Summary
PL2018217
WOODSIDE RIDGE 1ST PLAT - WATER LINE
Engineering Plan Review
Engineering Plan Review
Complete
12/03/2018
CLAYTON PROPERTIES GROUP INC
Locations
Contacts
OLSSON , Address:7301 W 133RD ST STE 200, Phone:(913) 381-1170  
CLAYTON PROPERTIES GROUP INC, Address:120 SE 30TH ST  
CLAYTON PROPERTIES GROUP INC, Address:120 SE 30TH ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review No Comments 03/21/2019 03/21/2019
Gene Williams, P.E.
Engineering Review Corrections 12/26/2018 12/31/2018
Gene Williams, P.E.
Corrective Action Required
12/26/2018

Sheet C301: Please revise the Public Works contact information to read "Development Services 816-969-1200".
Corrective Action Required
12/26/2018

Is it possible to provide a single page overview sheet, in addition to the larger scale overview sheets? This will greatly enhance the plans both in the field, and office.
Corrective Action Required
12/26/2018

Sheet C306: The water line is too deep at 16+50. Maximum depth of cover is 7 feet.
Corrective Action Required
12/31/2018

Sheet C312: The water main is too deep along the several portions of water line 9. In addition, the City prefers 3.5 feet depth of cover rather than pushing the limit.
Hearings

There are no hearings for this planning application.

Documents & Images
Date Uploaded File Type Document Name
12/31/2018 Letter DE-Comment Letter (Engineering Plans)
04/04/2019 Plans 2019.03.13.WaterPlans
04/08/2019 Engineer Report/Study Woodside Ridge First Plat Water Model
06/03/2019 Letter MDNR Approval
06/04/2019 FeeWorksheetWoodsideRidge1WaterMDP
06/18/2019 Letter DE-Engineering Plans Approval Letter
08/26/2019 Plans Revised C314 WATER MAIN PLAN & PROFILE
11/26/2019 Plans 19-11-19_Woodside Ridge_Water Main Relocation
03/30/2020 Email Fwd Woodside Ridge Water Connection Line 9
11/02/2020 Plans 2020_10_28 Water Main Extension AsBuilts
11/14/2022 Accepted Record Drawings Woodside Ridge 1st Water AsBuilts Accepted RD
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents