Review Type |
Outcome |
Est. Completion Date |
Completed |
Final Development Plan Review
|
Approved
|
|
03/24/2016
|
|
Mike Weisenborn
|
|
|
Licensed Contractors
|
Approved
|
02/29/2016
|
03/02/2016
|
|
Joe Frogge
|
|
|
Building Plan Review
|
Approved with Conditions
|
03/07/2016
|
03/02/2016
|
|
Joe Frogge
|
|
Final Development Plan
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required: Comment is for informational purposes.
1/20/16 - acknowledged in letter
|
|
Misc
412.4.4 Heating equipment. Heating equipment shall be placed in another room separated by 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. Entrance shall be from the outside or by means of a vestibule providing a two-doorway separation.
Exceptions:
1. Unit heaters and vented infrared radiant heating equipment suspended not less than 10 feet (3048 mm) above the upper surface of wings or engine enclosures of the highest aircraft that are permitted to be housed in the hangar need not be located in a separate room provided they are mounted not less than 8 feet (2438 mm) above the floor in shops, offices and other sections of the hangar communicating with storage or service areas.
2. Entrance to the separated room shall be permitted by a single interior door provided the sources of ignition in the appliances are not less than 18 inches (457 mm) above the floor.
Action required: Furnace to be in a room separated by 2 hour barrier. Provide construction details complete with UL. (It may be more economical to extend under floor heating?)
1/20/16 - updated drawings have omitted furnace in lieu of water heater.
-
-
- It is unclear how the exemptions listed on drawings apply to this situation.
-
-
2/17/16 - Entry door to boiler room moved to exteriror, but the separating structure (wall & ceiling) is still not designated as 2 hour barrier.
3/2/16 - resolved after Joe (me) altered a note on sheet A1 to clarify which walls are required to be fire rated
|
|
|
Fire Plan Review
|
Approved with Conditions
|
03/03/2016
|
03/02/2016
|
|
Joe Dir
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC OF ALPHBETIC BUILDING ADDRESS ON THE BUILDING READABLE FROM THE ROADWAY. VERIFIED AT INSPECTION.
(ADDRESSED IN LETTER AND PLANS)
|
|
Portable fire extinguishers - conspicuous locations
Corrective Action Required
2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
PROVIDE A MINIMUM OF THREE 2A-10BC ( 5 POUND)
FIRE EXTINGUISHERS. VERIFIED AT INSPECTION.
MOUNT THE THIRD FIRE EXTINGUISHER ON THE SOUTH WALL BETWEEN THE TWO MAN DOORS
(ADDRESSED IN LETTER AND PLANS)
|
|
|
Fire Plan Review
|
Approved with Conditions
|
02/23/2016
|
02/18/2016
|
|
Joe Dir
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC OF ALPHBETIC BUILDING ADDRESS ON THE BUILDING READABLE FROM THE ROADWAY. VERIFIED AT INSPECTION.
(ADDRESSED IN LETTER AND PLANS)
|
|
Portable fire extinguishers - conspicuous locations
Corrective Action Required
2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
PROVIDE A MINIMUM OF THREE 2A-10BC ( 5 POUND)
FIRE EXTINGUISHERS. VERIFIED AT INSPECTION.
MOUNT THE THIRD FIRE EXTINGUISHER ON THE SOUTH WALL BETWEEN THE TWO MAN DOORS
(ADDRESSED IN LETTER AND PLANS)
|
|
|
Licensed Contractors
|
Approved
|
02/16/2016
|
02/17/2016
|
|
Joe Frogge
|
|
|
Building Plan Review
|
Rejected
|
02/23/2016
|
02/17/2016
|
|
Joe Frogge
|
|
Final Development Plan
Corrective Action Required
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required: Comment is for informational purposes.
1/20/16 - acknowledged in letter
|
|
Misc
2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions)
Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
1/20/16 - letter received but lacks reference to being responsible for:
- testing of concrete
- bolts installed in concrete
- high strength bolting
|
|
Misc
412.4.1 Exterior walls. Exterior walls located less than 30 feet (9144 mm) from lot lines or a public way shall have a fire-resistance rating not less than 2 hours.
Action required: Provide UL listed 2 hour fire barrier at north exterior walls within 30 feet of property line.
