Permit Application Status

PRCOM20172129


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20172129
Building Permit - Commercial
Certificate of Occupancy
SOUTHSIDE PLAZA LLC
REPAIR REPLACE UPGRADE
FIRE REPAIR
06/26/2017
06/26/2017
03/09/2018
Locations
Contacts
CATCO INC, Address:3601 S PONCA DR, Phone:(816) 795-9100  
THREE TRAILS HEATING COOLING, Address:13223 S 71 HWY, Phone:(816) 701-6377  
CLAYCO ELECTRIC COMPANY, Address:319 E 11TH AVE, Phone:(816) 221-0593  
LEXINGTON PLUMBING & HEATING, Address:1620 TROOST AVE, Phone:(816) 231-2254  
SOUTHSIDE PLAZA LLC, Address:215 W 77TH ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 07/07/2017 06/26/2017
Joe Frogge
Health Dept Inspection
Corrective Action Required
06/26/2017

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Licensed Contractors Approved 06/26/2017 06/26/2017
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Repair/Replace/Upgrade $1,026.15 $1,026.15 Paid 06/26/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Passed 7/24/2017 7/24/2017 07/24/2017
In-wall Inspection Failed 10/16/2017 at 10:35 AM 10/16/2017
Misc
Corrective Action Required
10/16/2017
COMPLETE REPAIR OF EXISTING WALL FRAMING FOR STREGTH AND TRUENESS.
Misc
Corrective Action Required
10/16/2017
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES WHERE SPACE ALLOWS). CHECK ALL.
Misc
Corrective Action Required
10/16/2017
IPC 305 PROTECTION OF COPPER PIPING AT POTENTIAL CONTACT WITH STEEL OR OTHER DISSIMILAR METALS: INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL.
Misc
Corrective Action Required
10/16/2017
NEC 300-11, 330.30 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: NOT SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES.
Misc
Corrective Action Required
10/16/2017
NEC 110-12: UNUSED OPENINGS AT ELECTRICAL PANELS / JUNCTION BOXES NOT PLUGGED. CHECK ALL.
Misc
Corrective Action Required
10/16/2017
INSPECT BLACKENED AREAS OF DRYWALL FOR POSSIBLE MOLD. REPLACE OR REMEDIATE AS REQUIRED.
In-wall Inspection Not Ready 10/19/2017 at 8:15 AM 10/19/2017
Misc
Corrective Action Required
10/16/2017
COMPLETE REPAIR OF EXISTING WALL FRAMING FOR STREGTH AND TRUENESS. PROVIDE ARCHITECT REPORT ON BULKHEAD FRAMING BEHIND GREASE HOOD
Misc
Corrective Action Required
10/16/2017
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES WHERE SPACE ALLOWS). CHECK ALL.
Misc
Corrective Action Required
10/16/2017
IPC 305 PROTECTION OF COPPER PIPING AT POTENTIAL CONTACT WITH STEEL OR OTHER DISSIMILAR METALS: INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL.
Misc
Corrective Action Required
10/16/2017
NEC 300-11, 330.30 & 334-10 ENSURE MC ELECTRICAL CABLE: IS SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES.
Misc
Corrective Action Required
10/16/2017
NEC 110-12: UNUSED OPENINGS AT ELECTRICAL PANELS / JUNCTION BOXES NOT PLUGGED. CHECK ALL.
Misc
Corrective Action Required
10/16/2017
PROVIDE JACKSON COUNTY HEALTH DEPARTMENT REPORT ON BLACKENED AREAS OF DRYWALL FOR POSSIBLE MOLD.
Misc
Corrective Action Required
10/19/2017
NO FURTHER INSPECTIONS WITHOUT CITY-STAMPED PRINTS ON JOBSITE -- NOT TO BE USED AS WORKING SET.
Gas Piping Inspection - Commercial Partial 11/1/2017 at 1:45 PM 11/01/2017
Misc
Partial Correction
11/01/2017
PRESSURE TEST ON PIPING AT WATER HEATERS AND TO ROOFTOP HELD STEADY AT >10 PSI FOR >20 MIN.
In-wall Inspection Partial 11/1/2017 11/1/2017 at 11:15 AM 11/01/2017
Misc
Resolved
11/01/2017
COMPLETE REPAIR OF EXISTING WALL FRAMING FOR STREGTH AND TRUENESS. PROVIDE ARCHITECT REPORT ON BULKHEAD FRAMING BEHIND GREASE HOOD
Misc
Corrective Action Required
10/19/2017
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES WHERE SPACE ALLOWS). CHECK ALL.
