Permit Application Status

PRCOM20141072


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20141072
Building Permit - Commercial
Certificate of Occupancy
RESIDENCES AT NEW LONGVIEW LLC
NEW COMMERCIAL
LEASING OFFICE AND CLUBHOUSE
05/08/2014
07/10/2014
11/23/2014
08/09/2016
Locations
Contacts
NEIGHBORS CONSTRUCTION COMPANY INC, Address:1708 E 123RD ST, Phone:(913) 422-5555  
STANDARD HEATING & COOLING LLC, Address:2006 E PRAIRIE CIRCLE, Phone:(913) 782-5469  
LYNN ELECTRIC & COMMUNICATIONS INC, Address:725 N 2ND ST STE K, Phone:(785) 843-5709  
BLUE RIVER PLUMBING INC, Address:9125 BARTON ST, Phone:(913) 701-6410  
NSPJ ARCHITECTS, Address:3515 W 75TH ST, SUITE 201  
RESIDENCES AT NEW LONGVIEW LLC, Address:5015 NW CANAL ST  
CITY OF LEES SUMMIT, Address:220 S MAIN  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 10/10/2014
Brian Austerman
Misc
Corrective Action Required
10/10/2014

Building alarm plan is designed for having a sprinkler system, per the architect this building will not be a sprinklered building 10/10/14 Building will have a manual system with smoke detection. Also the other buildings will report alarms to this panel as supervisory/trouble
Misc
Corrective Action Required
10/10/2014

Delete outside horn strobe, building is not equipped with a sprinkler system
Alarm Plan Review Rejected 08/22/2014
Brian Austerman
Misc
Corrective Action Required
08/22/2014

Building alarm plan is designed for having a sprinkler system, per the architect this building will not be a sprinklered building
Licensed Contractors Approved 06/11/2014 07/09/2014
Mike Weisenborn
Business License
Resolved
07/09/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
License contractors
Resolved
07/09/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Final Development Plan Review Approved 07/22/2014 07/09/2014
Mike Weisenborn
Fire Plan Review Approved with Conditions 06/11/2014 06/11/2014
Mike Weisenborn
Hazardous material identification
Corrective Action Required
06/04/2014

2012 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. Indicate the types of chemicals to be used for pool water treatment, provide NFPA 704 diamond or other signage as necessary on chemical storage rooms
Type I hood - Where required
Corrective Action Required
06/04/2014

2012 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Provide information on Bistro kitchen equipment and use. If grease laden vapors will be prodiced a Type 1 hood will be required, submit hood plans. If grease vapors will not be produced provide a letter stating the use of the range ISSUE RESOLVED, IT IS TO BE USED AS A WARMING KITCHEN ONLY
Misc
Corrective Action Required
06/04/2014

[B] 1008.1.9.8  Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Groups A, B, E, I-2, M, R-1 or R-2, and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 or R-2, are permitted to be equipped with an approved entrance and egress access control system, listed in accordance with UL 294, which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public. For information only
Address numbers required
Corrective Action Required
06/04/2014

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). For information only, verified at inspection
Portable fire extinguishers - general
Corrective Action Required
06/04/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 2A10B;C extinguisher (5lb) for every 3,000 sq/ft or 75' travel distance
Misc
Corrective Action Required
06/09/2014

6/9/14. Plan review for added CO monitoring of the garages and common areas. Approved as submitted
Building Plan Review Approved with Conditions 06/11/2014 06/10/2014
Joe Frogge
Bldg - Panic and fire exit hardware 1008.1.10
Corrective Action Required
06/04/2014

2012 IBC 1008.1.10 – Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.9.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. Action required: Exit doors to have panic hardware. To be verified at inspection
Misc
Corrective Action Required
06/04/2014

