/2017
PLANNING INSPECTION TO BE REQUESTED AND PERFORMED AFTER FACADE IS COMPLETED AND RTU SCREENING IS IN PLACE.
Misc
Corrective Action Required
12/29/2017
AFFIX PERMANENT ADDRESS LABEL TO ELECTRICAL SERVICE METER/DISCONNECT
Misc
Corrective Action Required
12/29/2017
PERMANENT PATCH OPENING IN EXTERIOR REAR WALL WHERE ELECTRICAL FEEDER CONDUITS ENTER BUILDING.
Misc
Corrective Action Required
12/29/2017
GLAZING AT SOUTH ENTRY SUBJECT TO APPROVAL WHEN INSTALLED (MUST BE ETCHED "TEMPERED").
Misc
Corrective Action Required
12/29/2017
AIRLOCK AT SOUTH ENTRANCE SUBJECT TO APPROVAL WHEN INSTALLED (GLAZING MUST BE ETCHED "TEMPERED").
Misc
Corrective Action Required
12/29/2017
HANDRAILS AT SOUTH RAMP AND NORTH ENTRANCE SUBJECT TO APPROVAL WHEN COMPLETED PERMANENT.
Misc
Corrective Action Required
12/29/2017
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Occupancy Inspection - Fire Passed 12/29/2017 12/29/2017
Above Ceiling Inspection Passed 12/19/2017 01/02/2018
Misc
Resolved
01/02/2018
OK TO COVER WHEN READY GWB CEILING / SOFFIT / BULKHEAD FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING LOCATIONS: BULKHEAD @ HIPS/ABS/ STRETCHING E/SW/S; REMAINING NARROW SOFFITS AT SOUTH; [HANGING STRUCTURE AT FRONT VESTIBULE;
Misc
Resolved
01/02/2018
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @: 103A - 103C; 104 - 109; 111A - 111H; 112A; 115A - 115C; 116 FRONT DESK;
Misc
Resolved
01/02/2018
JANIOR AREA BETWEEN LOCKER ROOMS, OFFICE, CHECK IN DESK AREA AND ENTRANCE AREAS APPROVED.
In-wall Inspection Passed 12/5/2017 01/02/2018
Misc
Resolved
01/02/2018
OK TO COVER WHEN READY LIGHT-GAUGE STEEL FRAMING + ENCLOSED M/E/P SYSTEMS AT: FALSE WALL AT PERIMETER EXCEPT SOUTH WALL PARTIAL PENDING CREATION/MODIFICATION OF OPENINGS; EAST DEMISING WALL; WALLS SURROUNDING EGRESS HALL 118; PONY WALLS AT HIPS/ABS/STRETCHING; REMAINING WALL SECTIONS AT 104 & 109; 112 S WALL; ADDED WALLS CENTERED AT (4.6)/(E.8)-(F) TO ENCLOSE SPACE AT NE "NON-EGRESS" REAR ENTRANCE; [AREA 116 SOUTH WALL;
Miscellaneous Inspection Passed 12/13/2017 01/02/2018
Rated Assembly Inspection Passed 10/16/2017 01/02/2018
Misc
Resolved
01/02/2018
EAST 1 HOUR WALL DIVIDING THIS SPACE FROM ADJOINING SPACE: PLAN CALLS FOR 5/8THS X GYP ON EACH SIDE. WEST SIDE OF WALL LAYER IS APPROVED. EAST FACE OF WALL OK TO TAPE, MUD AND FIRE-STOP WHEN READY.
Occupancy Inspection - Codes Commercial Partial 1/2/2018 at 2:30 PM 01/02/2018
Misc
Corrective Action Required
12/29/2017
ROOFTOP INSPECTION TO BE REQUESTED AND PERFORMED WHEN READY.
Misc
Corrective Action Required
12/29/2017
PLANNING INSPECTION TO BE REQUESTED AND PERFORMED AFTER FACADE IS COMPLETED AND RTU SCREENING IS IN PLACE.
Misc
Corrective Action Required
12/29/2017
AFFIX PERMANENT ADDRESS LABEL TO ELECTRICAL SERVICE METER/DISCONNECT
Misc
Corrective Action Required
12/29/2017
PERMANENT PATCH OPENING IN EXTERIOR REAR WALL WHERE ELECTRICAL FEEDER CONDUITS ENTER BUILDING.
Misc
Resolved
01/02/2018
GLAZING AT SOUTH ENTRY SUBJECT TO APPROVAL WHEN INSTALLED (MUST BE ETCHED "TEMPERED").
Misc
Corrective Action Required
12/29/2017
AIRLOCK AT SOUTH ENTRANCE SUBJECT TO APPROVAL WHEN INSTALLED (GLAZING MUST BE ETCHED "TEMPERED").
