Permit Application Status

PRCOM20142400


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20142400
Building Permit - Commercial
Certificate of Occupancy
WHEELER DEALER 17 MULTI LLC
ALTERATION COMMERCIAL
CONVERT EXISTING SHOWROOM SPACE INTO SERVICE AND WASH BAYS
08/21/2014
08/29/2014
11/25/2014
Locations
Contacts
ROTHWELL CONSTRUCTION INC, Address:1500 NORTH 7 HWY STE 100, Phone:(816) 228-8808  
AIRTECH ENGINEERING, Address:9265 FLINT ST, Phone:(913) 888-5900  
KASA ELECTRIC LLC, Address:1206 NW VALLEY RIDGE DR, Phone:(816) 228-4886  
TAYLOR MECHANICAL INC, Address:23700 E 189th st, Phone:(816) 743-9900  
BLACK, CORLEY, OWENS & HUGHES, P.A., Address:2019 WEST SOUTH ST, Phone:(501) 315-7686  
WHEELER DEALER 17 MULTI LLC, Address:50 ROCKEFELLER PLAZA 2ND FLR  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 09/03/2014 08/28/2014
Joe Frogge
LC - MEP Subs
Resolved
08/28/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed Mechanical contractor.
Sprinkler Plan Review Released for Construction 08/27/2014
Brian Austerman
Misc
Corrective Action Required
08/27/2014

No FD comments
Building Plan Review Approved with Conditions 09/03/2014 08/27/2014
Joe Frogge
Bldg - Premises identification/address 501.2
Corrective Action Required
08/27/2014

2012 IBC 501.2 – Premises identification. Action required: Comment is for informational purposes. This structure is addressed separately from main car dealership. Correct address is 1047 SE Oldham Pkwy. Drawing correction is not required.
Fire Plan Review Approved 09/03/2014 08/25/2014
Brian Austerman
Construction documents for fire alarm systems
Corrective Action Required
08/25/2014

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. If alarm system requires modification submit alarm plans for approval
Construction documents - Fire protection systems
Corrective Action Required
08/25/2014

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. If the sprinkler system needs modifications submit alarm plans for approval
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $602.89 $602.89 Paid 08/29/2014
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underground Plumbing Inspection - Commercial Passed 9/23/2014 9/23/2014 at 12:00 AM 09/23/2014
Occupancy Inspection - Codes Commercial Failed 11/13/2014 11/13/2014 at 12:00 AM 11/13/2014
Misc
Corrective Action Required
11/13/2014
NEC 511.12- ALL 125 V, SINGLE PHASE 15- AND 20- AMP RECEPTACLES SHALL HAVE GFCI PROTECTION.
Occupancy Inspection - Fire Failed 11/13/2014 at 12:00 AM 11/14/2014
Misc
Corrective Action Required
11/14/2014
- Provide asprinkler head on the mezzanine, remove all combustibles until completed - provide sprinkler protection under the over head doors (west), (east) doors - properly cover open j-boxes over north door - remove lock from the door seperating the east bay from the south bay - extend alarm notification (alarm) appl into space
Occupancy Inspection - Codes Commercial Full C of O 11/25/2014 11/25/2014 at 12:00 AM 11/25/2014
Misc
Resolved
11/25/2014
NEC 511.12- ALL 125 V, SINGLE PHASE 15- AND 20- AMP RECEPTACLES SHALL HAVE GFCI PROTECTION.
Occupancy Inspection - Fire Passed 11/25/2014 11/25/2014 at 12:00 AM 11/25/2014
Misc
Corrective Action Required
11/14/2014
- Provide asprinkler head on the mezzanine, remove all combustibles until completed - provide sprinkler protection under the over head doors (west), (east) doors - properly cover open j-boxes over north door - remove lock from the door seperating the east bay from the south bay - extend alarm notification (alarm) appl into space
Documents & Images
Date Uploaded File Type Document Name
08/25/2014 Letter Fire Building Plan Review
08/27/2014 Letter Codes P/R Corrections Document
08/27/2014 Letter Fire (Sprinkler) Plan Review
08/29/2014 Letter Codes Plan Review Conditions
08/29/2014 Letter Codes Building Permit
08/29/2014 Receipt Receipt for transaction: 2014-001671
09/23/2014 Letter Inspection Summary
11/13/2014 Letter Inspection Summary
11/25/2014 Letter Codes Final Certificate of Occupancy
11/25/2014 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home