2012 IBC 1110.1 Signs. Required accessible elements shall be identified by the international symbol of accessibility at the following locations: 1. Accessible parking spaces required by section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessible rooms where multiple single-user toilet or bathing rooms are clustered at a single location. 4. Accessible entrances where not all entrances are accessible. 5. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 6. Family or assisted-use toilet and bathing rooms. 7. Accessible dressing, fitting and locker rooms where not all such rooms are accessible. 8. Accessible areas of refuge in accordance with Section 1007.9. 9. Exterior areas for assisted rescue in accordance with Section 1007.9. Action required: This comment is for informational purposes. Accessibility signage to be verified at inspection.
Misc
Resolved
06/10/2014

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected. noted receptacles served by gfci upstream
Licensed Contractors Rejected 06/20/2014 05/22/2014
Joe Frogge
Business License
Resolved
07/09/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
License contractors
Resolved
07/09/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of MEP contractors.
Building Plan Review Rejected 05/22/2014 05/21/2014
Joe Frogge
Bldg - Panic and fire exit hardware 1008.1.10
Corrective Action Required
05/21/2014

2012 IBC 1008.1.10 – Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.9.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. Action required: Exit doors to have panic hardware.
Misc
Corrective Action Required
05/21/2014

2012 IBC 1110.1 Signs. Required accessible elements shall be identified by the international symbol of accessibility at the following locations: 1. Accessible parking spaces required by section 1106.1 except where the total number of parking spaces provided is four or less. 2. Accessible passenger loading zones. 3. Accessible rooms where multiple single-user toilet or bathing rooms are clustered at a single location. 4. Accessible entrances where not all entrances are accessible. 5. Accessible check-out aisles where not all aisles are accessible. The sign, where provided, shall be above the check-out aisle in the same location as the check-out aisle number or type of check-out identification. 6. Family or assisted-use toilet and bathing rooms. 7. Accessible dressing, fitting and locker rooms where not all such rooms are accessible. 8. Accessible areas of refuge in accordance with Section 1007.9. 9. Exterior areas for assisted rescue in accordance with Section 1007.9. Action required: This comment is for informational purposes. Accessibility signage to be verified at inspection.
Misc
Corrective Action Required
05/21/2014

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected.
Fire Plan Review Rejected 05/22/2014 05/13/2014
Brian Austerman
Hazardous material identification
Corrective Action Required
05/13/2014

2012 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. Indicate the types of chemicals to be used for pool water treatment, provide NFPA 704 diamond or other signage as necessary on chemical storage rooms
Type I hood - Where required
Corrective Action Required
05/13/2014

2012 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Provide information on Bistro kitchen equipment and use. If grease laden vapors will be prodiced a Type 1 hood will be required, submit hood plans. If grease vapors will not be produced provide a letter stating the use of the range
Misc
Corrective Action Required
05/13/2014

[B] 1008.1.9.8  Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Groups A, B, E, I-2, M, R-1 or R-2, and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 or R-2, are permitted to be equipped with an approved entrance and egress access control system, listed in accordance with UL 294, which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public. For information only
Address numbers required
Corrective Action Required
05/13/2014