Misc
Resolved
11/01/2017
IPC 305 PROTECTION OF COPPER PIPING AT POTENTIAL CONTACT WITH STEEL OR OTHER DISSIMILAR METALS: INSTALL GROMMETS OR OTHER APPROVED PROTECTION FROM SHARP EDGES & DISSIMILAR METAL.
Misc
Resolved
11/01/2017
NEC 300-11, 330.30 & 334-10 ENSURE MC ELECTRICAL CABLE: IS SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES.
Misc
Resolved
11/01/2017
NEC 110-12: UNUSED OPENINGS AT ELECTRICAL PANELS / JUNCTION BOXES NOT PLUGGED. CHECK ALL.
Misc
Resolved
11/01/2017
PROVIDE JACKSON COUNTY HEALTH DEPARTMENT REPORT ON BLACKENED AREAS OF DRYWALL FOR POSSIBLE MOLD.
Misc
Resolved
10/19/2017
NO FURTHER INSPECTIONS WITHOUT CITY-STAMPED PRINTS ON JOBSITE -- NOT TO BE USED AS WORKING SET.
Misc
Partial Correction
11/01/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: AFTER ONE BLUNDER PLUG IS INSTALLED EXTERIOR WALLS OK EXCEPT NORTH WALL; INTERIOR WALLS AT DINING;
In-wall Inspection Partial 11/2/2017 11/2/2017 at 8:25 AM 11/02/2017
Misc
Corrective Action Required
11/01/2017
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES WHERE SPACE ALLOWS). CHECK ALL.
Misc
Partial Correction
11/01/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: SOUTH FACE OF MAIN E/W WALL AND ALL SOUTH OF IT;
In-wall Inspection Passed 11/3/2017 11/3/2017 at 11:20 AM 11/03/2017
Misc
Resolved
11/03/2017
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS (USE "BOCA" PLATES WHERE SPACE ALLOWS). CHECK ALL.
Misc
Resolved
11/03/2017
OK TO COVER WHEN READY LIGHT-GAUGE STEEL WALL FRAMING + IN-WALL SYSTEMS AT: SOUTH FACE OF MAIN E/W WALL AND ALL SOUTH OF IT;
Above Ceiling Inspection Not Ready 12/27/2017 2/21/2018 at 3:55 PM 12/27/2017
Misc
Corrective Action Required
12/27/2017
IBC 109.1, 109.5; IRC R109.3 INSPECTION ACCESS: PROPERTY LOCKED; INTERIOR NOT ACCESSIBLE. CALL FOR INSPECTION ON DAY WHEN JOBSITE IS ACCESSIBLE.
Above Ceiling Inspection Failed 1/16/2018 1/16/2018 at 12:20 PM 01/16/2018
Misc
Corrective Action Required
12/27/2017
PVC PLUMBING PIPE NOT ALLOWED IN CEILING PLENUM SPACE
Misc
Corrective Action Required
01/16/2018
MAKE UP AN CLOSE ALL OPEN ELECTRICAL BOXES
Misc
Corrective Action Required
01/16/2018
ENSURE CEILING SUPPORT WIRES SUPPORT ONLY CEILING GRID. INSTALL SLACK WIRES TO SUPPORT MC ELECTRICAL CABLE WHERE NEEDED.
Misc
Corrective Action Required
01/16/2018
REMOVE ALL TEMPORARY WIRING.
Misc
Corrective Action Required
01/16/2018
VENTILATION AIR PROVISIONS NOT FOUND AT RESTROOMS
Misc
Corrective Action Required
01/16/2018
KITCHEN NOT READY FOR INSPECTION. WORK IN PROGRESS.
Misc
Corrective Action Required
01/16/2018
WEST CORRIDOR NOT READY FOR INSPECTION. REMOVE ALL ABANDONED MATERIAL; MAKE REMAINING ELEMENTS COMPLIANT.
Above Ceiling Inspection Not Ready 1/19/2018 1/19/2018 at 7:55 AM 01/19/2018
Misc
Corrective Action Required
01/16/2018
PVC PLUMBING PIPE NOT ALLOWED IN CEILING PLENUM SPACE
Misc
Corrective Action Required
01/16/2018
MAKE UP AN CLOSE ALL OPEN ELECTRICAL BOXES
Misc
Corrective Action Required
01/16/2018
ENSURE CEILING SUPPORT WIRES SUPPORT ONLY CEILING GRID. INSTALL SLACK WIRES TO SUPPORT MC ELECTRICAL CABLE WHERE NEEDED.
