Permit Application Status

PRCOM20161179


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20161179
Building Permit - Commercial
Certificate of Occupancy
JOHN KNOX VILLAGE
NEW MULTI-FAMILY
BUILDING B - 3 STORY INDEPENDENT LIVING UNIT BUILDING
05/23/2016
11/09/2016
11/30/2016
09/11/2017
Locations
Contacts
PARIC CORPORATION , Address:77 WESTORT PLAZA STE 250, Phone:(636) 561-9795  
GREEN FIELD ENERGY GROUP INC, Address:5 SW 4TH ST, Phone:(816) 524-5616  
TORGESON ELECTRIC CO INC, Address:3545 SW 6TH AVE, Phone:(785) 233-2213 Ext:101  
LMG CONSTRUCTION, Address:3011 ROANOKE RD, Phone:(816) 474-0333  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
SFCS ARCHITECTS, Address:1927 SOUTH TRYON ST, SUITE 207, Phone:(704) 372-7327  
KRUGER TECHNOLOGIES INC, Address:8271 MELROSE DR, Phone:(913) 498-1114  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 12/19/2016
Joe Dir
Misc
Corrective Action Required
12/19/2016

Provide updated plans showing standpipe connections in stairway #5 on all floors.
Installation acceptance testing
Corrective Action Required
12/19/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING OF THE FIRE SPRINKLER SYSTEM WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DPEARTMENT AT 816-969-1300.
Licensed Contractors Approved 06/23/2016 11/21/2016
Mike Weisenborn
LC - MEP Subs
Corrective Action Required
06/23/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Special Inspections Review Approved 10/14/2016
Joe Frogge
Fire Plan Review Approved with Conditions 06/27/2016 06/23/2016
Joe Dir
06/23/2016

06/23/2016

Misc
Corrective Action Required
06/23/2016

DO NOT INSTALL STROBES (ALARM NOTIFICATION) IN THE STAIRWAYS
Construction documents for fire alarm systems
Corrective Action Required
06/23/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS OF THE FIRE ALARM SYSTEM TO BE INSTALLED
Address numbers required
Corrective Action Required
06/23/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF EACH BUILDING READABLE FROM THE ADDRESSES ROADWAY, MAT REQUIRE POSTING THE ADDRESS ON MORE THAN ONE SIDE OF THE BUILDING (VERIFIED AT INSPECTION)
Knox box required
Corrective Action Required
06/23/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. PROVIDE A KNOX BOX FOR EACH BUILDING AND EACH ELEVATOR BANK BOXES CAN BE OBTAINED ONLINE knoxbox.com 506.1.2 Key boxes for nonstandardized fire service elevator keys. Key boxes provided for nonstandardized fire service elevator keys shall comply with Section 506.1 and all of the following: 1. The key box shall be compatible with an existing rapid entry key box system in use in the jurisdiction and approved by the fire code official. 2. The front cover shall be permanently labeled with the words “Fire Department Use Only—Elevator Keys.” 3. The key box shall be mounted at each elevator bank at the lobby nearest to the lowest level of fire department access. 4. The key box shall be mounted 5 feet 6 inches (1676 mm) above the finished floor to the right side of the elevator bank. 5. Contents of the key box are limited to fire service elevator keys. Additional elevator access tools, keys and information pertinent to emergency planning or elevator access shall be permitted when authorized by the fire code official. 6. In buildings with two or more elevator banks, a single key box shall be permitted to be used when such elevator banks are separated by not more than 30 feet (9144 mm). Additional key boxes shall be provided for each individual elevator or elevator bank separated by more than 30 feet (9144 mm).
Construction documents - Fire protection systems
Corrective Action Required
06/23/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS OF FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
06/23/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING OF THE SPRINKLER, ALARM AND HOOD SUPRESSION SYSTEMS WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Portable fire extinguishers - general
Corrective Action Required
06/23/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. THE MINIMUM SIZE FIRE EXTINGUISHER SHALL BE (5POUND) 2A-10BC
Portable fire extinguishers - conspicuous locations
Corrective Action Required
06/23/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. THE MAXIMUM TRAVEL DISTANCE TO A FIRE EXTINGUISHER SHALL BE 75'
Misc
Corrective Action Required
06/23/2016

LABEL ALL DOORS TO SPRINKLER ROOMS, MECHANICAL ROOMS, ELEVATOR ROOMS WITH THE ROOM DESIGANTION (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
06/23/2016

ALL EXTERIOR HORN STROBES SHALL BE LOCATED AT OR OVER THE FDCS. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
06/23/2016

STAIRWAY LANDINGS SHALL BE LABELED WITH THE FLOOR LEVEL DESIGNATION. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
06/23/2016

DOORS/HARWARE B] 1008.1 Doors.Means of egress doors shall meet the requirements of this section. Doors serving a means of egress system shall meet the requirements of this section and Section 1020.2. Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section. B] 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT
Building Plan Review Rejected 06/30/2016 06/23/2016
Joe Frogge
License Tax Application
Corrective Action Required
06/23/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Final Development Plan
Corrective Action Required
06/23/2016

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Misc
Resolved
10/14/2016

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections. 6/23/16 - not included in submittal
Elevator Certificate of Inspection
Corrective Action Required
06/23/2016

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated prusuant to sections 701.350 to 701.380. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Elevator Equipment Permit
Corrective Action Required
06/23/2016

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Elevator Equipment Inspection
Corrective Action Required
06/23/2016

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Misc
Resolved
06/23/2016

Footings, pads, etc. to be designed per site conditions. Action required: Provide soils report by licensed engineer to verify existing soils conditions. Plans cite 2500 psf while 2000 psf is common in this area.
Misc
Resolved
06/23/2016

Additional information required. Action required: Provide complete details and information for -- U.L. 438 (wall P2) GA #351 (wall HH2) U.L. U905 (walls W, W1, & W2) U.L. unknown (Wall JJ)
Misc
Resolved
06/23/2016

ICC A117.1-2009 Section 1004.11.1 Grab Bar and Shower Seat Reinforcement. Reinforcement shall be provided for the future installation of grab bars and shower seats at water closets, bathtubs, and shower compartments. Where walls are located to permit the installation of grab bars and seats complying with Section 604.5 at water closets; grab bars complying with Section 607.4 at bathtubs; and for grab bars and shower seats complying with Sections, 608.3, 608.2.1.3, 608.2.2.3 and 608.2.3.2 at shower compartments; reinforcement shall be provided for the future installation of grab bars and seats complying with those requirements. (see code for exceptions) Action required: Provide blocking for future accessible features as noted in all Type B units.
Misc
Resolved
06/23/2016

ICC A117.1-2009 1003.11.2.4.2 Clearance Width. Clearance around the water closet shall be 60 inches minimum in width, measured perpendicular from the side wall. Action required: Maintain minimum water closet clearance width at Type A units.
Misc
Resolved
06/23/2016

ICC A117.1-2009 Section 1004.11.3.1.2.2.1 Clearance Width. Clearance around the water closet shall be 48 inches minimum in width, measured perpendicular from the side of the clearance that is 16 inches minimum and 18 inches maximum from the water closet centerline. Action required: Maintain minimum water closet clearance width at unit Type C.
Misc
Resolved
06/23/2016

ICC A117.1-2009 Section 1004.11.3.1.3.3 Shower Compartment. If a shower compartment is the only bathing facility, the shower compartment shall have dimensions of 36 inches minimum in width and 36 inches minimum in depth. A clearance of 48 inches minimum in length, measured perpendicular from the shower head wall, and 30 inches minimum in depth, measured from the face of the shower compartment, shall be provided. Reinforcing for a shower seat is not required in shower compartments larger than 36 inches in width and 36 inches in depth. Action required: Provide minimum shower compartment floor dimensions. Not compliant as scaled.
Misc
Resolved
06/23/2016

2012 IBC 716.5 Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Section 716.5.1, 716.5.2 or 716.5.3 and the fire protection rating indicated in Table 716.5. Fire door frames with transom lights, sidelights or both shall be permitted in accordance with Section 716.5.6. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and the NFPA 80. Action required: Review and update door schedule as concerns minimum fire ratings. Multiple found to be incorrect or missing.
Miscellaneous Correction
Corrective Action Required
06/23/2016

2012 IBC 3002.3 Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways and not to use the elevators in case of fire. The sign shall read: IN CASE OF FIRE, ELEVATORS ARE OUT OF SERVICE. USE EXIT STAIRS. (see code for exceptions) Action required: Comment is for informational purposes. May be field verified. 6/23/16 - acknowledged in letter (field verify)
Engineered truss package
Resolved
06/23/2016

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide floor and roof truss packages or request to defer to construction. 6/23/16 - deferred
Screening - Ground mounted equipment
Resolved
06/23/2016

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Miscellaneous Correction
Resolved
06/23/2016

2012 IPC 918.1 General. (as amended by LSCO 7-412) Section 918.1 is hereby amended to read as follows: Air admittance valve are only allowed when approved by the Administrative Authority. Vent systems utilizing air admittance valves shall comply with this section. Stack-type air admittance valves shall conform to ASSE 1050. Individual- and branch-type air admittance valves shall conform to ASSE 1051. Action required: Modify drawings to show compliance. 6/23/16 - it has been decided to allow based upon complexity/quantity of loop vents, quantity of penetrations in fire rated horizontal assembly, and presence of maintenance staff.
Misc 12
Resolved
06/23/2016