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). For information only, verified at inspection
Portable fire extinguishers - general
Corrective Action Required
05/13/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a 2A10B;C extinguisher (5lb) for every 3,000 sq/ft or 75' travel distance
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $3,111.68 $3,111.68 Paid 07/10/2014
8331507-Sewer Connection Fee $420.00 $420.00 Paid 07/10/2014
$420.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Failed 7/25/2014 (1:00) 7/25/2014 at 12:00 AM 07/25/2014
Misc
Corrective Action Required
07/25/2014
CLUB HOUSE-NO REBAR ON SITE- SITE MEETING ONLY
Footing Inspection - Commercial Partial 7/31/2014 (11:00) 7/31/2014 at 12:00 AM 07/31/2014
Foundation Inspection - Commercial Partial 8/6/2014 (10:00) 8/6/2014 at 12:00 AM 08/06/2014
Footing Inspection - Commercial Passed 8/15/2014 (9:00) 8/15/2014 at 12:00 AM 08/15/2014
Underslab Plumbing Inspection - Commercial Passed 8/20/2014 at 12:00 AM 08/20/2014
Underslab Electrical Inspection - Commercial Passed 8/29/2014 8/29/2014 at 12:00 AM 08/29/2014
Underslab Plumbing Inspection - Commercial Partial 9/3/2014 9/3/2014 at 12:00 AM 09/03/2014
Misc
Corrective Action Required
09/03/2014
PARTIAL-INTERIOR DRAIN TILE APPROVED
Foundation Inspection - Commercial Passed 9/16/2014 (8:00) 9/1/2014 09/16/2014
Misc
Corrective Action Required
09/16/2014
FOUNDATION POST TENSION -slab inspected
Sewer Service Inspection Passed 10/27/2014 at 12:00 AM 10/27/2014
All Rough Inspection - Commercial Partial 12/3/2014 12/3/2014 at 12:00 AM 12/03/2014
Misc
Corrective Action Required
12/03/2014
PARTIAL INSPECTION- -SHEAR WALL EXTERIOR PLYWOOD NAIL PATTERN
All Rough Inspection - Commercial Partial 12/11/2014 12/15/2014 at 12:00 AM 12/15/2014
Misc
Corrective Action Required
12/03/2014
PARTIAL INSPECTION- -SHEAR WALL EXTERIOR PLYWOOD NAIL PATTERN
All Rough Inspection - Commercial Partial 1/2/2015 1/2/2015 at 12:00 AM 01/02/2015
Misc
Corrective Action Required
12/15/2014
PARTIAL INSPECTION- -SHEAR WALL EXTERIOR PLYWOOD NAIL PATTERN BSMT CENTER NORTH SHEAR WALL OK TO INSULATE
Rough Electrical Inspection - Commercial Failed 1/13/2015 1/13/2015 at 12:00 AM 01/13/2015
Misc
Corrective Action Required
01/13/2015
INSPECTED 4 CAN LIGHTS IN THE SOUTH FACE PEAK OF EXTERIOR SOFFIT - SECURE MC TO FRAMING WITHIN 12" OF CAN.
Gas Service Inspection - Commercial Failed 1/14/2015 1/14/2015 at 12:00 AM 01/14/2015
Misc
Corrective Action Required
01/14/2015
tested from meter to pool room. 2" line no other pipe installed need to revise plans to show size and location of pipe.
All Rough Inspection - Commercial Failed 1/16/2015 1/16/2015 at 12:00 AM 01/16/2015
Misc
Corrective Action Required
01/02/2015
PARTIAL INSPECTION- -SHEAR WALL EXTERIOR PLYWOOD NAIL PATTERN
Misc
Corrective Action Required
01/16/2015
3301 -Firestop duct chase 1st floor -attic ventilation throughout -attic acces on north west end - protect all electrical within 6' of attic access - porivde truss repair reports - truss nail hangers into steel gusset plates - Nail plates plumbing at blocks mid wall - strap cut wall at hvac run next to kitchen ^ 10d nailles required each side of strap - nails each side screws don't meet code - Dead space for mail boxes Firestop (will rock ceiling). Bsmt level--- Tempered window landing -Lights at stairs and landing -Gas line resubmit -Seal hole gas line found wall -Fur out around gas line, install nail plates -Plumbing plates bsmt pool room -Hose bib pool wall studs cut, nail plates - Firestop ceiling height throughout seal all pentrations. -1000 sq ft -Clean out bsmt wall at main panel install all clean outs in basement where required by code. clean outs installed are turned in to wall 18" access is requried -Shear wall panel in wall plywood provide letter for panel in wall - Nail protection hall sink - clean outs foundation walls Main water line crimped at foundation wall where enters Valve water main. provide shut off at water main