2/18/16 - per earlier precedents, the 2hr barrier will not be required. Reasoning as I understand it is that we own the property so therefore have control over the construction
1/20/16 - updated drawings reference UL V473. Provide complete construction details including nail/screw patterns as our inspectors do not have UL information available in the field. Also, given that this assembly requires gyp on each side, provide details as to how this will be accomplished and inspected.
2/17/16 - Note has been added referring to an attached drawing that we do not have.
|
|
Misc
Corrective Action Required
412.4.4 Heating equipment. Heating equipment shall be placed in another room separated by 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. Entrance shall be from the outside or by means of a vestibule providing a two-doorway separation.
Exceptions:
1. Unit heaters and vented infrared radiant heating equipment suspended not less than 10 feet (3048 mm) above the upper surface of wings or engine enclosures of the highest aircraft that are permitted to be housed in the hangar need not be located in a separate room provided they are mounted not less than 8 feet (2438 mm) above the floor in shops, offices and other sections of the hangar communicating with storage or service areas.
2. Entrance to the separated room shall be permitted by a single interior door provided the sources of ignition in the appliances are not less than 18 inches (457 mm) above the floor.
Action required: Furnace to be in a room separated by 2 hour barrier. Provide construction details complete with UL. (It may be more economical to extend under floor heating?)
1/20/16 - updated drawings have omitted furnace in lieu of water heater.
-
-
- It is unclear how the exemptions listed on drawings apply to this situation.
-
-
2/17/16 - Entry door to boiler room moved to exteriror, but the separating structure (wall & ceiling) is still not designated as 2 hour barrier.
|
|
Misc
412.4.3 Floor surface. Floors shall be graded and drained to prevent water or fuel from remaining on the floor. Floor drains shall discharge through an oil separator to the sewer or to an outside vented sump. (see code for exceptions)
Action required: Provide oil separator at DWV piping system that serves trench drain.
1/20/16 - Specify oil separator size and provide installation details.
2/17/16 - separator omitted. floor slopes to o.h. door
|
|
Misc
Mechanical design incomplete.
Action required: Provide specifications for under floor heating system. Provide complete HVAC design at office area complete with, but not limited to, duct sizes, furnace specifications, furnace support, etc.
1/20/16 - reference comment #5 for heating equipment.
|
|
|
Special Inspections Review
|
Approved
|
|
02/16/2016
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Approved with Conditions
|
01/26/2016
|
01/21/2016
|
|
Joe Dir
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC OF ALPHBETIC BUILDING ADDRESS ON THE BUILDING READABLE FROM THE ROADWAY. VERIFIED AT INSPECTION.
(ADDRESSED IN LETTER AND PLANS)
|
|
Portable fire extinguishers - conspicuous locations
Corrective Action Required
2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
PROVIDE A MINIMUM OF TWO 2A-10BC ( 5 POUND)
FIRE EXTINGUISHERS. VERIFIED AT INSPECTION.
(ADDRESSED IN LETTER AND PLANS)
|
|
|
Building Plan Review
|
Rejected
|
01/26/2016
|
01/20/2016
|
|
Joe Frogge
|
|
Final Development Plan
Corrective Action Required
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required: Comment is for informational purposes.
1/20/16 - acknowledged in letter
|
|
Code analysis required
A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed.
Action required: Provide code analysis as noted.
1/20/16 - provided on revised sheet
|
|
Misc
Corrective Action Required
2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions)
Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
1/20/16 - letter received but lacks reference to being responsible for:
- testing of concrete
- bolts installed in concrete
- high strength bolting
|
|
Misc
Corrective Action Required
412.4.1 Exterior walls. Exterior walls located less than 30 feet (9144 mm) from lot lines or a public way shall have a fire-resistance rating not less than 2 hours.
Action required: Provide UL listed 2 hour fire barrier at north exterior walls within 30 feet of property line.
1/20/16 - updated drawings reference UL V473. Provide complete construction details including nail/screw patterns as our inspectors do not have UL information available in the field. Also, given that this assembly requires gyp on each side, provide details as to how this will be accomplished and inspected.
|
|
Misc
Corrective Action Required
412.4.4 Heating equipment. Heating equipment shall be placed in another room separated by 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. Entrance shall be from the outside or by means of a vestibule providing a two-doorway separation.