20012 IPC 708.3.4 Base of stack. A cleanout shall be provided at the base of each waste or soil stack. Action required: Modify drawings and/or diagrams to demonstrate compliance.
Misc 13
Resolved
06/23/2016

2012 IPC 1101.3 Prohibited drainage. (as amended by LSCO 7-414) Storm water shall not be drained into sewers intended for sewage only. Sanitary sewer systems shall be designed, built and maintained in such a manner to prevent all storm or ground water from draining, discharging or entering into the sanitary sewer system. Connection of sump pumps, foundation drains, yard drains, gutter downspouts and any other storm water drainage receptacle(s) or system(s) are specifically prohibited from being connected to the sanitary sewer system. Action required: Re-route elevator sump discharge to approved storm drainage location. Drainage into sanitary sewer is prohibited.
Misc 14
Resolved
06/23/2016

2011 NEC Article 110.26 (C)(3) Personnel Doors. Where equipment rated 1200 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 25 feet from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic bars, pressure plates or other devices that are normally latched but open under simple pressure. Action required: At rooms with large electrical equipment as defined above provide outswinging doors with panic hardware and emergency exit light.
Misc 15
Resolved
06/23/2016

ICC A117.1-2009 Section 1003.5 Doors and Doorways. The primary entrance door to the unit, and all other doorways intended for user passage, shall comply with Section 404. (see code for exceptions) ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum door maneuver clearance at Accessible Unit B108 Balcony Door. Also - clarify hardware for door U4 (currently noted as "all hardware") If there is a closer then the door into the accessible Bath at Accessible Unit B108 is inadequate.
Misc 16
Resolved
06/23/2016

ICC A117.1-2009 1003.11.2.4.2 Clearance Width. Clearance around the water closet shall be 60 inches minimum in width, measured perpendicular from the side wall. Action required: Modify Accessible Units A303 & D204 to show compliance of minimum width.
Fire Plan Review Rejected 06/07/2016 06/01/2016
Joe Dir
Misc
Corrective Action Required
06/01/2016

NO STROBES (ALARM NOTIFICATION) IN THE STAIRWAYS
Construction documents for fire alarm systems
Corrective Action Required
06/01/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS OF THE FIRE ALARM SYSTEM TO BE INSTALLED
Access roads required for building and facilities
Corrective Action Required
06/01/2016

2012 IFC 503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exception: The fire code official is authorized to increase the dimension of 150 feet (45,720 mm) where: 1.The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. 2. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided. 3. There are not more than two Group R-3 or Group U occupancies. PROVIDE DETAILS OF THE ACCESS ROADWAY AS PER PDP
Address numbers required
Corrective Action Required
06/01/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST THE NUMERIC ADDRESS OF EACH BUILDING READABLE FROM THE ADDRESSES ROADWAY, MAT REQUIRE POSTING THE ADDRESS ON MORE THAN ONE SIDE OF THE BUILDING
Knox box required
Corrective Action Required
06/01/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. PROVIDE A KNOX BOX FOR EACH BUILDING AND EACH ELEVATOR BANK BOXES CAN BE OBTAINED ONLINE knoxbox.com 506.1.2 Key boxes for nonstandardized fire service elevator keys. Key boxes provided for nonstandardized fire service elevator keys shall comply with Section 506.1 and all of the following: 1. The key box shall be compatible with an existing rapid entry key box system in use in the jurisdiction and approved by the fire code official. 2. The front cover shall be permanently labeled with the words “Fire Department Use Only—Elevator Keys.” 3. The key box shall be mounted at each elevator bank at the lobby nearest to the lowest level of fire department access. 4. The key box shall be mounted 5 feet 6 inches (1676 mm) above the finished floor to the right side of the elevator bank. 5. Contents of the key box are limited to fire service elevator keys. Additional elevator access tools, keys and information pertinent to emergency planning or elevator access shall be permitted when authorized by the fire code official. 6. In buildings with two or more elevator banks, a single key box shall be permitted to be used when such elevator banks are separated by not more than 30 feet (9144 mm). Additional key boxes shall be provided for each individual elevator or elevator bank separated by more than 30 feet (9144 mm).
Construction documents - Fire protection systems
Corrective Action Required
06/01/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS OF FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
06/01/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING OF THE SPRINKLER, ALARM AND HOOD SUPRESSION SYSTEMS WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Portable fire extinguishers - general
Corrective Action Required
06/01/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. THE MINIMUM SIZE FIRE EXTINGUISHER SHALL BE (5POUND) 2A-10BC
Portable fire extinguishers - conspicuous locations
Corrective Action Required
06/01/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. THE MAXIMUM TRAVEL DISTANCE TO A FIRE EXTINGUISHER SHALL BE 75'
Misc
Corrective Action Required
06/01/2016

LABEL ALL DOORS TO SPRINKLER ROOMS, MECHANICAL ROOMS, ELEVATOR ROOMS WITH THE ROOM DESIGANTION
Misc
Corrective Action Required
06/01/2016

ALL EXTERIOR HORN STROBES SHALL BE LOCATED AS CLOSE TO OR OVER THE FDCS.
Misc
Corrective Action Required
06/01/2016

NO MENTION OF CO MONITORING IN THE GARAGE AREA. CONFIRM IF CO MONITORING WILL BE PRESENT OR NOT.
Misc
Corrective Action Required
06/01/2016

STAIRWAY LANDINGS SHALL BE LABELED WITH THE FLOOR LEVEL DESIGNATION.
Misc
Corrective Action Required
06/01/2016

DOORS/HARWARE B] 1008.1 Doors.Means of egress doors shall meet the requirements of this section. Doors serving a means of egress system shall meet the requirements of this section and Section 1020.2. Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section. B] 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT
Building Plan Review Rejected 06/07/2016 05/27/2016
Joe Frogge
License Tax Application
Corrective Action Required
05/27/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Final Development Plan
Corrective Action Required
05/27/2016

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
05/27/2016

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Elevator Certificate of Inspection
Corrective Action Required
05/27/2016

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated prusuant to sections 701.350 to 701.380. Action required: Comment is for informational purposes.
Elevator Equipment Permit
Corrective Action Required
05/27/2016

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is for informational purposes.
Elevator Equipment Inspection
Corrective Action Required
05/27/2016

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
05/27/2016

Footings, pads, etc. to be designed per site conditions. Action required: Provide soils report by licensed engineer to verify existing soils conditions. Plans cite 2500 psf while 2000 psf is common in this area.
Misc
Corrective Action Required
05/27/2016

Additional information required. Action required: Provide complete details and information for -- U.L. 438 (wall P2) GA #351 (wall HH2) U.L. U905 (walls W, W1, & W2) U.L. unknown (Wall JJ)
Misc
Corrective Action Required
05/27/2016

ICC A117.1-2009 Section 1004.11.1 Grab Bar and Shower Seat Reinforcement. Reinforcement shall be provided for the future installation of grab bars and shower seats at water closets, bathtubs, and shower compartments. Where walls are located to permit the installation of grab bars and seats complying with Section 604.5 at water closets; grab bars complying with Section 607.4 at bathtubs; and for grab bars and shower seats complying with Sections, 608.3, 608.2.1.3, 608.2.2.3 and 608.2.3.2 at shower compartments; reinforcement shall be provided for the future installation of grab bars and seats complying with those requirements. (see code for exceptions) Action required: Provide blocking for future accessible features as noted in all Type B units.
Misc
Corrective Action Required
05/27/2016

ICC A117.1-2009 1003.11.2.4.2 Clearance Width. Clearance around the water closet shall be 60 inches minimum in width, measured perpendicular from the side wall. Action required: Maintain minimum water closet clearance width at Type A units.
Misc
Corrective Action Required
05/27/2016

ICC A117.1-2009 Section 1004.11.3.1.2.2.1 Clearance Width. Clearance around the water closet shall be 48 inches minimum in width, measured perpendicular from the side of the clearance that is 16 inches minimum and 18 inches maximum from the water closet centerline. Action required: Maintain minimum water closet clearance width at unit Type C.
Misc
Corrective Action Required
05/27/2016

ICC A117.1-2009 Section 1004.11.3.1.3.3 Shower Compartment. If a shower compartment is the only bathing facility, the shower compartment shall have dimensions of 36 inches minimum in width and 36 inches minimum in depth. A clearance of 48 inches minimum in length, measured perpendicular from the shower head wall, and 30 inches minimum in depth, measured from the face of the shower compartment, shall be provided. Reinforcing for a shower seat is not required in shower compartments larger than 36 inches in width and 36 inches in depth. Action required: Provide minimum shower compartment floor dimensions. Not compliant as scaled.
Misc
Corrective Action Required
05/27/2016

2012 IBC 716.5 Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Section 716.5.1, 716.5.2 or 716.5.3 and the fire protection rating indicated in Table 716.5. Fire door frames with transom lights, sidelights or both shall be permitted in accordance with Section 716.5.6. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and the NFPA 80. Action required: Review and update door schedule as concerns minimum fire ratings. Multiple found to be incorrect or missing.
Miscellaneous Correction
Corrective Action Required
05/27/2016