All Rough Inspection - Commercial Failed 1/22/2015 1/22/2015 at 12:00 AM 01/22/2015
Misc
Corrective Action Required
01/16/2015
PARTIAL INSPECTION- -SHEAR WALL EXTERIOR PLYWOOD NAIL PATTERN interior walls- 2nd side incomplete
Misc
Corrective Action Required
01/16/2015
3301 -Firestop duct chase 1st floor, 2 open holes in the floor -attic ventilation throughout, incomplete, covered with insulation - porivde truss repair reports, need to get copies - truss nail hangers into steel gusset plates** - Nail plates plumbing at blocks mid wall - strap cut wall at hvac run next to kitchen ^ 10d nailles required each side of strap, need to firestop from attic at strap Tempered window landing -Gas line resubmit, -Fur out around gas line, install nail plates -Plumbing plates bsmt pool room- incorrect plates used -1000 sq ft -Clean out bsmt walls, install all clean outs in basement where required by code. clean outs installed are turned in to wall 18" access is requried -Shear wall panel in wall plywood provide letter for panel in wall, need letter - clean outs foundation walls Main water line crimped at foundation wall where enters Valve water main. provide shut off at water main- incomplete inspection items incomplete. recall when all items are completed. remove insulation from water line, attic vents and all inspectio items.
Underground Electrical Inspection - Commercial Partial 1/26/2015 1/26/2015 at 12:00 AM 01/26/2015
Misc
Corrective Action Required
01/26/2015
underground electrical - from club house to around pool under pool deck , ok to cover
Electrical Service Inspection Partial 2/10/2015 2/10/2015 at 12:00 AM 02/10/2015
Misc
Corrective Action Required
02/10/2015
Main disconnect approved to release for service. Grounding inspected to disconnect. no other panels approved to release. Main Disconnect will be locked
Above Ceiling Inspection Failed 3/24/2015 3/24/2015 at 12:00 AM 03/24/2015
LOWER LEVEL
Corrective Action Required
03/24/2015
HARD CEILING IT ROOM NEXT TO BAR AREA- CEILING COVERING ELECTICAL BOX FOR CEILING LIGHT ON EAST WALL OF ROOOM.
Gas Piping Inspection - Commercial Failed 4/6/2015 4/6/2015 at 12:00 AM 04/06/2015
Misc
Corrective Action Required
04/06/2015
INSTALL TRACE WIRE FOR UNDERGROUND UNDERSLAB PIPING
Gas Piping Inspection - Commercial Partial 4/7/2015 4/7/2015 at 12:00 AM 04/07/2015
Misc
Corrective Action Required
04/06/2015
GAS PIPE INSPECITON- FROM BUILDING TO BBQ GRILL LOCATION, PIPE ONLY NO FIITINGS, NO CONNECTION TO STEEL PIPE, NO PRESSURE TEST. PARTIAL APPROVAL
Alarm Test Passed 4/15/2015 at 12:00 AM 04/15/2015
Alarm Test Failed 4/14/2015 at 12:00 AM 04/15/2015
Occupancy Inspection - Engineering Temporary C of O 4/17/2015 at 12:00 AM 04/17/2015
PW-Misc
Corrective Action Required
04/17/2015
Clubhouse and building one okay to have Occupancy. Bonds and Affidavits will be needed before building 3 is released A full more appropriate punch list will be given at a later date
Occupancy Inspection - Fire Temporary C of O 4/17/2015 at 12:00 AM 04/17/2015
Occupancy Inspection - Planning Temporary C of O 04/17/2015
Corrective Action Required
04/17/2015
Complete landscaping per approved plan.
Corrective Action Required
04/17/2015
Incorrect accessible parking spaces signs were installed. Required signs are type R7-8 in the Manual of Uniform Traffic Control Devices (MUTCD), which have a white background, green text, green border and blue wheelchair symbol.
Resolved
03/25/2016
Sidewalk connecting the parking area on the west side of the clubhouse to the pool area below the clubhouse shall be completed per the approved plan.
