Permit Application Status

PRRES20245637


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20245637
Building Permit - Residential
Issued
DJ23 INVESTMENTS LLC
NEW SINGLE FAMILY
NEW HOUSE - ROOF TRUSSES - FINISHED AND UNFINISHED BASEMENT - UNCOVERED DECK
10/23/2024
11/14/2024
04/27/2025
Locations
Contacts
Avital Homes, LLC, Address:7500 W 151st Street, #23100, Phone:(816) 914-7128  
DJ23 INVESTMENTS LLC, Address:7200 W 132ND ST  
Doug Jenson, Address:11010 Nora Dodge Dr, Phone:(816) 266-0685  
DOUG@APGKC.COM  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
CARUTHERS ELECTRICAL LLC, Address:30905 E TRUMAN RD, Phone:(816) 508-9050  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sanitary Sewer Development Fee $2,285.00 $2,285.00 Paid 11/14/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 11/14/2024
7232302-Residential Excise Tax Fee $1,022.72 $1,022.72 Paid 11/14/2024
8331401-Water Tap Fee $3,973.00 $3,973.00 Paid 11/14/2024
8350015-Water Meter Fee $748.03 $748.03 Paid 11/14/2024
9110078-Valuation Fee New Single Family $1,360.85 $1,360.85 Paid 11/14/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 02/10/2025
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 02/10/2025
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 03/17/2025
Outstanding Fees Amount Paid Owing Date Paid
9110080-Not Ready Inspection Fee $75.00 $0.00 $75.00 Not Paid


$75.00    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Plot Plan Inspection Pending
Occupancy Inspection - Codes Residential Pending
Underslab Plumbing Inspection - Residential Pending
Miscellaneous Correction
Corrective Action Required
12/31/2024
Inspection denied. See failed erosion control inspection dated 12/16/2024 and 12/31/2024 KBEARD
Erosion Control Inspection Residential Pending
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
03/04/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - Remove all gravel from within the street - Remove portable toilet from within the street
Erosion Control Inspection Residential Partial 11/26/2024 11/26/2024
Miscellaneous Correction
Informational
11/26/2024
Erosion control is in place at the time of inspection
Footing Inspection - Residential Passed 11/26/2024 11/26/2024 11/26/2024
Water Service Inspection - R Partial 12/16/2024 12/16/2024
Misc
Corrective Action Required
12/16/2024
PARTIAL- POLY OUT OF FOUNDATION
Sewer Service Inspection - R Passed 12/16/2024 12/16/2024 12/16/2024
Erosion Control Inspection Residential Failed 12/16/2024 12/16/2024
Miscellaneous Correction
Resolved
12/16/2024
Erosion control is in place at the time of inspection
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
12/16/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - POST ADDRESS - REMOVE GRAVEL AND DEBRIS FROM STREET - REPAIR SILT FENCE
Water Service Inspection - R Passed 12/17/2024 12/17/2024 12/17/2024
Misc
Resolved
12/17/2024
PARTIAL- POLY OUT OF FOUNDATION
Underslab Plumbing Inspection - Residential Failed 12/19/2024 12/19/2024 12/19/2024
Miscellaneous Correction
Corrective Action Required
12/19/2024
Inspection denied. See failed erosion control inspection dated 12/16/2024 KBEARD
Erosion Control Inspection Residential Failed 12/19/2024 12/19/2024
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
12/16/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - POST ADDRESS - REMOVE GRAVEL AND DEBRIS FROM STREET - REPAIR SILT FENCE
Erosion Control Inspection Residential Failed 12/31/2024 12/31/2024
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
12/19/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - REPAIR SILT FENCE - INSTALL GRAVEL FILTER
Underslab Plumbing Inspection - Residential Failed 12/31/2024 12/31/2024 12/31/2024
Miscellaneous Correction
Corrective Action Required
12/19/2024
Inspection denied. See failed erosion control inspection dated 12/16/2024 and 12/31/2024 KBEARD
Erosion Control Inspection Residential Not Ready 1/8/2025 1/8/2025 01/08/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
12/31/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - REPAIR SILT FENCE - INSTALL GRAVEL FILTER No improvements were made since the last inspection WALK YOUR PROPERTY before scheduling inspections Not ready for re inspection 01/08/2025. KBEARD
Erosion Control Inspection Residential Not Ready 1/23/2025 1/23/2025 01/23/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
01/23/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - REPAIR SILT FENCE - INSTALL GRAVEL FILTER No improvements were made since the last inspection WALK YOUR PROPERTY before scheduling inspections Not ready for re inspection 01/08/2025. KBEARD
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
