Planning Application Status

PL2021022




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2021022
Shake Shack
Commercial Final Development Plan
Commercial Final Development Plan
Approved
01/19/2021
CITY OF LEES SUMMIT
Locations
Contacts
CITY OF LEES SUMMIT, Address:220 SE GREEN ST  
STREETS OF WEST PRYOR LLC, Address:7200 W 132ND ST STE 150  
Sam Malinowsky, Address:SM Engineering, Phone:(785) 341-9747  
SWP II LLC, Address:7200 W 132ND ST STE 150  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Review Approved with Conditions 03/09/2021 03/09/2021
Dawn Bell
Code Statement
Corrective Action Required
03/02/2021

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Engineering Review Approved with Conditions 03/09/2021 03/09/2021
Sue Pyles, P.E.
DE C&O #11 Pavement Thickness
Corrective Action Required
03/09/2021

Private parking lots shall follow Article 8 of the Unified Development Ordinance for pavement thickness and base requirements.
DE Contact Field Eng. Inspector
Corrective Action Required
03/09/2021

Prior to the commencement of any construction activities, the Contractor shall contact Field Engineering Inspections at (816) 969-1200 to coordinate a preconstruction meeting / conference with the assigned Field Engineering Inspector.
DE Engineers Estimate
Corrective Action Required
03/09/2021

The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $39,619.69
DE Future Repair Work
Corrective Action Required
03/09/2021

Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
Misc.
Corrective Action Required
03/09/2021

A recorded copy of the proposed U/E along NW Lowenstein Drive must be provided to the City prior to any form of occupancy.
Planning Review No Comments 03/09/2021 03/08/2021
Jennifer Thompson
Traffic Review No Comments 03/09/2021 03/04/2021
Michael Park
Building Codes Review No Comments 03/09/2021 03/03/2021
Joe Frogge
Building Codes Review No Comments 02/26/2021 02/26/2021
Joe Frogge
Planning Review No Comments 02/26/2021 02/25/2021
Jennifer Thompson
Engineering Review Corrections 02/26/2021 02/24/2021
Sue Pyles, P.E.
Corrective Action Required
02/24/2021

Please show and label all current easements throughout the plan set. Please note that some of the easements shown on the Final Plat included in the plans have been vacated.
Corrective Action Required
02/24/2021

Please show the existing water line crossing NW Lowenstein Drive throughout the plan set, not just on Sheet C5.0.
Corrective Action Required
02/24/2021

Sheet C5.0: • Please locate the water meters in the utility easement within 1’ of the easement line, as required by Design and Construction Manual Section 6901.L.1. • Please locate the backflow prevention vault within 5’ of the utility easement line, on the private side, as required by Design and Construction Manual Section 6901.I.3. • Revise Utility Note 9 to specify Type “K” Copper material at least 10 feet beyond the water meter.
Corrective Action Required
02/24/2021

Sheet C10.0: The geogrid specified in the asphalt pavement details isn’t on the current Public Works Approved Products List. Please revise.
Corrective Action Required
02/24/2021

Sheet C14.0: Please relocate the irrigation water source label leader, it appears to be pointing to the wrong location.
Corrective Action Required
02/24/2021

Estimate: • Include erosion and sediment control items. • Please verify the water service line quantity.
Fire Review Approved with Conditions 02/26/2021 02/24/2021
Jim Eden
Code Statement
Corrective Action Required
02/26/2021

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Traffic Review No Comments 02/26/2021 02/22/2021
Michael Park
Building Codes Review No Comments 02/04/2021 02/18/2021
Joe Frogge
Planning Review Corrections 02/04/2021 02/17/2021
Jennifer Thompson
Corrective Action Required
02/17/2021

Provide color elevation renderings similar to what was submitted with the preliminary development plan. They also provided a multidimensional view. Label the exterior building materials. Label the orientation for each elevation. Dash in the roof-mounted units and illustrate how they will be screened from view (for each elevation).
Corrective Action Required
02/17/2021

On Sheet C1.0 the legal description reflects both lots, revise to reference Lot 2 only.
Corrective Action Required
02/17/2021

Show the proposed stacking of the vehicles within the drive-thru.
Traffic Review No Comments 02/04/2021 02/03/2021
Michael Park
Engineering Review Corrections 02/04/2021 02/03/2021
Sue Pyles, P.E.
Corrective Action Required
02/03/2021

Submit an Engineer's Estimate of Probable Construction Costs.
Corrective Action Required
02/03/2021

Sheet C1.0: Show location of all oil/gas wells, or indicate none are present, and cite the source.
Corrective Action Required
02/03/2021

Sheet C3.0: • Please remove the “PV1” label. It isn’t necessary on this sheet. • As this sheet is intended to show the overall layout for the proposed project, it should reflect just that. Please clearly show the new portion of retaining wall and delete the existing retaining wall that is being removed.
Corrective Action Required
02/03/2021

Sheet C4.0: • The Detail List shows “CW1” for the curb walk at building, but it is labeled as “CW2” in the Plan view. Please revise. If “CW1” is not used, please delete from the list. • “TP” is shown in Plan view but is not included in the Detail List. Please add. • The Detail List shows “PK-2” for the accessible sign, but they are labeled as “PK1” in the Plan view. Please revise.
Corrective Action Required
02/03/2021

Sheet C5.0: • Please locate the domestic water line connection, water meter, and Backflow Prevention Device per Section 6900 of the Design and Construction Manual. • Please revise the detail referenced in Note 20E, it is incorrect. • Why is the sanitary sewer service line 6”? That seems excessive. • Note 61 seems to be pointing to the wrong location. • Please include flowlines at the sanitary cleanouts and connection to the public main. • Utility Note 10 references KCP&L, now Evergy.
Corrective Action Required
02/03/2021

Sheet C6.0: Please clearly delineate the existing TW and BW where the new wall will connect.
Corrective Action Required
02/03/2021

Sheet C7.0: The ADA-accessible ramps to the north of the proposed building do not have complete design information. Please revise similar to the other ramps on site.
Corrective Action Required
02/03/2021

Sheet C9.0: The existing inlets are grate inlets. Please include the appropriate standard detail.
Fire Review Approved with Conditions 02/04/2021 01/25/2021
Jim Eden
Code Statement
Informational
01/25/2021

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Fees
Paid Fees Amount Paid Owing Date Paid
9110077-Final Development Plan fee $600.00 $600.00 Paid 02/17/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Hearings

There are no hearings for this planning application.

Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home