Misc
Corrective Action Required
01/16/2018
REMOVE ALL TEMPORARY WIRING.
Misc
Corrective Action Required
01/16/2018
VENTILATION AIR PROVISIONS NOT FOUND AT RESTROOMS
Misc
Corrective Action Required
01/16/2018
KITCHEN NOT READY FOR INSPECTION. WORK IN PROGRESS.
Misc
Corrective Action Required
01/16/2018
WEST CORRIDOR NOT READY FOR INSPECTION. REMOVE ALL ABANDONED MATERIAL; MAKE REMAINING ELEMENTS COMPLIANT.
Above Ceiling Inspection Partial 1/22/2018 at 10:00 AM 01/22/2018
Misc
Resolved
01/22/2018
PVC PLUMBING PIPE NOT ALLOWED IN CEILING PLENUM SPACE
Misc
Resolved
01/22/2018
MAKE UP AN CLOSE ALL OPEN ELECTRICAL BOXES
Misc
Resolved
01/22/2018
ENSURE CEILING SUPPORT WIRES SUPPORT ONLY CEILING GRID. INSTALL SLACK WIRES TO SUPPORT MC ELECTRICAL CABLE WHERE NEEDED.
Misc
Resolved
01/22/2018
REMOVE ALL TEMPORARY WIRING.
Misc
Resolved
01/22/2018
VENTILATION AIR PROVISIONS NOT FOUND AT RESTROOMS
Misc
Resolved
01/22/2018
KITCHEN NOT READY FOR INSPECTION. WORK IN PROGRESS.
Misc
Corrective Action Required
01/19/2018
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS EXCEPT AT WEST CORRIDOR WEST CORRIDOR NOT READY FOR INSPECTION. REMOVE ALL ABANDONED MATERIAL; MAKE REMAINING ELEMENTS COMPLIANT.
Above Ceiling Inspection Failed 1/26/2018 1/26/2018 at 8:20 AM 01/26/2018
Misc
Corrective Action Required
01/22/2018
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS EXCEPT AT WEST CORRIDOR WEST CORRIDOR NOT READY FOR INSPECTION. REMOVE ALL ABANDONED MATERIAL; COMPLETE PERMAMENT WORK; MAKE REMAINING ELEMENTS COMPLIANT.
Miscellaneous Inspection Partial 1/30/2018 at 11:20 AM 01/30/2018
Miscellaneous Inspection Partial 2/1/2018 at 9:05 AM 02/01/2018
Miscellaneous Inspection Partial 2/5/2018 at 3:25 PM 02/05/2018
Gas Piping Inspection - Commercial Not Ready 2/6/2018 2/7/2018 at 9:20 AM 02/07/2018
Misc
Partial Correction
11/01/2017
PRESSURE TEST ON PIPING AT WATER HEATERS AND TO ROOFTOP HELD STEADY AT >10 PSI FOR >20 MIN.
Miscellaneous Inspection Partial 2/7/2018 at 9:35 AM 02/07/2018
Alternate Protection Systems Inspection Passed 2/13/2018 02/13/2018
Alarm Test Passed 2/13/2018 02/13/2018
Gas Piping Inspection - Commercial Partial 2/14/2018 2/15/2018 at 1:10 PM 02/15/2018
Misc
Partial Correction
02/07/2018
PRESSURE TEST ON COMPLETE SYSTEM HELD STEADY AT >10 PSI FOR >10 MIN.
Misc
Corrective Action Required
02/15/2018
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE NEW GAS PIPING AT ROOFTOP.
