Oakview Storage Lot 5 Public Sanitary Main Extension
Engineering Plan Review
Engineering Plan Review
Approved
02/02/2021
OAK VIEW LEES SUMMIT LLC
Locations
Contacts
OAK VIEW LEES SUMMIT LLC, Address:201 HAWKS RIDGE TRL  
SCHLAGEL & ASSOCIATES, Address:14920 W 107TH ST, Phone:(913) 492-5158  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review No Comments 03/10/2021 03/10/2021
Sue Pyles, P.E.
Engineering Review Corrections 03/05/2021 03/03/2021
Sue Pyles, P.E.
Corrective Action Required
03/03/2021

Minimum lateral spacing required is 4’ outside edge of MH to edge of wye fitting. Review the lateral spacing and revise as needed. Please add enough information to ensure it can be located correctly during construction.
Engineering Review Corrections 02/18/2021 02/18/2021
Sue Pyles, P.E.
Corrective Action Required
02/18/2021

General: • Remove the proposed stub at MH B1. • Please submit the proposed easement for review. • Please revise the engineer’s estimate to match the information in the plans.
Corrective Action Required
02/18/2021

Sheet C0.0: • Remove Dena Mezger as the Public Works contact. • Revise the Water department name to Water Utilities. • KCP&L is now Evergy. Please revise the contact information. • Revise General Note 15 to “The contractor shall contact the City’s Development Services Engineering Inspection to schedule a pre-construction meeting with an inspector prior to any land disturbance work at (816) 969-1200”. • Delete General Notes 16 & 17. • Remove the approval signature block for the City. A stamp will be provided electronically when approved. • Revise the Summary of Quantities to match the information in the plans.
Corrective Action Required
02/18/2021

Sheet C1.0: Show location of all oil/gas wells, or indicate none are present, and cite the source.
Corrective Action Required
02/18/2021

Sheet C3.0: • The City’s trenching requirements have changed. There is now 12” of rock required over the pipe. Please revise the detail. • Remove Standard Details SAN-1 & WAT-6, they are not used.
Hearings

There are no hearings for this planning application.

Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home