2012 IBC 3002.3 Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways and not to use the elevators in case of fire. The sign shall read: IN CASE OF FIRE, ELEVATORS ARE OUT OF SERVICE. USE EXIT STAIRS. (see code for exceptions) Action required: Comment is for informational purposes. May be field verified.
Engineered truss package
Corrective Action Required
05/27/2016

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide floor and roof truss packages or request to defer to construction.
Screening - Ground mounted equipment
Corrective Action Required
05/27/2016

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Miscellaneous Correction
Corrective Action Required
05/27/2016

2012 IPC 918.1 General. (as amended by LSCO 7-412) Section 918.1 is hereby amended to read as follows: Air admittance valve are only allowed when approved by the Administrative Authority. Vent systems utilizing air admittance valves shall comply with this section. Stack-type air admittance valves shall conform to ASSE 1050. Individual- and branch-type air admittance valves shall conform to ASSE 1051. Action required: Modify drawings to show compliance.
Misc 12
Corrective Action Required
05/27/2016

20012 IPC 708.3.4 Base of stack. A cleanout shall be provided at the base of each waste or soil stack. Action required: Modify drawings and/or diagrams to demonstrate compliance.
Misc 13
Corrective Action Required
05/27/2016

2012 IPC 1101.3 Prohibited drainage. (as amended by LSCO 7-414) Storm water shall not be drained into sewers intended for sewage only. Sanitary sewer systems shall be designed, built and maintained in such a manner to prevent all storm or ground water from draining, discharging or entering into the sanitary sewer system. Connection of sump pumps, foundation drains, yard drains, gutter downspouts and any other storm water drainage receptacle(s) or system(s) are specifically prohibited from being connected to the sanitary sewer system. Action required: Re-route elevator sump discharge to approved storm drainage location. Drainage into sanitary sewer is prohibited.
Misc 14
Corrective Action Required
05/27/2016

2011 NEC Article 110.26 (C)(3) Personnel Doors. Where equipment rated 1200 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 25 feet from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic bars, pressure plates or other devices that are normally latched but open under simple pressure. Action required: At rooms with large electrical equipment as defined above provide outswinging doors with panic hardware and emergency exit light.
Misc 15
Corrective Action Required
05/27/2016

ICC A117.1-2009 Section 1003.5 Doors and Doorways. The primary entrance door to the unit, and all other doorways intended for user passage, shall comply with Section 404. (see code for exceptions) ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum door maneuver clearance at Accessible Unit B108 Balcony Door. Also - clarify hardware for door U4 (currently noted as "all hardware") If there is a closer then the door into the accessible Bath at Accessible Unit B108 is inadequate.
Misc 16
Corrective Action Required
05/27/2016