Occupancy Inspection - Codes Commercial Failed 4/17/2015 4/17/2015 at 12:00 AM 04/17/2015
Misc
Corrective Action Required
04/17/2015
- pending approval from other departments - pool will not be included in this inspection Clubhouse- - provide Grippable handrails for stairs - guard is at 41" at stairs -Tanning room needs ada doorknobs - adjust door push and pull on all doors for ada requirement -water shut off valve not installed - back flow not installed - need gas line change on plans for pool heaters -elevator approval - occupancy load signs -see other department comments for other outstanding issues ok to Stock furniture and equipment. NOT to be open to the Public.
Occupancy Inspection - Codes Commercial Temporary C of O 4/22/2015 4/22/2015 at 12:00 AM 04/22/2015
Misc
Corrective Action Required
04/17/2015
Clubhouse- - provide Grippable handrails for stairs, provide 1 1/2" clearance on west handrail to landing -see other department comments for other outstanding issues Approved for TCO- 4-22-15 Not included in this inspection, pool, gas line to grills, fence, pool deck, pool shut off, etc. building of club house structure only.
Gas Piping Inspection - Commercial Failed 6/22/2015 6/22/2015 at 12:00 AM 06/22/2015
Misc
Corrective Action Required
04/07/2015
GAS PIPE INSPECITON- open pipe in pool heater room. flue clearance to pool heaters at exterior wall. need to check combustion air requirements on room size. do not release gas
Gas Piping Inspection - Commercial Failed 6/22/2015 06/22/2015
Misc
Corrective Action Required
06/22/2015
GAS PIPE INSPECITON- open pipe in pool heater room. flue clearance to pool heaters at exterior wall. need to check combustion air requirements on room size. ** no connection from gas line in room to pool bbq grills, grills not installed do not release gas
Occupancy Inspection - Codes Commercial Failed 6/23/2015 at 12:00 AM 06/23/2015
Misc
Corrective Action Required
04/22/2015
- pending approval from other departments - pool will not be included in this inspection Clubhouse- - provide Grippable handrails for stairs, provide 1 1/2" clearance on west handrail to landing -see other department comments for other outstanding issues Approved for TCO- 4-22-15
Gas Piping Inspection - Commercial Partial 6/23/2015 at 12:00 AM 06/23/2015
Misc
Corrective Action Required
06/22/2015
GAS PIPE INSPECITON- open pipe in pool heater room. flue clearance to pool heaters at exterior wall. ** no connection from gas line in room to pool bbq grills, grills not installed GAS CAPPED AT POOL ROOM NO CONNECTION TO GRILLS TO OUTSIDE WALL
Corrective Action Required
06/23/2015
Gas Service Inspection - Commercial Partial 09/22/2015
Misc
Corrective Action Required
01/14/2015
no connection from pool room to grill line out side the building. ok to release for partial approval.
Occupancy Inspection - Fire Passed 3/17/2016 12/31/2015
Occupancy Inspection - Water Utilities Passed 4/22/2015 4/22/2015 at 12:00 AM 03/11/2016
Occupancy Inspection - Engineering Passed 03/17/2016
PW-Misc
Corrective Action Required
04/17/2015
Clubhouse and building one okay to have Occupancy. Bonds and Affidavits will be needed before building 3 is released A full more appropriate punch list will be given at a later date
Gas Piping Inspection - Commercial Passed 1/26/2015 at 12:00 AM 03/25/2016
Gas Service Inspection - Commercial Passed 1/26/2015 03/25/2016
Misc
Resolved
03/25/2016
no connection from pool room to grill line out side the building. ok to release for partial approval.
Underslab Plumbing Inspection - Commercial Passed 10/27/2014 5/28/2014 04/25/2016
Misc
Resolved
04/25/2016
PARTIAL-INTERIOR DRAIN TILE APPROVED
Rough Electrical Inspection - Commercial Passed 04/25/2016
Misc
Resolved
04/25/2016
INSPECTED 4 CAN LIGHTS IN THE SOUTH FACE PEAK OF EXTERIOR SOFFIT - SECURE MC TO FRAMING WITHIN 12" OF CAN.