01/23/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - Clean lot of all debris - REPAIR SILT FENCE - INSTALL GRAVEL FILTER No improvements were made since the last inspection WALK YOUR PROPERTY before scheduling inspections Not ready for re inspection 01/23/25. KBEARD
All Rough Inspection - Residential Failed 1/23/2025 1/23/2025 01/23/2025
Miscellaneous Correction
Corrective Action Required
01/23/2025
Inspection denied, see failed erosion control EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - REPAIR SILT FENCE - INSTALL GRAVEL FILTER No improvements were made since the last inspection WALK YOUR PROPERTY before scheduling inspections Not ready for re inspection 01/08/2025. KBEARD
Erosion Control Inspection Residential Failed 1/29/2025 1/29/2025 01/29/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
01/29/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - Clean lot of all debris - REPAIR SILT FENCE - INSTALL GRAVEL FILTER No improvements were made since the last inspection WALK YOUR PROPERTY before scheduling inspections Not ready for re inspection 01/23/25. KBEARD
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
01/29/2025
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. No inspections until lot has been cleaned - Clean lot of all debris WALK YOUR PROPERTY before scheduling inspections 01/29/25 KBEARD
Erosion Control Inspection Residential Partial 2/3/2025 2/3/2025 02/03/2025
DCM3 ESC REQUIRED 2 DAY
Resolved
02/03/2025
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. No inspections until lot has been cleaned - Clean lot of all debris WALK YOUR PROPERTY before scheduling inspections 01/29/25 KBEARD
Miscellaneous Correction
Informational
02/03/2025
Full erosion control is in place at the time of inspection
Erosion Control Inspection Residential Partial 2/11/2025 02/11/2025
Miscellaneous Correction
Resolved
02/11/2025
Full erosion control is in place at the time of inspection
All Rough Inspection - Residential Failed 2/11/2025 2/11/2025 02/11/2025
Miscellaneous Correction
Resolved
02/11/2025
Inspection denied, see failed erosion control EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - REPAIR SILT FENCE - INSTALL GRAVEL FILTER No improvements were made since the last inspection WALK YOUR PROPERTY before scheduling inspections Not ready for re inspection 01/08/2025. KBEARD
Miscellaneous Correction
Corrective Action Required
02/11/2025
- Exterior garage PFH sheathing failed inspection - Sheathing does not extend to both top plates. See bracing detailed in plans on page S530 illustration #5 This inspection was for a exterior garage PFH only
Electrical Service Inspection Passed 3/4/2025 03/04/2025
Gas Service Inspection - Residential Failed 3/4/2025 03/04/2025
Miscellaneous Correction
Corrective Action Required
03/04/2025
Gas gauge at 0 PSI at time of inspection
Erosion Control Inspection Residential Failed 3/4/2025 03/04/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
03/04/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - Remove all gravel from within the street - Remove portable toilet from within the street
All Rough Inspection - Residential Failed 3/4/2025 3/4/2025 03/04/2025
Miscellaneous Correction
Resolved
03/04/2025
- Exterior garage PFH sheathing failed inspection - Sheathing does not extend to both top plates. See bracing detailed in plans on page S530 illustration #5 This inspection was for a exterior garage PFH only
Miscellaneous Correction
Corrective Action Required
03/04/2025
Note from inspection dated 02/11/2025 Exterior garage PFH sheathing failed inspection - Sheathing does not extend to both top plates. See bracing detailed in plans on page S530 illustration #5 This inspection was for a exterior garage PFH only - See failed erosion control (03/04/25) - See failed gas inspection (03/04/25) - Truss plans are not on site (93/04/25)
All Rough Inspection - Residential Not Ready 3/7/2025 3/7/2025 03/07/2025
Miscellaneous Correction
Corrective Action Required
03/04/2025
Note from inspection dated 02/11/2025 Exterior garage PFH sheathing failed inspection - Sheathing does not extend to both top plates. See bracing detailed in plans on page S530 illustration #5 This inspection was for a exterior garage PFH only - See failed erosion control (03/04/25) - See failed gas inspection (03/04/25) - Truss plans are not on site (3/04/25)
Misc
Corrective Action Required
03/07/2025
No complete truss packet on site for inspection -no city stamped plans on site for inspection
Gas Service Inspection - Residential Passed 3/20/2025 3/20/2025 03/20/2025
Miscellaneous Correction
Corrective Action Required
03/04/2025
Gas gauge at 0 PSI at time of inspection
All Rough Inspection - Residential Failed 3/20/2025 3/20/2025 03/20/2025
Miscellaneous Correction
Corrective Action Required