Misc
Corrective Action Required
12/29/2017
HANDRAILS AT SOUTH RAMP AND NORTH ENTRANCE SUBJECT TO APPROVAL WHEN COMPLETED PERMANENT.
Misc
Corrective Action Required
12/29/2017
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Occupancy Inspection - Codes Commercial Temporary C of O 1/10/2018 1/10/2018 at 9:40 AM 01/10/2018
Misc
Corrective Action Required
01/02/2018
ROOFTOP INSPECTION TO BE REQUESTED AND PERFORMED WHEN READY.
Misc
Corrective Action Required
01/02/2018
PLANNING INSPECTION TO BE REQUESTED AND PERFORMED AFTER FACADE IS COMPLETED AND RTU SCREENING IS IN PLACE.
Misc
Resolved
01/10/2018
AFFIX PERMANENT ADDRESS LABEL TO ELECTRICAL SERVICE METER/DISCONNECT
Misc
Resolved
01/10/2018
PERMANENT PATCH OPENING IN EXTERIOR REAR WALL WHERE ELECTRICAL FEEDER CONDUITS ENTER BUILDING.
Misc
Corrective Action Required
01/02/2018
AIRLOCK AT SOUTH ENTRANCE SUBJECT TO APPROVAL WHEN INSTALLED (GLAZING MUST BE ETCHED "TEMPERED").
Misc
Resolved
01/10/2018
HANDRAILS AT SOUTH RAMP AND NORTH ENTRANCE SUBJECT TO APPROVAL WHEN COMPLETED PERMANENT.
Misc
Resolved
01/10/2018
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Occupancy Inspection - Codes Commercial Failed 1/25/2018 1/25/2018 at 8:40 AM 01/25/2018
Misc
Corrective Action Required
01/10/2018
ROOFTOP NOT READY FOR FINAL INSPECTION: - REMOVE ABANDONED EQUIPMENT AND MATERIAL - RTU SCREENING DRAWINGS JUST SUBMITTED; INSTALLATION SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Corrective Action Required
01/10/2018
PLANNING INSPECTION TO BE REQUESTED AND PERFORMED AFTER FACADE IS COMPLETED AND RTU SCREENING IS IN PLACE.
Misc
Resolved
01/25/2018
AIRLOCK AT SOUTH ENTRANCE SUBJECT TO APPROVAL WHEN INSTALLED (GLAZING MUST BE ETCHED "TEMPERED").
Misc
Corrective Action Required
01/25/2018
MINIMUM 42" HIGH ROOF EDGE GUARD IS REQUIRED WHERE ACCESS HATCH AND APPLIANCES REQUIRING SERVICING ARE LOCATED WITHIN 10' OF ROOF EDGE. SEE IMC FOR DETAILED REQUIREMENTS.
Misc
Corrective Action Required
01/25/2018
IFGC 407 / 415: STEEL GAS PIPING SUPPORT SPACING INTERVAL: MAXIMUM 8' FOR 3/4" OR 1"; 10' FOR 1-1/4" OR LARGER. LOOSE-CLAMP PIPE AT ALL SUPPORTS. IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED FOR CLEANING AND REPLACED. BOTTOM OF CAP TO BE NO CLOSER TO ROOF THAN DEPTH OF CAP + 1/4". IFGC 407; 415: PROTECTION OF ROOF MEMBRANE UNDER WOODEN PIPING SUPPORT BLOCKS FOR ROOFTOP EQUIPMENT AND GAS PIPING: COMPLY WITH MAXIMUM SUPPORT SPACING PER IFGC. USE WEATHER-RESISTANT BLOCKING MATERIAL PROVIDING SOLID SUPPORT UNDER PIPE. LOOSE-CLAMP BLOCKS TO PIPE. APPLY SPECIFIED / APPROVED, ROOF-COMPATIBLE SLIP SHEET TO UNDERSIDE OF BLOCKS WITH METAL FASTENERS AT SIDES OF BLOCKS. IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING AT METER AND ROOFTOP.
Occupancy Inspection - Codes Commercial Temporary C of O 1/25/2018 01/25/2018
Misc
Corrective Action Required
01/25/2018
ROOFTOP NOT READY FOR FINAL INSPECTION: - REMOVE ABANDONED EQUIPMENT AND MATERIAL - RTU SCREENING DRAWINGS ONLY PRESENTLY SUBMITTED; PLANNING INSPECTION TO BE REQUESTED AND PERFORMED AFTER RTU SCREENING IS IN PLACE.
Misc
Resolved
01/25/2018
Misc
Corrective Action Required
01/25/2018
MINIMUM 42" HIGH ROOF EDGE GUARD IS REQUIRED WHERE ACCESS HATCH AND APPLIANCES REQUIRING SERVICING ARE LOCATED WITHIN 10' OF ROOF EDGE. SEE IMC FOR DETAILED REQUIREMENTS.