Water Service Inspection Passed 04/25/2016
Above Ceiling Inspection Passed 04/25/2016
LOWER LEVEL
Resolved
04/25/2016
HARD CEILING IT ROOM NEXT TO BAR AREA- CEILING COVERING ELECTICAL BOX FOR CEILING LIGHT ON EAST WALL OF ROOOM.
Underground Electrical Inspection - Commercial Passed 5/13/2015 04/25/2016
Misc
Resolved
04/25/2016
underground electrical - from club house to around pool under pool deck , ok to cover
All Rough Inspection - Commercial Passed 1/23/2015 04/25/2016
Misc
Resolved
04/25/2016
PARTIAL INSPECTION- -SHEAR WALL EXTERIOR PLYWOOD NAIL PATTERN interior walls- 2nd side incomplete
Misc
Resolved
04/25/2016
3301 -Firestop duct chase 1st floor, 2 open holes in the floor -attic ventilation throughout, incomplete, covered with insulation - porivde truss repair reports, need to get copies - truss nail hangers into steel gusset plates** - Nail plates plumbing at blocks mid wall - strap cut wall at hvac run next to kitchen ^ 10d nailles required each side of strap, need to firestop from attic at strap Tempered window landing -Gas line resubmit, -Fur out around gas line, install nail plates -Plumbing plates bsmt pool room- incorrect plates used -1000 sq ft -Clean out bsmt walls, install all clean outs in basement where required by code. clean outs installed are turned in to wall 18" access is requried -Shear wall panel in wall plywood provide letter for panel in wall, need letter - clean outs foundation walls Main water line crimped at foundation wall where enters Valve water main. provide shut off at water main- incomplete inspection items incomplete. recall when all items are completed. remove insulation from water line, attic vents and all inspectio items.
Occupancy Inspection - Codes Commercial Failed 6/20/2016 06/20/2016
Misc
Corrective Action Required
06/23/2015
Clubhouse- - provide Grippable handrails for stairs, provide 1 1/2" clearance on west handrail to landing. failed no change-6/20/16
Occupancy Inspection - Codes Commercial Full C of O 08/09/2016
Misc
Corrective Action Required
06/20/2016
Clubhouse- - provide Grippable handrails for stairs, provide 1 1/2" clearance on west handrail to landing. failed no change-6/20/16
Documents & Images
Date Uploaded File Type Document Name
05/13/2014 Letter Fire Building Plan Review
05/22/2014 Letter Codes P/R Corrections Document
06/09/2014 Letter Fire Building Plan Review
07/09/2014 Letter Codes Plan Review Conditions
07/10/2014 Letter Codes Building Permit
07/25/2014 Letter Inspection Summary
07/31/2014 Letter Inspection Summary
08/06/2014 Letter Inspection Summary
08/15/2014 Letter Inspection Summary
08/20/2014 Letter Inspection Summary
08/22/2014 Letter Fire (Alarm) Plan Review Notice
08/29/2014 Letter Inspection Summary
09/03/2014 Letter Inspection Summary
09/09/2014 Letter Codes Plan Review Conditions
09/16/2014 Letter Inspection Summary
10/10/2014 Letter Fire (Alarm) Plan Review Notice
10/27/2014 Letter Inspection Summary
12/03/2014 Letter Inspection Summary
01/02/2015 Letter Inspection Summary
01/13/2015 Letter Inspection Summary
01/14/2015 Letter Inspection Summary
01/16/2015 Letter Inspection Summary
01/22/2015 Letter Inspection Summary
01/26/2015 Letter Inspection Summary
02/10/2015 Letter Inspection Summary
03/24/2015 Letter Inspection Summary
04/06/2015 Letter Inspection Summary
04/07/2015 Letter Inspection Summary
04/17/2015 Letter PW-Daily Inspection Summary
04/17/2015 Letter Inspection Summary
04/22/2015 Letter Codes Temporary Certificate of Occupancy
06/23/2015 Letter Inspection Summary
06/23/2015 Letter Inspection Summary
09/22/2015 Letter Inspection Summary
04/25/2016 PW-Punch List0
06/20/2016 Letter Inspection Summary
08/09/2016 Letter Codes Final Certificate of Occupancy
08/10/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home