Summary
PL2022265
TIFFANY WOODS LOTS 4C AND 7C - HYDRANT RELOCATION
Engineering Plan Review
Engineering Plan Review
Approved
07/12/2022
MILLIGAN TYLER & ERIN
Locations
Contacts
Julie Sellers, Address:Olsson Associates, Phone:(816) 361-1177  
MILLIGAN TYLER & ERIN, Address:1600 NE DALTONS RIDGE DR  
UMB BANK NA, Address:1010 GRAND BLVD  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review No Comments 08/09/2022 08/03/2022
Sue Pyles, P.E.
Engineering Review Corrections 08/04/2022 08/02/2022
Sue Pyles, P.E.
Corrective Action Required
08/02/2022

Include the straddle block symbol in the Plan View Legend.
Corrective Action Required
08/02/2022

Include a call-out for the straddle block in Plan view.
Corrective Action Required
08/02/2022

Include the necessary City standard details (WAT-3 and WAT-7) in the plan set.
Corrective Action Required
08/02/2022

The City will allow the existing main to be either abandoned in place or removed. Please specify which alternative will be used.
Engineering Review Corrections 07/27/2022 07/25/2022
Sue Pyles, P.E.
Corrective Action Required
07/25/2022

Submit an Engineer's Estimate of Probable Construction Costs.
Corrective Action Required
07/25/2022

Show location of all oil/gas wells, or indicate none are present, and cite the source.
Corrective Action Required
07/25/2022

Show and label the location and limits of the one percent annual chance flood, as set forth on the current FEMA maps, with reference to the panel number and effective date. Elevations shall be provided if shown on the FEMA map.
Corrective Action Required
07/25/2022

Please add the following note: “The contractor shall contact the City’s Development Services Engineering Inspection to schedule a pre-construction meeting with a Field Engineering Inspector prior to any land disturbance work at (816) 969-1200.”
Corrective Action Required
07/25/2022

The plan set must be signed/sealed by a professional engineer licensed in the State of Missouri.
Corrective Action Required
07/26/2022

Locate the FH a minimum of 10’ north of the property line between 512 and 521 NE Promised View Drive. This is required in order to make the private service line connection on 512 NE Promised View Drive. Include a straddle block to restrain the isolation valve of the fire hydrant.
Fire Review No Comments 07/27/2022 07/14/2022
Jim Eden
Hearings

There are no hearings for this planning application.

Documents & Images
Upload Documents
  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:
Browse..





    Portal Home