Misc
Corrective Action Required
01/25/2018
IFGC 407 / 415: STEEL GAS PIPING SUPPORT SPACING INTERVAL: MAXIMUM 8' FOR 3/4" OR 1"; 10' FOR 1-1/4" OR LARGER. LOOSE-CLAMP PIPE AT ALL SUPPORTS. IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED FOR CLEANING AND REPLACED. BOTTOM OF CAP TO BE NO CLOSER TO ROOF THAN DEPTH OF CAP + 1/4". IFGC 407; 415: PROTECTION OF ROOF MEMBRANE UNDER WOODEN PIPING SUPPORT BLOCKS FOR ROOFTOP EQUIPMENT AND GAS PIPING: COMPLY WITH MAXIMUM SUPPORT SPACING PER IFGC. USE WEATHER-RESISTANT BLOCKING MATERIAL PROVIDING SOLID SUPPORT UNDER PIPE. LOOSE-CLAMP BLOCKS TO PIPE. APPLY SPECIFIED / APPROVED, ROOF-COMPATIBLE SLIP SHEET TO UNDERSIDE OF BLOCKS WITH METAL FASTENERS AT SIDES OF BLOCKS. IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING AT METER AND ROOFTOP.
Occupancy Inspection - Codes Commercial Temporary C of O 2/14/2018 at 11:25 AM 02/14/2018
Misc
Corrective Action Required
01/25/2018
ROOFTOP NOT READY FOR FINAL INSPECTION: - REMOVE ABANDONED EQUIPMENT AND MATERIAL - RTU SCREENING DRAWINGS ONLY PRESENTLY SUBMITTED; PLANNING INSPECTION TO BE REQUESTED AND PERFORMED AFTER RTU SCREENING IS IN PLACE.
Misc
Corrective Action Required
01/25/2018
MINIMUM 42" HIGH ROOF EDGE GUARD IS REQUIRED WHERE ACCESS HATCH AND APPLIANCES REQUIRING SERVICING ARE LOCATED WITHIN 10' OF ROOF EDGE. SEE IMC FOR DETAILED REQUIREMENTS.
Misc
Corrective Action Required
01/25/2018
IFGC 407 / 415: STEEL GAS PIPING SUPPORT SPACING INTERVAL: MAXIMUM 8' FOR 3/4" OR 1"; 10' FOR 1-1/4" OR LARGER. LOOSE-CLAMP PIPE AT ALL SUPPORTS. IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED FOR CLEANING AND REPLACED. BOTTOM OF CAP TO BE NO CLOSER TO ROOF THAN DEPTH OF CAP + 1/4". IFGC 407; 415: PROTECTION OF ROOF MEMBRANE UNDER WOODEN PIPING SUPPORT BLOCKS FOR ROOFTOP EQUIPMENT AND GAS PIPING: COMPLY WITH MAXIMUM SUPPORT SPACING PER IFGC. USE WEATHER-RESISTANT BLOCKING MATERIAL PROVIDING SOLID SUPPORT UNDER PIPE. LOOSE-CLAMP BLOCKS TO PIPE. APPLY SPECIFIED / APPROVED, ROOF-COMPATIBLE SLIP SHEET TO UNDERSIDE OF BLOCKS WITH METAL FASTENERS AT SIDES OF BLOCKS. IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING AT METER AND ROOFTOP.
Occupancy Inspection - Codes Commercial Partial 3/14/2018 at 4:00 PM 03/14/2018
Misc
Corrective Action Required
02/14/2018
ROOFTOP FINAL INSPECTION: - REMOVE ABANDONED EQUIPMENT AND MATERIAL - CONTACT HECTOR SOTO @ 816-969-1238 TO REQUEST LS PLANNING INSPECTION OF COMPLETED RTU SCREENING - RTU SCREENS ARE NOT SECURED TO ROOF STRUCTURE - FINAL CLEAN ALL DEBRIS AND LOOSE MATERIAL FROM PLANET FITNESS ROOFTOP FOOTPRINT
Misc
Resolved
03/14/2018
MINIMUM 42" HIGH ROOF EDGE GUARD IS REQUIRED WHERE ACCESS HATCH AND APPLIANCES REQUIRING SERVICING ARE LOCATED WITHIN 10' OF ROOF EDGE. SEE IMC FOR DETAILED REQUIREMENTS.