ICC A117.1-2009 1003.11.2.4.2 Clearance Width. Clearance around the water closet shall be 60 inches minimum in width, measured perpendicular from the side wall. Action required: Modify Accessible Units A303 & D204 to show compliance of minimum width.
Licensed Contractors Rejected 05/23/2016 05/27/2016
Joe Frogge
LC - MEP Subs
Corrective Action Required
05/27/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Multi-Family $17,125.60 $17,125.60 Paid 11/09/2016
8331507-Sewer Connection Fee $3,000.00 $3,000.00 Paid 11/09/2016
8331401-Water Tap Fee $21,427.00 $21,427.00 Paid 11/09/2016
8350015-Water Meter Fee $2,816.73 $2,816.73 Paid 11/09/2016
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 11/09/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underground Electrical Inspection - Commercial Partial 12/20/2016 12/20/2016 12/20/2016
Misc
Partial Correction
12/20/2016
OK TO COVER WHEN READY ONE 2" PVC CONDUIT + FOUR 4" CONDUITS FROM NE CORNER OF BLDG TO TRANSFORMER LOCATION FOR SECONDARY POWER
Rough Framing Inspection - Commercial Partial 12/29/2016 12/30/2016 12/30/2016
Misc
Partial Correction
12/30/2016
NO DETAIL FOUND FOR EXTERIOR SHEAR WALLS OR NAILING PATTERN. THE FIRST FLOOR WAS NAILED FLUSH IN EXCESS OF 4" ON THE SEEMS AND 6" IN THE FIELD.
Rough Framing Inspection - Commercial Partial 1/3/2017 01/03/2017
Misc
Partial Correction
12/30/2016
NO DETAIL FOUND FOR EXTERIOR SHEAR WALLS OR NAILING PATTERN. THE FIRST FLOOR WAS NAILED FLUSH IN EXCESS OF 4" ON THE SEAMS AND 6" IN THE FIELD. SOUTH ELEVATION: WARNING RE HIGH PERCENTAGE OF OVER-DRIVEN NAILS. PATTERN GENERALLY GOOD; SOME INSIDE AND OUTSIDE CORNERS TO BE FURTHER NAILED
Rough Framing Inspection - Commercial Partial 1/6/2017 1/6/2017 01/06/2017
Misc
Partial Correction
01/03/2017
OK TO COVER WITH BUILDING WRAP: SOUTH ELEVATION; HIGH PERCENTAGE OF OVER-DRIVEN NAILS -- TO BE CORRECTED ON SUBSEQUENT WORK.
Rough Framing Inspection - Commercial Partial 1/10/2017 01/10/2017
Misc
Partial Correction
01/06/2017
OK TO COVER WITH BUILDING WRAP: SOUTH ELEVATION; WEST ELEVATION; CORRECTIONS IN PROGRESS AT NORTH ELEVATION HIGH PERCENTAGE OF OVER-DRIVEN NAILS -- TO BE CORRECTED ON SUBSEQUENT WORK.
Rough Framing Inspection - Commercial Not Ready 1/13/2017 1/13/2017 01/13/2017
Misc
Partial Correction
01/10/2017
OK TO COVER WITH BUILDING WRAP: SOUTH ELEVATION; WEST ELEVATION; CORRECTIONS IN PROGRESS AT NORTH ELEVATION HIGH PERCENTAGE OF OVER-DRIVEN NAILS -- TO BE CORRECTED ON SUBSEQUENT WORK.
Rough Framing Inspection - Commercial Not Ready 1/17/2017 1/17/2017 01/17/2017
Misc
Partial Correction
01/13/2017
OK TO COVER WITH BUILDING WRAP: SOUTH ELEVATION; WEST ELEVATION; CORRECTIONS IN PROGRESS AT NORTH ELEVATION HIGH PERCENTAGE OF OVER-DRIVEN NAILS -- TO BE CORRECTED ON SUBSEQUENT WORK.
Misc
Corrective Action Required
01/17/2017
GROUND CONDITIONS TOO WET/SLICK FOR LIFT TO TRAVERSE NORTH SIDE OF BUILDING
Rough Framing Inspection - Commercial Not Ready 1/19/2017 1/19/2017 01/19/2017
Misc
Partial Correction
01/17/2017
OK TO COVER WITH BUILDING WRAP: SOUTH ELEVATION; WEST ELEVATION; CORRECTIONS IN PROGRESS AT NORTH ELEVATION HIGH PERCENTAGE OF OVER-DRIVEN NAILS -- TO BE CORRECTED ON SUBSEQUENT WORK.
Misc
Corrective Action Required
01/17/2017
GROUND CONDITIONS TOO WET/SLICK FOR LIFT TO TRAVERSE NORTH SIDE OF BUILDING
Rough Framing Inspection - Commercial Not Ready 1/20/2017 1/20/2017 01/20/2017
Rough Framing Inspection - Commercial Failed 1/23/2017 1/23/2017 01/23/2017
Misc
Partial Correction
01/19/2017
OK TO COVER WITH BUILDING WRAP: SOUTH ELEVATION; WEST ELEVATION; CORRECTIONS IN PROGRESS AT NORTH ELEVATION HIGH PERCENTAGE OF OVER-DRIVEN NAILS -- TO BE CORRECTED ON SUBSEQUENT WORK.
Misc
Corrective Action Required
01/19/2017
CORRECTIONS POINTED OUT TO BE MADE ON WALL SHEATHING AT NORTH SIDE OF BUILDING
Rough Framing Inspection - Commercial Partial 1/25/2017 01/25/2017
Misc
Partial Correction
01/25/2017
OK TO COVER WITH BUILDING WRAP: ALL ELEVATIONS FULL HEIGHT HIGH PERCENTAGE OF OVER-DRIVEN NAILS -- TO BE CORRECTED ON SUBSEQUENT BUILDINGS.
Misc
Resolved
01/25/2017
CORRECTIONS POINTED OUT TO BE MADE ON WALL SHEATHING AT NORTH SIDE OF BUILDING
All Rough Inspection - Commercial Partial 1/10/2017 1/25/2017 01/25/2017
Misc
Partial Correction
01/25/2017
OK TO PRE-ROCK SHOWER WALLS/CHASES AT: [108]; [109]; [115]; [118];
All Rough Inspection - Commercial Partial 1/27/2017 01/27/2017
Misc
Partial Correction
01/25/2017
OK TO PRE-ROCK SHOWER WALLS/CHASES AT: [106]; [108]; [109]; [111]; [113]; [115]; [118];
Rated Assembly Inspection Partial 1/31/2017 1/31/2017 01/31/2017
Misc
Partial Correction
01/31/2017
OK TO TAPE, MUD AND FIRE-STOP WALLS/CHASES SHOWER WALLS AT: [106]; [108]; [109]; [111]; [113]; [114]; [115];
All Rough Inspection - Commercial Partial 1/31/2017 01/31/2017
Misc
Partial Correction
01/27/2017
OK TO INSTALL TYPE X DRYWALL AT PRE-ROCK SHOWER WALLS AT:B106; 108; 109; 111; 113; 114; 115; B206; 208; 209; 211; 213; 214; 215; ENSURE SPECIAL INSPECTOR HAS APPROVED HOLD-DOWN HARDWARE INSTALLATION BEFORE COVERING ABOVE WALLS
Above Ceiling Inspection Not Ready 1/31/2017 1/31/2017 01/31/2017
Above Ceiling Inspection Not Ready 2/1/2017 2/1/2017 02/01/2017
Misc
Partial Correction
02/01/2017
FRAMING AND SYSTEMS ABOVE BOTTOM CHORD OF JOISTS OK FOR INSTALLATION OF INSULATION AND RESILIENT CHANNEL AT:
All Rough Inspection - Commercial Partial 2/3/2017 02/03/2017
Misc
Partial Correction
01/31/2017
OK TO INSTALL TYPE X DRYWALL AT PRE-ROCK SHOWER WALLS AT:B106; 108; 109; 111; 113; 114; 115; B206; 208; 209; 211; 213; 214; 215; ENSURE SPECIAL INSPECTOR HAS APPROVED HOLD-DOWN HARDWARE INSTALLATION BEFORE COVERING ABOVE WALLS
Misc
Partial Correction
02/03/2017
OK TO COVER CEILING AND WALL CAVITIES AT 1ST FLOOR: B106 WALLS; CEILING EXCEPT AT BR B108 WALLS; CEILING EXCEPT AT BR B114 CEILING ONLY EXCLUDING BR
Gas Piping Inspection - Commercial Partial 2/6/2017 02/06/2017
Misc
Partial Correction
02/06/2017
GAS FEEDER LINE TRENCHED, LAID, AND BACKFILLED FROM PRINT MARK (G1) TO (G2); TRACER WIRE IN PLACE
All Rough Inspection - Commercial Partial 2/6/2017 2/6/2017 02/06/2017
Misc
Resolved
02/06/2017
OK TO INSTALL TYPE X DRYWALL AT PRE-ROCK SHOWER WALLS AT:B106; 108; 109; 111; 113; 114; 115; B206; 208; 209; 211; 213; 214; 215; ENSURE SPECIAL INSPECTOR HAS APPROVED HOLD-DOWN HARDWARE INSTALLATION BEFORE COVERING ABOVE WALLS
Misc
Partial Correction
02/06/2017
OK TO COVER CEILING AND WALL CAVITIES AT 1ST FLOOR: B106; B108; B113; B114; B115; EXCLUDING CEILINGS AT BATHROOMS & WALLS AT SHOWERS
Gas Piping Inspection - Commercial Partial 2/7/2017 02/07/2017
Misc
Partial Correction
02/06/2017
GAS FEEDER LINE TRENCHED, LAID, AND BACKFILLED FROM PRINT MARK (G1) TO (G2); COMPLETE EAST TO RISER LOCATION TRACER WIRE IN PLACE
All Rough Inspection - Commercial Partial 2/8/2017 2/8/2017 02/08/2017
Misc
Partial Correction
02/06/2017
OK TO INSTALL TYPE X DRYWALL AT PRE-ROCK SHOWER WALLS AT: B106; 108; 109; 111; 113; 114; 115; CORRECTIONS IN PROGRESS AT [B206; 208; 209; 211; 213; 214; 215; ] ENSURE SPECIAL INSPECTOR HAS APPROVED HOLD-DOWN HARDWARE INSTALLATION BEFORE COVERING ABOVE WALLS
Misc
Partial Correction
02/06/2017
OK TO COVER CEILING AND WALL CAVITIES AT 1ST FLOOR: B106; B108; B113; B114; B115; EXCLUDING CEILINGS AT BATHROOMS & WALLS AT SHOWERS
All Rough Inspection - Commercial Partial 2/9/2017 2/9/2017 02/09/2017
Misc
Partial Correction
02/09/2017
OK TO COVER WHEN READY WALL FRAMING AND CEILING FRAMING AND CONCEALED SYSTEMS AT 2ND FLOOR SPACES: WALLS ONLY AT B206; 208; 213; 214; 215;
Partial Correction
02/09/2017