Exceptions:
1. Unit heaters and vented infrared radiant heating equipment suspended not less than 10 feet (3048 mm) above the upper surface of wings or engine enclosures of the highest aircraft that are permitted to be housed in the hangar need not be located in a separate room provided they are mounted not less than 8 feet (2438 mm) above the floor in shops, offices and other sections of the hangar communicating with storage or service areas.
2. Entrance to the separated room shall be permitted by a single interior door provided the sources of ignition in the appliances are not less than 18 inches (457 mm) above the floor.
Action required: Furnace to be in a room separated by 2 hour barrier. Provide construction details complete with UL. (It may be more economical to extend under floor heating?)
1/20/16 - updated drawings have omitted furnace in lieu of water heater.
- Information is still inadequate for approval. Provide complete design. (information provided was for the heating equipment only)
- If this heater is to be used for domestic water provide details as to how the domestic water system will be protected.
- It is unclear how the exemptions listed on drawings apply to this situation.
- If nonpotable water is utilized it must be identified per IPC 608.8
- Given the lack of a complete design, this review is cursory and incomplete. i.e. more review comments are possible upon submission.
|
|
Misc
Corrective Action Required
412.4.3 Floor surface. Floors shall be graded and drained to prevent water or fuel from remaining on the floor. Floor drains shall discharge through an oil separator to the sewer or to an outside vented sump. (see code for exceptions)
Action required: Provide oil separator at DWV piping system that serves trench drain.
1/20/16 - Specify oil separator size and provide installation details.
|
|
Engineered truss package
Copies of the pre-engineered metal building package were not provided at the time of permit application.
Action required: Provide steel building package or request to defer to construction.
1/20/16 - provided
|
|
Misc
Interior walls not specified.
Action required: Provide construction details for interior walls.
1/20/16 - provided
|
|
Accessibility - Water closet clearance width 604.3.1
ICC A117.1-2009 604.3.1 – Clearance width. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall.
Action required: Modify restroom design to demonstrate compliance.
1/20/16 - provided
|
|
Accessibility - Flush controls 604.6
ICC A117.1-2009 604.6 – Flush controls. Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 309. Flush controls shall be located on the open side of the water closet.
Action required: Modify restroom design to demonstrate compliance.
1/20/16 - provided
|
|
Accessibility - Swinging doors - restrooms404.2.3.2
ICC A117.1-2009 Section 603.2.2 Door Swing. Doors shall not swing into the clear floor space or clearance for any fixture. (see code for exceptions)
Action required: Modify restroom design to demonstrate compliance.
1/20/16 - provided
|
|
Bldg - Accessibility - Continuity and components 1007.2
2012 IBC 1007.2 – Continuity and components. Each required accessible means of egress shall be continuous to a public way and shall consist of one or more of the following components: 1. Accessible routes complying with Section 1104. 2. Interior exit stairways complying with Sections 1007.3 and 1022. 3. Interior exit access stairways complying with Sections 1007.3 and 1009.3. 4. Exterior exit stairways complying with Sections 1007.3 and 1026 and serving levels other than the level of exit discharge. 5. Elevators complying with Section 1007.4. 6. Platform lifts complying with Section 1007.5. 7. Horizontal exits complying with Section 1025. 8. Ramps complying with Section 1010. 9. Areas of refuge complying with Section 1007.6. 10. Exterior area for assisted rescue complying with Section 1007.7.
Action required: Specify method and location of accessible entry.
1/20/16 - provided
|
|
Misc
Corrective Action Required
Mechanical design incomplete.
Action required: Provide specifications for under floor heating system. Provide complete HVAC design at office area complete with, but not limited to, duct sizes, furnace specifications, furnace support, etc.
1/20/16 - reference comment #5 for heating equipment.
|
|
Misc
2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
Action required: Provide exterior convenience receptacle within 25' of condensing unit.
1/20/16 - provided
|
|
|
Licensed Contractors
|
Approved
|
01/19/2016
|
01/20/2016
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Approved with Conditions
|
01/05/2016
|
01/05/2016
|
|
Joe Dir
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC OF ALPHBETIC BUILDING ADDRESS ON THE BUILDING READABLE FROM THE ROADWAY. VERIFIED AT INSPECTION.
|
|
Portable fire extinguishers - conspicuous locations
Corrective Action Required
2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
PROVIDE A MINIMUM OF TWO 2A-10BC ( 5 POUND)
FIRE EXTINGUISHERS. VERIFIED AT INSPECTION.
|
|
|
Building Plan Review
|
Rejected
|
01/05/2016
|
12/31/2015
|
|
Joe Frogge
|
|
Final Development Plan
Corrective Action Required
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required: Comment is for informational purposes.
|
|
Code analysis required
Corrective Action Required
A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed.