Misc
Corrective Action Required
02/14/2018
IFGC 407; 415: PROTECTION OF ROOF MEMBRANE UNDER WOODEN PIPING SUPPORT BLOCKS FOR ROOFTOP EQUIPMENT AND GAS PIPING: APPLY SPECIFIED / APPROVED, ROOF-COMPATIBLE SLIP SHEET TO UNDERSIDE OF BLOCKS WITH METAL FASTENERS AT SIDES OF BLOCKS. SOME WOOD BLOCKS LACK SLIP SHEETS
Occupancy Inspection - Codes Commercial Temporary C of O 3/15/2018 03/15/2018
Misc
Corrective Action Required
03/14/2018
ROOFTOP FINAL INSPECTION: - REMOVE ABANDONED EQUIPMENT AND MATERIAL - CONTACT HECTOR SOTO @ 816-969-1238 TO REQUEST LS PLANNING INSPECTION OF COMPLETED RTU SCREENING - RTU SCREENS ARE NOT SECURED TO ROOF STRUCTURE - FINAL CLEAN ALL DEBRIS AND LOOSE MATERIAL FROM PLANET FITNESS ROOFTOP FOOTPRINT
Misc
Corrective Action Required
03/14/2018
IFGC 407; 415: PROTECTION OF ROOF MEMBRANE UNDER WOODEN PIPING SUPPORT BLOCKS FOR ROOFTOP EQUIPMENT AND GAS PIPING: APPLY SPECIFIED / APPROVED, ROOF-COMPATIBLE SLIP SHEET TO UNDERSIDE OF BLOCKS WITH METAL FASTENERS AT SIDES OF BLOCKS. SOME WOOD BLOCKS LACK SLIP SHEETS.
Occupancy Inspection - Codes Commercial Temporary C of O 4/26/2018 4/26/2018 at 10:20 AM 04/26/2018
Misc
Corrective Action Required
03/15/2018
ROOFTOP FINAL INSPECTION: - CONTACT HECTOR SOTO @ 816-969-1238 TO REQUEST LS PLANNING INSPECTION OF COMPLETED RTU SCREENING
Misc
Resolved
04/26/2018
IFGC 407; 415: PROTECTION OF ROOF MEMBRANE UNDER WOODEN PIPING SUPPORT BLOCKS FOR ROOFTOP EQUIPMENT AND GAS PIPING: APPLY SPECIFIED / APPROVED, ROOF-COMPATIBLE SLIP SHEET TO UNDERSIDE OF BLOCKS WITH METAL FASTENERS AT SIDES OF BLOCKS. SOME WOOD BLOCKS LACK SLIP SHEETS.
Occupancy Inspection - Planning Passed 4/26/2018 04/26/2018
Informational
04/26/2018
Site work continues for the overall site, but today's inspection revealed no visible evidence of rtus.
Occupancy Inspection - Codes Commercial Full C of O 4/30/2018 at 4:25 PM 04/30/2018
Misc
Resolved
04/30/2018
ROOFTOP FINAL INSPECTION: - CONTACT HECTOR SOTO @ 816-969-1238 TO REQUEST LS PLANNING INSPECTION OF COMPLETED RTU SCREENING
Documents & Images
Date Uploaded File Type Document Name
07/17/2017 Letter Fire Building Plan Review
07/18/2017 Letter Codes P/R Corrections Document
08/28/2017 Letter Fire Building Plan Review
08/30/2017 Letter Codes P/R Corrections Document
08/30/2017 Letter Codes Plan Review Conditions
08/30/2017 Receipt Receipt for transaction: 2017-006098
08/30/2017 Letter Codes Building Permit
08/31/2017 Letter Inspection Summary
09/01/2017 Letter Inspection Summary
09/07/2017 Letter Inspection Summary
09/21/2017 Letter Inspection Summary
09/25/2017 Letter Inspection Summary
09/27/2017 Letter Inspection Summary
10/02/2017 Letter Fire (Sprinkler) Plan Review
10/03/2017 Letter Inspection Summary
10/03/2017 Letter Inspection Summary
10/11/2017 Letter Inspection Summary
10/12/2017 Letter Inspection Summary
10/16/2017 Letter Inspection Summary
10/27/2017 Letter Fire (Alarm) Plan Review Notice
10/31/2017 Letter Fire (Sprinkler) Plan Review
11/07/2017 Letter Inspection Summary
11/07/2017 Letter Inspection Summary
11/17/2017 Letter Inspection Summary
12/05/2017 Letter Inspection Summary
12/07/2017 Letter Inspection Summary
12/19/2017 Letter Inspection Summary
12/22/2017 Letter Inspection Summary
12/27/2017 Letter Inspection Summary
12/29/2017 Letter Codes Temporary Certificate of Occupancy
01/10/2018 Letter Codes Temporary Certificate of Occupancy
01/25/2018 Letter Inspection Summary
01/25/2018 Letter Codes Temporary Certificate of Occupancy
02/14/2018 Letter Codes Temporary Certificate of Occupancy
03/14/2018 Letter Inspection Summary
03/15/2018 Letter Codes Temporary Certificate of Occupancy
04/26/2018 Letter Codes Temporary Certificate of Occupancy
04/26/2018 Letter Planning Inspection Summary
04/30/2018 Letter Field Certificate of Occupancy
05/01/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home