OK TO COVER WHEN READY WALL FRAMING AND CEILING FRAMING AND CONCEALED SYSTEMS AT 3RD FLOOR SPACES: SHOWER WALL PRE-ROCK AT B306; 308; 309; 311; 313; 314; 315;
All Rough Inspection - Commercial Partial 2/14/2017 2/13/2017 02/13/2017
Misc
Partial Correction
02/13/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 1ST FLOOR SPACES: 106; 108; 109; 111; 113; 114; 115;
Misc
Partial Correction
02/13/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 2ND FLOOR SPACES: 206; 208; 209 BA & CLO CLGS ONLY; 211; 213; 214; 215;
Rated Assembly Inspection Partial 2/13/2017 2/13/2017 02/13/2017
Misc
Partial Correction
01/31/2017
OK TO TAPE, MUD AND FIRE-STOP SHOWER WALLS /CHASES AT: 1ST FLOOR UNITS; 2ND FLOOR UNITS; 3RD FLOOR UNITS: 306; 308; 309; 311; 314; 315
Misc
Partial Correction
02/13/2017
RATED STAIRWELL WALLS: 1ST FLR: OK TO COVER UNIT-FACE AT: 106; 2ND FLR: OK TO COVER UNIT-FACE AT: 206;
All Rough Inspection - Commercial Partial 2/14/2017 02/14/2017
Misc
Partial Correction
02/13/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 1ST FLOOR SPACES: 106; 108; 109; 111; 113; 114; 115;
Misc
Partial Correction
02/13/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 2ND FLOOR SPACES: 206; 208; 209 BA & CLO CLGS ONLY; 211; 213; 214; 215;
Misc
Partial Correction
02/13/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 3RD FLOOR SPACES: SHOWER WALLS /CHASES AT 306, 308, 309, 311, 314, 315;
Gas Piping Inspection - Commercial Partial 2/14/2017 02/14/2017
Misc
Partial Correction
02/07/2017
GAS FEEDER LINE TRENCHED, LAID, AND BACKFILLED FROM PRINT MARK (G1) TO (G2); COMPLETE EAST TO BLDG ENTRY AT NE CORNER. INFRASOURCE PRESSURE TEST WITNESSED AT 100 PSI STEADY FOR >10 MINUTES. FEEDER PIPING TO BUILDING OK FOR USE. TRACER WIRE IN PLACE
Rated Assembly Inspection Partial 2/16/2017 2/16/2017 02/16/2017
Misc
Partial Correction
02/13/2017
OK TO TAPE, MUD AND FIRE-STOP SHOWER WALLS /CHASES AT: 1ST FLOOR UNITS; 2ND FLOOR UNITS; 3RD FLOOR UNITS: 306; 308; 309; 311; 314; 315
Misc
Partial Correction
02/13/2017
RATED STAIRWELL WALLS: 1ST FLR: OK TO COVER UNIT-FACE AT: 106; 2ND FLR: OK TO COVER UNIT-FACE AT: 206;
Misc
Partial Correction
02/16/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT CEILINGS AND WALLS AT: 106; 108; 111 EAST WALL ABOVE CEILING; 113; 114; 115;
All Rough Inspection - Commercial Partial 2/16/2017 2/16/2017 02/16/2017
Misc
Partial Correction
02/14/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 1ST FLOOR SPACES: 106; 108; 109; 111; 113; 114; 115;
Misc
Partial Correction
02/14/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 2ND FLOOR SPACES: 206; 208; 209 BA & CLO CLGS ONLY; 211; 213; 214; 215;
Misc
Partial Correction
02/14/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 3RD FLOOR SPACES: SHOWER WALLS /CHASES; CORRIDOR; 306; 308; 313; 314;
Rated Assembly Inspection Partial 2/17/2017 2/17/2017 02/17/2017
Misc
Partial Correction
02/16/2017
OK TO TAPE, MUD AND FIRE-STOP SHOWER WALLS /CHASES AT: 1ST FLOOR UNITS; 2ND FLOOR UNITS; 3RD FLOOR UNITS: 306; 308; 309; 311; 314; 315
Misc
Partial Correction
02/16/2017
RATED STAIRWELL WALLS: 1ST FLR: OK TO COVER UNIT-FACE AT: 106; 2ND FLR: OK TO COVER UNIT-FACE AT: 206;
Misc
Partial Correction
02/16/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT CEILINGS AND WALLS AT: 106; 108; 113; 114; 115; 109; 111 INCLUDING EAST WALL ABOVE CEILING;
All Rough Inspection - Commercial Partial 2/21/2017 2/21/2017 02/21/2017
Misc
Partial Correction
02/16/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 2ND FLOOR SPACES: 206; 208; 209 BA & CLO CLGS ONLY; 211; 213; 214; 215; JOIST SPACE ABOVE CORRIDOR AND ELEVATOR VESTIBULE;
Misc
Partial Correction
02/16/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 3RD FLOOR SPACES: SHOWER WALLS /CHASES; CORRIDOR; 306; 308; 313; 314; ALL UNITS INCLUDING 309 & 311
Misc
Partial Correction
02/16/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 1ST FLOOR SPACES: 106; 108; 109; 111; 113; 114; 115;
All Rough Inspection - Commercial Partial 2/23/2017 2/23/2017 02/23/2017
Misc
Partial Correction
02/21/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 2ND FLOOR SPACES: 206; 208; 209 BA & CLO CLGS ONLY; 211; 213; 214; 215; JOIST SPACE ABOVE CORRIDOR AND ELEVATOR VESTIBULE;
Misc
Partial Correction
02/21/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 3RD FLOOR SPACES: SHOWER WALLS /CHASES; CORRIDOR; 306; 308; 313; 314; ALL UNITS INCLUDING 309 & 311
Misc
Partial Correction
02/21/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 1ST FLOOR SPACES: 106; 108; 109; 111; 113; 114; 115; MAIN CORRIDOR/VESTIBULE; 102; 103;
Rated Assembly Inspection Partial 2/23/2017 2/23/2017 02/23/2017
Misc
Partial Correction
02/17/2017
OK TO TAPE, MUD AND FIRE-STOP SHOWER WALLS /CHASES AT: 1ST FLOOR UNITS; 2ND FLOOR UNITS; 3RD FLOOR UNITS: 306; 308; 309; 311; 314; 315
Misc
Partial Correction
02/17/2017
RATED STAIRWELL WALLS: 1ST FLR: OK TO COVER UNIT-FACE AT: 106; 2ND FLR: OK TO COVER UNIT-FACE AT: 206;
Misc
Partial Correction
02/17/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 1ST FLOOR CEILINGS AND WALLS AT: 106; 108; 113; 114; 115; 109; 111 INCLUDING EAST WALL ABOVE CEILING;
Misc
Partial Correction
02/23/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 2ND FLOOR CEILINGS AND WALLS AT: 206; 208; 213; 214; 215;
All Rough Inspection - Commercial Partial 2/24/2017 02/24/2017
Misc
Partial Correction
02/23/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 1ST FLOOR SPACES: 106; 108; 109; 111; 113; 114; 115; MAIN CORRIDOR/VESTIBULE; 102; 103;
Misc
Partial Correction
02/23/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 2ND FLOOR SPACES: 206; 208; 209 BA & CLO CLGS ONLY; 211; 213; 214; 215; JOIST SPACE ABOVE CORRIDOR AND ELEVATOR VESTIBULE;
Misc
Partial Correction
02/23/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 3RD FLOOR SPACES: SHOWER WALLS /CHASES; CORRIDOR; 306; 308; 313; 314; ALL UNITS INCLUDING 309 & 311
All Rough Inspection - Commercial Partial 2/27/2017 02/27/2017
Misc
Partial Correction
02/24/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 1ST FLOOR SPACES: 106; 108; 109; 111; 113; 114; 115; MAIN CORRIDOR/VESTIBULE; 102; 103;
Misc
Partial Correction
02/24/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 2ND FLOOR SPACES: 206; 208; 209 BA & CLO CLGS ONLY; 211; 213; 214; 215; JOIST SPACE ABOVE CORRIDOR AND ELEVATOR VESTIBULE; 209; 211;
Misc
Partial Correction
02/24/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 3RD FLOOR SPACES: SHOWER WALLS /CHASES; CORRIDOR; 306; 308; 313; 314; ALL UNITS INCLUDING 309 & 311
Foundation Inspection - Commercial Passed 2/27/2017 (1:00) 2/27/2017 02/27/2017
Rated Assembly Inspection Partial 2/28/2017 2/28/2017 02/28/2017
Misc
Resolved
02/28/2017
OK TO TAPE, MUD AND FIRE-STOP SHOWER WALLS /CHASES AT: 1ST FLOOR UNITS; 2ND FLOOR UNITS; 3RD FLOOR UNITS: 306; 308; 309; 311; 314; 315
Misc
Partial Correction
02/23/2017
RATED STAIRWELL WALLS: 1ST FLR: OK TO COVER UNIT-FACE AT: 106; 2ND FLR: OK TO COVER UNIT-FACE AT: 206;
Misc
Partial Correction
02/23/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 1ST FLOOR CEILINGS AND WALLS AT 1ST FLOOR: 106; 108; 113; 114; 115; 109; 111 INCLUDING EAST WALL ABOVE CEILING;
Misc
Partial Correction
02/23/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 2ND FLOOR CEILINGS AND WALLS AT: CORRIDOR; 206; 208; 213; 214; 215;
Misc
Partial Correction
02/28/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 3RD FLOOR CEILINGS AND WALLS AT: CORRIDOR; 306; 308; 309; 311; 313; 314;
All Rough Inspection - Commercial Partial 2/28/2017 02/28/2017
Misc
Partial Correction