03/07/2025
Note from inspection dated 02/11/2025 Exterior garage PFH sheathing failed inspection - Sheathing does not extend to both top plates. See bracing detailed in plans on page S530 illustration #5 This inspection was for a exterior garage PFH only - See failed erosion control (03/04/25) - See failed gas inspection (03/04/25) - Truss plans are not on site (3/04/25)
Misc
Corrective Action Required
03/07/2025
-provide City Stamp truss plans for inspection -Provide solid blocking on sheathing breaks in garage on west wall -Strap top plate where lapped less than 24” west garage wall -seal floor penetrations at kitchen island -Fire block wall space to ceiling space at fireplace -stud shoe missing nails at primary bathroom -Fire block primary bathroom fured out wall to ceiling space -Protect dryer vent top plate -Add stud in bed 2 on NE wall where greater than 16” center -Fire block furr down ends -tighten all anchor bolts in basement -provide 3 studs at exterior wall corners in basement -fire blocking must be of approved material (1/2” osb not approved), insulation must be packed tightly and secured -sister all notched wall studs where over notched for anchor bolts
All Rough Inspection - Residential Not Ready 3/24/2025 3/24/2025 03/24/2025
Miscellaneous Correction
Resolved
03/24/2025
Note from inspection dated 02/11/2025 Exterior garage PFH sheathing failed inspection - Sheathing does not extend to both top plates. See bracing detailed in plans on page S530 illustration #5 This inspection was for a exterior garage PFH only - See failed erosion control (03/04/25) - See failed gas inspection (03/04/25) - Truss plans are not on site (3/04/25)
Misc
Corrective Action Required
03/20/2025
-Strap top plate where lapped less than 24” west garage wall -Fire block wall space to ceiling space at fireplace -stud shoe missing nails at primary bathroom -Protect dryer vent top plate -Add stud in bed 2 on NE wall where greater than 16” OC -Fire block furr down ends -tighten all anchor bolts in basement -provide 3 studs at exterior wall corners in basement -fire blocking must be of approved material (1/2” osb not approved), insulation must be packed tightly and secured
All Rough Inspection - Residential Failed 3/25/2025 3/25/2025 03/25/2025
Misc
Corrective Action Required
03/24/2025
-Fire block furr down ends -tighten all anchor bolts in basement Okay insulate
All Rough Inspection - Residential Passed 3/27/2025 3/27/2025 03/27/2025
Misc
Resolved
03/27/2025
-Fire block furr down ends -tighten all anchor bolts in basement Okay insulate
Driveway Inspection Partial 5/9/2025 5/9/2025 05/09/2025
Misc
Informational
05/09/2025
05-09-25 Jamie S, DW is formed compacted. Approved to pour.
Driveway Inspection Passed 5/16/2025 5/16/2025 05/16/2025
Misc
Informational
05/09/2025
05-09-25 Jamie S, DW is formed compacted. Approved to pour. 05-16-25 Jamie S, DW is in compliance with city standards.
Piers/Caissons Inspection - Residential Passed 6/2/2025 6/2/2025 06/02/2025
Documents & Images
Date Uploaded File Type Document Name
10/23/2024 MN 114 License_Tax_Application
10/25/2024 Permit Codes Residential Plan Review
10/25/2024 Approved Plans APPROVED TRUSS LAYOUT
10/28/2024 Application Form Permit Application_1
10/29/2024 Permit Codes Residential Plan Review
10/29/2024 Plot Plan APPROVED PLOT PLAN
10/31/2024 Approved Plans APPROVED PLANS
10/31/2024 Permit Codes Residential Plan Review
11/14/2024 Permit DS Building Permit
11/14/2024 Receipt Receipt for transaction:2024-008976
11/26/2024 Letter INSPECTION SUMMARY
11/26/2024 Letter INSPECTION SUMMARY
12/16/2024 Letter INSPECTION SUMMARY
12/16/2024 Letter INSPECTION SUMMARY
12/16/2024 Letter INSPECTION SUMMARY
12/17/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
12/31/2024 Letter INSPECTION SUMMARY
12/31/2024 Letter INSPECTION SUMMARY
01/08/2025 Letter INSPECTION SUMMARY
01/23/2025 Letter INSPECTION SUMMARY
01/23/2025 Letter INSPECTION SUMMARY
01/29/2025 Letter INSPECTION SUMMARY
02/03/2025 Letter INSPECTION SUMMARY
02/10/2025 Receipt Receipt for transaction:2025-000865
02/11/2025 Letter INSPECTION SUMMARY
02/11/2025 Letter INSPECTION SUMMARY
03/04/2025 Letter INSPECTION SUMMARY
03/04/2025 Letter INSPECTION SUMMARY
03/04/2025 Letter INSPECTION SUMMARY
03/04/2025 Letter INSPECTION SUMMARY
03/07/2025 Letter INSPECTION SUMMARY
03/17/2025 Receipt Receipt for transaction:2025-001612
03/20/2025 Letter INSPECTION SUMMARY
03/20/2025 Letter INSPECTION SUMMARY
03/20/2025 Approved Plans APPROVED TRUSS PACKET
03/24/2025 Letter INSPECTION SUMMARY
03/25/2025 Letter INSPECTION SUMMARY
03/27/2025 Letter INSPECTION SUMMARY
05/09/2025 Letter INSPECTION SUMMARY
05/16/2025 Letter INSPECTION SUMMARY
06/02/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home