Action required: Provide code analysis as noted.
|
|
Misc
Corrective Action Required
2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions)
Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
|
|
Misc
Corrective Action Required
412.4.1 Exterior walls. Exterior walls located less than 30 feet (9144 mm) from lot lines or a public way shall have a fire-resistance rating not less than 2 hours.
Action required: Provide UL listed 2 hour fire barrier at north exterior walls within 30 feet of property line.
|
|
Misc
Corrective Action Required
412.4.4 Heating equipment. Heating equipment shall be placed in another room separated by 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. Entrance shall be from the outside or by means of a vestibule providing a two-doorway separation.
Exceptions:
1. Unit heaters and vented infrared radiant heating equipment suspended not less than 10 feet (3048 mm) above the upper surface of wings or engine enclosures of the highest aircraft that are permitted to be housed in the hangar need not be located in a separate room provided they are mounted not less than 8 feet (2438 mm) above the floor in shops, offices and other sections of the hangar communicating with storage or service areas.
2. Entrance to the separated room shall be permitted by a single interior door provided the sources of ignition in the appliances are not less than 18 inches (457 mm) above the floor.
Action required: Furnace to be in a room separated by 2 hour barrier. Provide construction details complete with UL. (It may be more economical to extend under floor heating?)
|
|
Misc
Corrective Action Required
412.4.3 Floor surface. Floors shall be graded and drained to prevent water or fuel from remaining on the floor. Floor drains shall discharge through an oil separator to the sewer or to an outside vented sump. (see code for exceptions)
Action required: Provide oil separator at DWV piping system that serves trench drain.
|
|
Engineered truss package
Corrective Action Required
Copies of the pre-engineered metal building package were not provided at the time of permit application.
Action required: Provide steel building package or request to defer to construction.
|
|
Misc
Corrective Action Required
Interior walls not specified.
Action required: Provide construction details for interior walls.
|
|
Accessibility - Water closet clearance width 604.3.1
Corrective Action Required
ICC A117.1-2009 604.3.1 – Clearance width. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall.
Action required: Modify restroom design to demonstrate compliance.
|
|
Accessibility - Flush controls 604.6
Corrective Action Required
ICC A117.1-2009 604.6 – Flush controls. Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 309. Flush controls shall be located on the open side of the water closet.
Action required: Modify restroom design to demonstrate compliance.
|
|
Accessibility - Swinging doors - restrooms404.2.3.2
Corrective Action Required
ICC A117.1-2009 Section 603.2.2 Door Swing. Doors shall not swing into the clear floor space or clearance for any fixture. (see code for exceptions)
Action required: Modify restroom design to demonstrate compliance.
|
|
Bldg - Accessibility - Continuity and components 1007.2
Corrective Action Required
2012 IBC 1007.2 – Continuity and components. Each required accessible means of egress shall be continuous to a public way and shall consist of one or more of the following components: 1. Accessible routes complying with Section 1104. 2. Interior exit stairways complying with Sections 1007.3 and 1022. 3. Interior exit access stairways complying with Sections 1007.3 and 1009.3. 4. Exterior exit stairways complying with Sections 1007.3 and 1026 and serving levels other than the level of exit discharge. 5. Elevators complying with Section 1007.4. 6. Platform lifts complying with Section 1007.5. 7. Horizontal exits complying with Section 1025. 8. Ramps complying with Section 1010. 9. Areas of refuge complying with Section 1007.6. 10. Exterior area for assisted rescue complying with Section 1007.7.
Action required: Specify method and location of accessible entry.
|
|
Misc
Corrective Action Required
Mechanical design incomplete.
Action required: Provide specifications for under floor heating system. Provide complete HVAC design at office area complete with, but not limited to, duct sizes, furnace specifications, furnace support, etc. Specify restroom exhaust fan complete with duct and termination information.
|
|
Misc
Corrective Action Required
2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
Action required: Provide exterior convenience receptacle within 25' of condensing unit.
|
|
|
Licensed Contractors
|
Approved
|
01/05/2016
|
12/18/2015
|
|
Joe Frogge
|
|
|