02/27/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 1ST FLOOR SPACES: 104; 106; 108; 109; 111; 113; 114; 115; MAIN CORRIDOR/VESTIBULE; 102; 103;
Misc
Partial Correction
02/27/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 2ND FLOOR SPACES: 206; 208; 209 BA & CLO CLGS ONLY; 211; 213; 214; 215; JOIST SPACE ABOVE CORRIDOR AND ELEVATOR VESTIBULE; 209; 211; [202; 203; 204 N, E, S WALLS;
Misc
Partial Correction
02/27/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 3RD FLOOR SPACES: SHOWER WALLS /CHASES; CORRIDOR; 306; 308; 313; 314; ALL UNITS INCLUDING 309 & 311
Electrical Service Inspection Partial 3/1/2017 3/1/2017 03/01/2017
Partial Correction
03/01/2017
RELEASE TEMPORARY ELECTRICAL SERVICE
All Rough Inspection - Commercial Partial 3/1/2017 3/1/2017 03/01/2017
Misc
Partial Correction
02/28/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 1ST FLOOR SPACES: 104; 106; 108; 109; 111; 113; 114; 115; MAIN CORRIDOR/VESTIBULE; 102; 103; 110; 116&117 EXCEPT CLEANOUT ACCESS AT PLUMBING STACK;
Misc
Partial Correction
02/28/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 2ND FLOOR SPACES: 206; 208; 209 BA & CLO CLGS ONLY; 211; 213; 214; 215; JOIST SPACE ABOVE CORRIDOR AND ELEVATOR VESTIBULE; 209; 211; 202; 203; 204 N, E, S WALLS; 210
Misc
Partial Correction
02/28/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 3RD FLOOR SPACES: SHOWER WALLS /CHASES; CORRIDOR; ALL UNITS INCLUDING 315
Rated Assembly Inspection Not Ready 3/1/2017 3/1/2017 03/01/2017
Misc
Partial Correction
02/28/2017
RATED STAIRWELL WALLS: 1ST FLR: OK TO COVER UNIT-FACE AT: 106; 2ND FLR: OK TO COVER UNIT-FACE AT: 206; WEST STAIRWELL, STAIRWELL FACE NOT APPROVED: INSTALL ASW CLIPS PER MANUFACTURER'S INSTRUCTIONS. NO LEVEL-TO-LEVEL FIREBLOCKING INSTALLED.
Misc
Partial Correction
02/28/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 1ST FLOOR CEILINGS AND WALLS AT 1ST FLOOR: 106; 108; 113; 114; 115; 109; 111 INCLUDING EAST WALL ABOVE CEILING;
Misc
Partial Correction
02/28/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 2ND FLOOR CEILINGS AND WALLS AT: CORRIDOR; 206; 208; 213; 214; 215;
Misc
Partial Correction
02/28/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 3RD FLOOR CEILINGS AND WALLS AT: CORRIDOR; 306; 308; 309; 311; 313; 314;
All Rough Inspection - Commercial Partial 3/3/2017 03/03/2017
Misc
Partial Correction
03/01/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 1ST FLOOR SPACES: 104; 106; 108; 109; 111; 113; 114; 115; MAIN CORRIDOR/VESTIBULE; 102; 103; 110; 116&117 EXCEPT CLEANOUT ACCESS AT PLUMBING STACK;
Misc
Partial Correction
03/01/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 2ND FLOOR SPACES: 206; 208; 209 BA & CLO CLGS ONLY; 211; 213; 214; 215; JOIST SPACE ABOVE CORRIDOR AND ELEVATOR VESTIBULE; 209; 211; 202; 203; 204 N, E, S WALLS; 210; 216; 217;
Misc
Partial Correction
03/01/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 3RD FLOOR SPACES: SHOWER WALLS /CHASES; CORRIDOR; ALL UNITS INCLUDING 315; 302; 303; 304; 316; 317;
Misc
Partial Correction
03/03/2017
OK TO COVER WHEN READY 1ST FLOOR GWB DROP CEILING AREAS AT: BATHROOMS AT 109; 111;
Misc
Partial Correction
03/03/2017
OK TO COVER WHEN READY 2ND FLOOR GWB DROP CEILING AREAS AT:
Misc
Partial Correction
03/03/2017
OK TO COVER WHEN READY 3RD FLOOR GWB DROP CEILING AREAS AT:
Rated Assembly Inspection Partial 3/2/2017 3/3/2017 03/03/2017
Misc
Partial Correction
03/01/2017
RATED STAIRWELL WALLS -- OK TO COVER: 1ST FLR: UNIT-FACE AT: 106; 2ND FLR: UNIT-FACE AT: 206; WEST AND EAST STAIRWELLS AT STAIRWELL FACE
Misc
Partial Correction
03/01/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 1ST FLOOR CEILINGS AND WALLS AT: 106; 108; 113; 114; 115; 109; 111 INCLUDING EAST WALL ABOVE CEILING; MAIN CORRIDOR;
Misc
Partial Correction
03/01/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 2ND FLOOR CEILINGS AND WALLS AT: CORRIDOR; 206; 208; 213; 214; 215; 209; 211;
Misc
Partial Correction
03/01/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 3RD FLOOR CEILINGS AND WALLS AT: CORRIDOR; 306; 308; 309; 311; 313; 314; 315;
Rated Assembly Inspection Partial 3/8/2017 3/8/2017 03/08/2017
Misc
Partial Correction
03/03/2017
RATED STAIRWELL WALLS -- OK TO COVER: 1ST FLR: UNIT-FACE AT: 106; 102-4 116-7 2ND FLR: UNIT-FACE AT: 206; WEST AND EAST STAIRWELLS AT STAIRWELL FACE
Misc
Partial Correction
03/03/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 1ST FLOOR CEILINGS AND WALLS AT: 106; 108; 113; 114; 115; 109; 111 INCLUDING EAST WALL ABOVE CEILING; MAIN CORRIDOR; 102-4 116-7
Misc
Partial Correction
03/03/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 2ND FLOOR CEILINGS AND WALLS AT: CORRIDOR; 206; 208; 213; 214; 215; 209; 211; 202-4 216-7
Misc
Partial Correction
03/03/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 3RD FLOOR CEILINGS AND WALLS AT: CORRIDOR; 306; 308; 309; 311; 313; 314; 315; 302-4 316-7
Rated Assembly Inspection Partial 3/14/2017 3/14/2017 03/14/2017
Misc
Partial Correction
03/08/2017
RATED WEST AND EAST STAIRWELLS: OK TO TAPE, MUD AND FIRE-STOP UNIT FACE AND STAIRWELL FACE FULL HEIGHT BOTH STAIRS
Misc
Partial Correction
03/08/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 1ST FLOOR CEILINGS AND WALLS AT: 106; 108; 113; 114; 115; 109; 111 INCLUDING EAST WALL ABOVE CEILING; MAIN CORRIDOR; 102-4 116-7
Misc
Partial Correction
03/08/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 2ND FLOOR CEILINGS AND WALLS AT: CORRIDOR; 206; 208; 213; 214; 215; 209; 211; 202-4 216-7
Misc
Partial Correction
03/08/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 3RD FLOOR CEILINGS AND WALLS AT: CORRIDOR; 306; 308; 309; 311; 313; 314; 315; 302-4 316-7
Gas Piping Inspection - Commercial Partial 3/14/2017 3/14/2017 03/14/2017
Misc
Partial Correction
02/14/2017
GAS FEEDER LINE TRENCHED, LAID, AND BACKFILLED FROM PRINT MARK (G1) TO (G2); COMPLETE EAST TO BLDG ENTRY AT NE CORNER. INFRASOURCE PRESSURE TEST WITNESSED AT 100 PSI STEADY FOR >10 MINUTES. FEEDER PIPING TO BUILDING OK FOR USE. TRACER WIRE IN PLACE
Misc
Partial Correction
03/14/2017
GAS PIPING FROM BUILDING ENTRY TO WATER HEATER LOCATION ON 2ND FLOOR: NO ISSUES ON VISUAL INSPECTION. PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN. OK FOR USE WHEN READY.
Above Ceiling Inspection Partial 3/29/2017 3/29/2017 03/29/2017
Misc
Partial Correction
02/01/2017
FRAMING AND SYSTEMS ABOVE BOTTOM CHORD OF JOISTS OK FOR INSTALLATION OF INSULATION AND RESILIENT CHANNEL AT:
Misc
Partial Correction
03/29/2017
OK TO COVER WHEN READY FRAMING AND SYSTEMS TO BE CONCEALED AT INTERMITTANT GWB DROPPED CEILING SEGMENTS IN MAIN CORRIDORS AT 3RD, 2ND AND 1ST FLOORS CEILING AREAS AT ELEVATOR LOBBIES NOT READY FOR INSPECTION
Rough Electrical Inspection - Commercial Partial 3/31/2017 03/31/2017
Misc
Partial Correction
03/31/2017
NO ISSUES FOUND ON INSTALLATION OR MAKE-UP OF ELECTRICAL PANELS AT: UNITS ON 1ST, 2ND & 3RD FLOORS; PANELS AT COMMON SPACES NOT READY FOR INSPECTION
Misc
Partial Correction
03/31/2017
NO ISSUES FOUND ON MAKE-UP OF SEVEN TAP BOXES AT 1ST FLOOR -- SIX IN CORRIDOR; ONE IN NE UNIT
In-wall Inspection Partial 5/1/2017 5/1/2017 05/01/2017
Misc
Partial Correction
05/01/2017
OK TO COVER WHEN READY WOOD WALL FRAMING AND IN-WALL SYSTEMS AT: B118; B119;
Above Ceiling Inspection Partial 5/2/2017 5/2/2017 05/02/2017
Misc
Resolved
05/02/2017
FRAMING AND SYSTEMS ABOVE BOTTOM CHORD OF JOISTS OK FOR INSTALLATION OF INSULATION AND RESILIENT CHANNEL AT:
Misc
Partial Correction
03/29/2017
OK TO COVER WHEN READY FRAMING AND SYSTEMS TO BE CONCEALED AT INTERMITTANT GWB DROPPED CEILING SEGMENTS IN MAIN CORRIDORS AT 3RD, 2ND AND 1ST FLOORS CEILING AREAS AT ELEVATOR LOBBIES NOT READY FOR INSPECTION