Miscellaneous Inspection Partial 2/21/2018 at 4:00 PM 02/21/2018
Miscellaneous Inspection Partial 2/22/2018 at 9:00 AM 02/22/2018
Misc
Corrective Action Required
02/21/2018
- WHEN OK FOR CONTENTS? - ADDRESS AT REAR DOOR - ADDRESS AT GAS SERVICE - B/F AT WATER-PIPED APPLIANCES - VAC BRK AT HOSE BIBB(S) - ELECT RECEPT BACK-SET - SOFT/LOOSE ELECT RECEPTS -
Miscellaneous Inspection Partial 2/23/2018 at 4:30 PM 02/23/2018
Misc
Corrective Action Required
02/22/2018
- WHEN OK FOR CONTENTS? - ADDRESS AT REAR DOOR - ADDRESS AT GAS SERVICE - B/F AT WATER-PIPED APPLIANCES - VAC BRK AT HOSE BIBB(S) - ELECT RECEPT BACK-SET - SOFT/LOOSE ELECT RECEPTS -
Miscellaneous Inspection Partial 2/26/2018 02/27/2018
Misc
Resolved
02/26/2018
- WHEN OK FOR CONTENTS? - ADDRESS AT REAR DOOR - ADDRESS AT GAS SERVICE - B/F AT WATER-PIPED APPLIANCES - VAC BRK AT HOSE BIBB(S) - ELECT RECEPT BACK-SET - SOFT/LOOSE ELECT RECEPTS -
Miscellaneous Inspection Passed 2/27/2018 at 11:05 AM 02/27/2018
Occupancy Inspection - Codes Commercial Temporary C of O 2/27/2018 2/27/2018 at 1:55 PM 02/27/2018
Misc
Corrective Action Required
02/26/2018
BACKFLOW PREVENTION DEVICE REQUIRED AT WATER-PIPED DISH WASHER
Misc
Corrective Action Required
02/27/2018
VACUUM BREAKER REQUIRED AT HOSE BIB AT KITCHEN
Misc
Corrective Action Required
02/27/2018
NEC 110-22; 384-13; IRC E36O6.2 PANEL SCHEDULES / LABELING OF ELECTRICAL CIRCUIT BREAKERS: EACH BREAKER MUST BE LABELED WITH REFERENCE TO SPECIFIC SPACE(S) OR EQUIPMENT SERVED. MUST BE LEGIBLE; SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS FOR INDIVIDUAL BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Corrective Action Required
02/27/2018
PAINT NEW ROOFTOP GAS PIPING 100%
Misc
Corrective Action Required
02/27/2018
RESOLVE ANY FIRE DEPARTMENT ISSUES
Above Ceiling Inspection Passed 1/26/2018 02/27/2018
Misc
Resolved
02/27/2018
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS EXCEPT AT WEST CORRIDOR WEST CORRIDOR NOT READY FOR INSPECTION. REMOVE ALL ABANDONED MATERIAL; COMPLETE PERMAMENT WORK; MAKE REMAINING ELEMENTS COMPLIANT.
Gas Piping Inspection - Commercial Passed 2/27/2018 02/27/2018
Misc
Resolved
02/27/2018
PRESSURE TEST ON COMPLETE SYSTEM HELD STEADY AT >10 PSI FOR >10 MIN.
Misc
Resolved
02/27/2018
IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE NEW GAS PIPING AT ROOFTOP.
Occupancy Inspection - Fire Passed 3/9/2018 03/09/2018
Occupancy Inspection - Codes Commercial Full C of O 3/9/2018 3/9/2018 03/10/2018
Misc
Resolved
03/09/2018
BACKFLOW PREVENTION DEVICE REQUIRED AT WATER-PIPED DISH WASHER
Misc
Resolved
03/09/2018
VACUUM BREAKER REQUIRED AT HOSE BIB AT KITCHEN
Misc
Resolved
03/09/2018
NEC 110-22; 384-13; IRC E36O6.2 PANEL SCHEDULES / LABELING OF ELECTRICAL CIRCUIT BREAKERS: EACH BREAKER MUST BE LABELED WITH REFERENCE TO SPECIFIC SPACE(S) OR EQUIPMENT SERVED. MUST BE LEGIBLE; SPECIFIC. NO DITTO MARKS OR CONTINUATION SYMBOLS FOR INDIVIDUAL BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Resolved
03/09/2018
PAINT NEW ROOFTOP GAS PIPING 100%
Misc
Resolved
03/09/2018
RESOLVE ANY FIRE DEPARTMENT ISSUES
Documents & Images
Date Uploaded File Type Document Name
06/26/2017 Letter Codes Plan Review Conditions
06/26/2017 Letter Codes Building Permit
06/26/2017 Receipt Receipt for transaction: 2017-004243
07/24/2017 Letter Inspection Summary
10/16/2017 Letter Inspection Summary
10/19/2017 Letter Inspection Summary
11/01/2017 Letter Inspection Summary
11/02/2017 Letter Inspection Summary
11/03/2017 Letter Inspection Summary
12/27/2017 Letter Inspection Summary
01/16/2018 Letter Inspection Summary
01/22/2018 Letter Inspection Summary
01/26/2018 Letter Inspection Summary
02/15/2018 Letter Inspection Summary
02/27/2018 Letter Codes Temporary Certificate of Occupancy
02/27/2018 Letter NEBB Report
03/09/2018 Letter Field Certificate of Occupancy
03/14/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home