Misc
Partial Correction
05/02/2017
OK TO COVER WHEN READY CEILING FRAMING & ABOVE-CEILING SYSTEMS AT: B118; B119;
Electrical Service Inspection Failed 5/2/2017 5/2/2017 05/02/2017
Misc
Corrective Action Required
05/02/2017
NO APPROVED ELECTRICAL RISER DRAWING FOR THIS BUILDING
Rated Assembly Inspection Failed 5/3/2017 5/3/2017 05/03/2017
Misc
Resolved
05/03/2017
RATED WEST AND EAST STAIRWELLS: OK TO TAPE, MUD AND FIRE-STOP UNIT FACE AND STAIRWELL FACE FULL HEIGHT BOTH STAIRS
Misc
Resolved
05/03/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 1ST FLOOR CEILINGS AND WALLS AT: 106; 108; 113; 114; 115; 109; 111 INCLUDING EAST WALL ABOVE CEILING; MAIN CORRIDOR; 102-4 116-7
Misc
Resolved
05/03/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 2ND FLOOR CEILINGS AND WALLS AT: CORRIDOR; 206; 208; 213; 214; 215; 209; 211; 202-4 216-7
Misc
Resolved
05/03/2017
OK TO TAPE, MUD AND FIRE-STOP WHEN READY 5/8" TYPE X GWB AT 3RD FLOOR CEILINGS AND WALLS AT: CORRIDOR; 306; 308; 309; 311; 313; 314; 315; 302-4 316-7
Misc
Corrective Action Required
05/03/2017
RAIN WATER IS SATURATING 5/8" TYPE X GWB AT WALLS AND CEILINGS AT B118 & B119. NOT APPROVED TO TAPE & MUD. REMOVE AND REPLACE ANY SATURATED GWB.
Electrical Service Inspection Passed 5/3/2017 5/3/2017 05/03/2017
Misc
Resolved
05/03/2017
NO APPROVED ELECTRICAL RISER DRAWING FOR THIS BUILDING
Rated Assembly Inspection Partial 5/4/2017 05/04/2017
Misc
Partial Correction
05/04/2017
OK TO TAPE, MUD AND FIRE-STOP WALLS AT: B118; B119 NOT APPROVED TO TAPE & MUD. REMOVE AND REPLACE ANY SATURATED GWB
Rated Assembly Inspection Partial 5/5/2017 5/5/2017 05/05/2017
Misc
Partial Correction
05/04/2017
OK TO TAPE, MUD AND FIRE-STOP WALLS AT B118 & B119
Rough Framing Inspection - Commercial Partial 5/5/2017 05/05/2017
Misc
Partial Correction
01/25/2017
OK TO COVER EXTERIOR WALL SHEATHING AT LINK.AT EAST END CONNECTING TO ADJACENT STRUCTURES
Above Ceiling Inspection Passed 5/2/2017 05/19/2017
Misc
Resolved
05/19/2017
OK TO COVER WHEN READY FRAMING AND SYSTEMS TO BE CONCEALED AT INTERMITTANT GWB DROPPED CEILING SEGMENTS IN MAIN CORRIDORS AT 3RD, 2ND AND 1ST FLOORS CEILING AREAS AT ELEVATOR LOBBIES NOT READY FOR INSPECTION
Misc
Resolved
05/19/2017
OK TO COVER WHEN READY CEILING FRAMING & ABOVE-CEILING SYSTEMS AT: B118; B119;
All Rough Inspection - Commercial Passed 3/3/2017 05/19/2017
Misc
Resolved
05/19/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 1ST FLOOR SPACES: 104; 106; 108; 109; 111; 113; 114; 115; MAIN CORRIDOR/VESTIBULE; 102; 103; 110; 116&117 EXCEPT CLEANOUT ACCESS AT PLUMBING STACK;
Misc
Resolved
05/19/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 2ND FLOOR SPACES: 206; 208; 209 BA & CLO CLGS ONLY; 211; 213; 214; 215; JOIST SPACE ABOVE CORRIDOR AND ELEVATOR VESTIBULE; 209; 211; 202; 203; 204 N, E, S WALLS; 210; 216; 217;
Misc
Resolved
05/19/2017
OK TO COVER WHEN READY WALL FRAMING, CEILING FRAMING AND CONCEALED SYSTEMS AT 3RD FLOOR SPACES: SHOWER WALLS /CHASES; CORRIDOR; ALL UNITS INCLUDING 315; 302; 303; 304; 316; 317;
Misc
Resolved
05/19/2017
OK TO COVER WHEN READY 1ST FLOOR GWB DROP CEILING AREAS AT: BATHROOMS AT 109; 111;
Misc
Resolved
05/19/2017
OK TO COVER WHEN READY 2ND FLOOR GWB DROP CEILING AREAS AT:
Misc
Resolved
05/19/2017
OK TO COVER WHEN READY 3RD FLOOR GWB DROP CEILING AREAS AT:
Gas Piping Inspection - Commercial Passed 3/14/2017 05/19/2017
Misc
Resolved
05/19/2017
GAS FEEDER LINE TRENCHED, LAID, AND BACKFILLED FROM PRINT MARK (G1) TO (G2); COMPLETE EAST TO BLDG ENTRY AT NE CORNER. INFRASOURCE PRESSURE TEST WITNESSED AT 100 PSI STEADY FOR >10 MINUTES. FEEDER PIPING TO BUILDING OK FOR USE. TRACER WIRE IN PLACE
Misc
Resolved
05/19/2017
GAS PIPING FROM BUILDING ENTRY TO WATER HEATER LOCATION ON 2ND FLOOR: NO ISSUES ON VISUAL INSPECTION. PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN. OK FOR USE WHEN READY.
In-wall Inspection Passed 5/1/2017 05/19/2017
Misc
Resolved
05/19/2017
OK TO COVER WHEN READY WOOD WALL FRAMING AND IN-WALL SYSTEMS AT: B118; B119;
Rated Assembly Inspection Passed 5/5/2017 05/19/2017
Misc
Resolved
05/19/2017
OK TO TAPE, MUD AND FIRE-STOP WALLS AT B118 & B119
Rough Electrical Inspection - Commercial Passed 3/31/2017 05/19/2017
Misc
Resolved
05/19/2017
NO ISSUES FOUND ON INSTALLATION OR MAKE-UP OF ELECTRICAL PANELS AT: UNITS ON 1ST, 2ND & 3RD FLOORS; PANELS AT COMMON SPACES NOT READY FOR INSPECTION
Misc
Resolved
05/19/2017
NO ISSUES FOUND ON MAKE-UP OF SEVEN TAP BOXES AT 1ST FLOOR -- SIX IN CORRIDOR; ONE IN NE UNIT
Rough Framing Inspection - Commercial Passed 5/5/2017 05/19/2017
Misc
Resolved
05/19/2017
OK TO COVER EXTERIOR WALL SHEATHING AT LINK.AT EAST END CONNECTING TO ADJACENT STRUCTURES
Underground Electrical Inspection - Commercial Passed 5/10/2017 12/20/2016 05/19/2017
Misc
Resolved
05/19/2017
OK TO COVER WHEN READY ONE 2" PVC CONDUIT + FOUR 4" CONDUITS FROM NE CORNER OF BLDG TO TRANSFORMER LOCATION FOR SECONDARY POWER
Above Ceiling Inspection Partial 5/23/2017 5/23/2017 05/23/2017
Misc
Partial Correction
05/23/2017
ELEVATOR SHAFT: ENSURE TIE-DOWN CLIPS AT ROOF TRUSS BEARING; THEN OK TO APPLY GWB LID PER APPROVED DRAWINGS
Rated Assembly Inspection Partial 5/24/2017 5/24/2017 05/24/2017
Misc
Partial Correction
05/23/2017
ELEVATOR SHAFT LID, OK TO COVER: FRAMING AND SHAFT LINER BOARD 1ST LAYER 5/8" TYPE X GWB;
Rated Assembly Inspection Partial 5/25/2017 5/25/2017 05/25/2017
Misc
Partial Correction
05/24/2017
ELEVATOR SHAFT LID, OK TO COVER: FRAMING AND SHAFT LINER BOARD 1ST LAYER 5/8" TYPE X GWB; 2ND LAYER 5/8" TYPE X OK TO TAPE, MUD & FIRE-STOP
Above Ceiling Inspection Not Ready 5/26/2017 5/26/2017 05/26/2017
Misc
Resolved
05/26/2017
ELEVATOR SHAFT: ENSURE TIE-DOWN CLIPS AT ROOF TRUSS BEARING; THEN OK TO APPLY GWB LID PER APPROVED DRAWINGS
Misc
Corrective Action Required
05/26/2017
INSTALL NO CEILING TILE BEFORE ABOVE-CEILING INSPECTION -- EXCEPT THOSE FEW REQUIRED FOR MOUNTING OF DEVICES.
Above Ceiling Inspection Partial 5/31/2017 05/31/2017
Misc
Partial Correction
05/31/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: ELEVATOR LOBBIES AT 1ST & 2ND FLOORS;
Above Ceiling Inspection Partial 6/2/2017 6/2/2017 06/02/2017
Misc
Partial Correction
05/31/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: CORRIDORS AT 1ST (EXCEPT AT SPRINKLE CONTROL), 2ND AND 3RD FLOORS; ELEVATOR LOBBIES AT 3RD & 2ND FLOORS;
Occupancy Inspection - Water Utilities Passed 6/14/2017 06/05/2017
Sprinkler - Hydrostatic Test Failed 6/9/2017 06/09/2017
Above Ceiling Inspection Passed 6/9/2017 6/9/2017 06/09/2017
Misc
Resolved
06/09/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: CORRIDORS AT 1ST (EXCEPT AT SPRINKLE CONTROL), 2ND AND 3RD FLOORS; ELEVATOR LOBBIES AT 3RD & 2ND FLOORS;
Rated Assembly Inspection Passed 5/25/2017 06/09/2017
Misc
Resolved
06/09/2017
ELEVATOR SHAFT LID, OK TO COVER: FRAMING AND SHAFT LINER BOARD 1ST LAYER 5/8" TYPE X GWB; 2ND LAYER 5/8" TYPE X OK TO TAPE, MUD & FIRE-STOP
Sprinkler - Hydrostatic Test Passed 6/12/2017 06/12/2017
Sprinkler - Flow Test Passed 6/13/2017 06/13/2017
Alarm Test Passed 6/13/2017 06/13/2017
Occupancy Inspection - Fire Not Ready 6/14/2017 06/14/2017
Occupancy Inspection - Planning Temporary C of O 6/14/2017 06/14/2017
Corrective Action Required
06/14/2017
LANDSCAPING. Landscaping shall be completed per the approved plan.
Corrective Action Required
06/14/2017
PARKING LOT LIGHTING. Parking lot light poles and fixtures shall be installed per the approved plan.
Corrective Action Required
06/14/2017
PARKING LOT. The previously existing parking lot at the far southwest corner of the site shall be re-striped when it is no longer used as a staging area.
Occupancy Inspection - Codes Commercial Failed 6/14/2017 6/14/2017 06/14/2017
Misc
Corrective Action Required
06/14/2017
BUILDING EXTERIOR: - HEIGHT OF THRESHOLDS AT PATIO DOORS - SEAL ALL OPENINGS IN EXTERIOR WALL - SEAL AROUND DISCONNECT ENCLOSURES, ETC - OPEN J.B. + MISSING FACE PLATE @ LINK - COMPLETE INSTALLATION OF DOWNSPOUTS - EXHAUST HOOD MISSING AT NORTH WALL 2ND LVL - INSTALL GAS PRESURE REGULATOR - PAINT EXTERIOR EXPOSED FERROUS GAS PIPING - OPEN 4" PVC PIPE RISER NORTH OF BUILDING - INSTALL PARKING LOT LIGHT POLE - COMPLETE FINISH SITEWORK
Misc
Corrective Action Required
06/14/2017
VERIFY AND LABEL CIRCUIT POSITION NUMBERS AT UNIT SUB-PANELS
Misc
Corrective Action Required
06/14/2017
PVC PIPE PENETRATIONS OF RATED CEILING ASSEMBLIES TO BE FIRE-STOPPED PER APPROVED DRAWINGS
Misc
Corrective Action Required
06/14/2017
RESOLVE ISSUES PRESENTED BY: FIRE DEPARTMENT WATER UTILITIES DEPARTMENT PLANNING DIVISION PUBLIC WORKS
Occupancy Inspection - Fire Temporary C of O 6/15/2017 06/15/2017
Occupancy Inspection - Codes Commercial Temporary C of O 6/15/2017 06/15/2017
Misc
Corrective Action Required
06/14/2017
VERIFY AND LABEL CIRCUIT POSITION NUMBERS AT UNIT SUB-PANELS
Misc
Corrective Action Required
06/14/2017
PVC PIPE PENETRATIONS OF RATED CEILING ASSEMBLIES TO BE FIRE-STOPPED PER APPROVED DRAWINGS
Misc
Corrective Action Required
06/14/2017
RESOLVE ISSUES PRESENTED BY: FIRE DEPARTMENT WATER UTILITIES DEPARTMENT PLANNING DIVISION PUBLIC WORKS
Misc
Corrective Action Required
06/14/2017
BUILDING EXTERIOR: - HEIGHT OF THRESHOLDS AT PATIO DOORS - SEAL ALL OPENINGS IN EXTERIOR WALL - SEAL AROUND DISCONNECT ENCLOSURES, ETC - OPEN J.B. + MISSING FACE PLATE @ LINK - COMPLETE INSTALLATION OF DOWNSPOUTS - EXHAUST HOOD MISSING AT NORTH WALL 2ND LVL - INSTALL GAS PRESURE REGULATOR - PAINT EXTERIOR EXPOSED FERROUS GAS PIPING - OPEN 4" PVC PIPE RISER NORTH OF BUILDING - INSTALL PARKING LOT LIGHT POLE - COMPLETE FINISH SITEWORK
Occupancy Inspection - Codes Commercial Partial 6/16/2017 06/16/2017
Misc
Resolved
06/16/2017
VERIFY AND LABEL CIRCUIT POSITION NUMBERS AT UNIT SUB-PANELS
Misc
Corrective Action Required
06/15/2017
PVC PIPE PENETRATIONS OF RATED CEILING ASSEMBLIES TO BE FIRE-STOPPED PER APPROVED DRAWINGS
Misc
Corrective Action Required
06/15/2017
RESOLVE ISSUES PRESENTED BY: FIRE DEPARTMENT WATER UTILITIES DEPARTMENT PLANNING DIVISION PUBLIC WORKS
Misc
Corrective Action Required
06/15/2017
BUILDING EXTERIOR: - HEIGHT OF THRESHOLDS AT PATIO DOORS - SEAL ALL OPENINGS IN EXTERIOR WALL - SEAL AROUND DISCONNECT ENCLOSURES, ETC - COMPLETE INSTALLATION OF DOWNSPOUTS - EXHAUST HOOD MISSING AT NORTH WALL 2ND LVL - INSTALL GAS PRESURE REGULATOR - PAINT EXTERIOR EXPOSED FERROUS GAS PIPING - OPEN 4" PVC PIPE RISER NORTH OF BUILDING - INSTALL PARKING LOT LIGHT POLES - COMPLETE FINISH SITEWORK
Occupancy Inspection - Codes Commercial Partial 6/30/2017 6/30/2017 06/30/2017
Misc
Corrective Action Required
06/16/2017
PVC PIPE PENETRATIONS OF RATED CEILING ASSEMBLIES TO BE PROTECTED AND FIRE-STOPPED PER APPROVED DRAWINGS.
Misc
Corrective Action Required
06/16/2017
BUILDING EXTERIOR: - INSTALL PARKING LOT LIGHT POLES - COMPLETE FINISH SITEWORK
Misc
Corrective Action Required
06/16/2017
RESOLVE ISSUES PRESENTED BY: - FIRE DEPARTMENT - PLANNING DIVISION - PUBLIC WORKS
Occupancy Inspection - Codes Commercial Not Ready 7/5/2017 07/05/2017
Misc
Corrective Action Required
06/30/2017
PVC PIPE PENETRATIONS OF RATED CEILING ASSEMBLIES TO BE PROTECTED AND FIRE-STOPPED PER APPROVED DRAWINGS.
Misc
Corrective Action Required
06/30/2017
BUILDING EXTERIOR: - INSTALL PARKING LOT LIGHT POLES - COMPLETE FINISH SITEWORK
Misc
Corrective Action Required
06/30/2017
RESOLVE ISSUES PRESENTED BY: - FIRE DEPARTMENT - PLANNING DIVISION - PUBLIC WORKS
Occupancy Inspection - Codes Commercial Not Ready 7/14/2017 7/14/2017 07/14/2017
Misc
Corrective Action Required
07/05/2017
PVC PIPE PENETRATIONS OF RATED CEILING ASSEMBLIES TO BE PROTECTED AND FIRE-STOPPED PER APPROVED DRAWINGS.
Misc
Corrective Action Required
07/05/2017
BUILDING EXTERIOR: - INSTALL PARKING LOT LIGHT POLES - COMPLETE FINISH SITEWORK
Misc
Corrective Action Required
07/05/2017
RESOLVE ISSUES PRESENTED BY: - FIRE DEPARTMENT - PLANNING DIVISION - PUBLIC WORKS
Occupancy Inspection - Codes Commercial Temporary C of O 7/18/2017 07/18/2017
Misc
Resolved
07/18/2017
PVC PIPE PENETRATIONS OF RATED CEILING ASSEMBLIES TO BE PROTECTED AND FIRE-STOPPED PER APPROVED DRAWINGS.
Misc
Corrective Action Required
07/14/2017
BUILDING EXTERIOR: - INSTALL PERMANENT PARKING LOT LIGHT POLES - COMPLETE FINISH SITEWORK
Misc
Corrective Action Required
07/14/2017
RESOLVE ISSUES PRESENTED BY: - FIRE DEPARTMENT - PLANNING DIVISION
Occupancy Inspection - Codes Commercial Partial 9/7/2017 at 2:50 PM 09/07/2017
Misc
Resolved
09/07/2017
BUILDING EXTERIOR: - INSTALL PERMANENT PARKING LOT LIGHT POLES - COMPLETE FINISH SITEWORK
Misc
Corrective Action Required
07/18/2017
RESOLVE ISSUES PRESENTED BY: - PLANNING DIVISION
Occupancy Inspection - Codes Commercial Full C of O 9/11/2017 at 9:40 AM 09/11/2017
Misc
Resolved
09/11/2017
RESOLVE ISSUES PRESENTED BY: - PLANNING DIVISION
Occupancy Inspection - Fire Passed 9/11/2017 09/18/2017
Documents & Images
Date Uploaded File Type Document Name
06/01/2016 Letter Fire Building Plan Review
06/03/2016 Letter Codes P/R Corrections Document
06/23/2016 Letter Fire Building Plan Review
11/09/2016 Receipt Receipt for transaction: 2016-006766
11/09/2016 Letter Codes Building Permit
11/09/2016 Letter Codes Plan Review Conditions
12/19/2016 Letter Fire (Sprinkler) Plan Review
12/20/2016 Letter Inspection Summary
12/30/2016 Letter Inspection Summary
01/03/2017 Letter Inspection Summary
01/06/2017 Letter Inspection Summary
01/10/2017 Letter Inspection Summary
01/17/2017 Letter Inspection Summary
01/23/2017 Letter Inspection Summary
01/25/2017 Letter Inspection Summary
01/27/2017 Letter Inspection Summary
01/31/2017 Letter Inspection Summary
02/03/2017 Letter Inspection Summary
02/06/2017 Letter Inspection Summary
02/07/2017 Letter Inspection Summary
02/08/2017 Letter Inspection Summary
02/09/2017 Letter Inspection Summary
02/13/2017 Letter Inspection Summary
02/14/2017 Letter Inspection Summary
02/16/2017 Letter Inspection Summary
02/17/2017 Letter Inspection Summary
02/21/2017 Letter Inspection Summary
02/23/2017 Letter Inspection Summary
02/27/2017 Letter Inspection Summary
02/27/2017 Letter Inspection Summary
02/28/2017 Letter Inspection Summary
03/01/2017 Letter Inspection Summary
03/03/2017 Letter Inspection Summary
03/08/2017 Letter Inspection Summary
03/14/2017 Letter Inspection Summary
03/14/2017 Letter Inspection Summary
03/29/2017 Letter Inspection Summary
03/31/2017 Letter Inspection Summary
05/01/2017 Letter Inspection Summary
05/02/2017 Letter Inspection Summary
05/03/2017 Letter Inspection Summary
05/04/2017 Letter Inspection Summary
05/05/2017 Letter Inspection Summary
05/23/2017 Letter Inspection Summary
05/23/2017 Letter Inspection Summary
05/24/2017 Letter Inspection Summary
05/25/2017 Letter Inspection Summary
05/26/2017 Letter Inspection Summary
05/31/2017 Letter Inspection Summary
06/02/2017 Letter Inspection Summary
06/14/2017 Letter Inspection Summary
06/15/2017 Letter Codes Temporary Certificate of Occupancy
06/16/2017 Letter Inspection Summary
06/16/2017 Letter Inspection Summary
06/30/2017 Letter Inspection Summary
07/05/2017 Letter Inspection Summary
07/18/2017 Letter Codes Temporary Certificate of Occupancy
09/11/2017 Letter Field Certificate of Occupancy
09/14/2017 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home