Summary
PRRES20242853
Building Permit - Residential
Certificate of Occupancy
DJ23 INVESTMENTS LLC
NEW SINGLE FAMILY
NEW HOUSE - ROOF TRUSSES - FINISHED AND UNFINISHED BASEMENT -
06/04/2024
06/11/2024
12/04/2024
10/17/2024
Locations
Contacts
Avital Homes, LLC, Address:7500 W 151st Street, #23100, Phone:(816) 914-7128  
DJ23 INVESTMENTS LLC, Address:7200 W 132ND ST  
Doug Jenson, Address:11010 Nora Dodge Dr, Phone:(816) 266-0685  
DOUG@APGKC.COM  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
CARUTHERS ELECTRICAL LLC, Address:30905 E TRUMAN RD, Phone:(816) 508-9050  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sanitary Sewer Development Fee $2,159.00 $2,159.00 Paid 06/11/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 06/11/2024
7232302-Residential License Tax Fee $1,022.72 $1,022.72 Paid 06/11/2024
8331401-Water Tap Fee $3,760.00 $3,760.00 Paid 06/11/2024
8350015-Water Meter Fee $680.46 $680.46 Paid 06/11/2024
9110078-Valuation Fee New Single Family $1,368.60 $1,368.60 Paid 06/11/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 09/26/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 10/16/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 6/17/2024 6/17/2024 06/17/2024
Miscellaneous Correction
Informational
06/17/2024
UFER is located along the south wall of the garage No exterior piers were installed at the time of this footing inspection
Erosion Control Inspection Residential Failed 6/26/2024 06/26/2024
Miscellaneous Correction
Corrective Action Required
06/26/2024
Most of erosion control is completed. More gravel is needed from the street to the foundation. Full erosion control measures are required until CofO
Underslab Plumbing Inspection - Residential Passed 6/26/2024 6/26/2024 06/26/2024
Sewer Service Inspection - R Passed 7/11/2024 07/11/2024
Erosion Control Inspection Residential Partial 7/11/2024 07/11/2024
Miscellaneous Correction
Resolved
07/11/2024
Most of erosion control is completed. More gravel is needed from the street to the foundation. Full erosion control measures are required until CofO
Miscellaneous Correction
Informational
07/11/2024
Full erosion control measures are in place and needs to be maintained until CofO
Water Service Inspection - R Failed 7/11/2024 07/11/2024
Miscellaneous Correction
Corrective Action Required
07/11/2024
PEX has need run from the foundation to about 20 feet out Okay to cover This is a partial pass only
Water Service Inspection - R Passed 7/12/2024 07/12/2024
Miscellaneous Correction
Resolved
07/12/2024
PEX has need run from the foundation to about 20 feet out Okay to cover This is a partial pass only
All Rough Inspection - Residential Not Ready 7/23/2024 7/23/2024 07/23/2024
Miscellaneous Correction
Corrective Action Required
07/23/2024
Nailing pattern is not present on exterior garage sheeting This was scheduled for a garage portal inspection only Not ready for inspection
Erosion Control Inspection Residential Partial 7/23/2024 07/23/2024
Miscellaneous Correction
Resolved
07/23/2024
Full erosion control measures are in place and needs to be maintained until CofO
Miscellaneous Correction
Informational
07/23/2024
Full erosion control measures are in place and needs to be maintained until CofO
All Rough Inspection - Residential Failed 7/25/2024 7/25/2024 07/25/2024
Miscellaneous Correction
Resolved
07/25/2024
Nailing pattern is not present on exterior garage sheeting This was scheduled for a garage portal inspection only Not ready for inspection
Miscellaneous Correction
Informational
07/25/2024
Garage portal inspection passed and is okay to cover. This is a partial pass only
Electrical Service Inspection Passed 8/8/2024 8/8/2024 08/08/2024
Gas Service Inspection - Residential Failed 8/8/2024 8/8/2024 08/08/2024
Misc
Corrective Action Required
08/08/2024
-Faulty pressure gauge. Install new gauge and re-pressurize
All Rough Inspection - Residential Failed 8/8/2024 8/8/2024 08/08/2024
Miscellaneous Correction
Informational
07/25/2024
Garage portal inspection passed and is okay to cover. This is a partial pass only
Misc
Corrective Action Required
08/08/2024
-Missing 2ea TJC-37 truss brackets (west side of garage) -Missing fire blocking at top plate in basement bedroom closet (east)
All Rough Inspection - Residential Passed 8/15/2024 8/15/2024 08/15/2024
Miscellaneous Correction
Resolved
08/15/2024
Garage portal inspection passed and is okay to cover. This is a partial pass only
Misc
Resolved
08/15/2024
-Missing 2ea TJC-37 truss brackets (west side of garage) -Missing fire blocking at top plate in basement bedroom closet (east)
Gas Service Inspection - Residential Passed 8/15/2024 8/15/2024 08/15/2024
Misc
Corrective Action Required
08/08/2024
-Faulty pressure gauge. Install new gauge and re-pressurize
Erosion Control Inspection Residential Partial 8/15/2024 08/15/2024
Miscellaneous Correction
Resolved
08/15/2024
Full erosion control measures are in place and needs to be maintained until CofO
Miscellaneous Correction
Informational
08/15/2024
Full erosion control measures are in place and needs to be maintained until CofO
Erosion Control Inspection Residential Partial 9/6/2024 09/06/2024
Miscellaneous Correction
Informational
08/15/2024
Full erosion control measures are in place and needs to be maintained until CofO
Driveway Inspection Failed 9/10/2024 9/10/2024 09/10/2024
Misc
Informational
09/10/2024
9-10-24 PS Driveway approach inspection failed, base aggregate not compacted, no plate compactor on site
Driveway Inspection Partial 9/10/2024 9/10/2024 09/10/2024
Misc
Informational
09/10/2024
9-10-24 PS Driveway approach inspection failed, base aggregate not compacted, no plate compactor on site 9-10-24 Dustin A, DW has been compacted approved to pour
Driveway Inspection Passed 9/17/2024 9/17/2024 09/16/2024
Misc
Informational
09/10/2024
9-10-24 PS Driveway approach inspection failed, base aggregate not compacted, no plate compactor on site 9-10-24 Dustin A, DW has been compacted approved to pour 9-16-24 Dustin A, Dw is poured to city specs, forms are pulled. Passed
Occupancy Inspection - Codes Residential Failed 10/4/2024 10/4/2024 10/04/2024
Miscellaneous Correction
Corrective Action Required
10/04/2024
1901 SW Hightown Occupancy Check whole house electrical for open ground Fire block gaps in garage sheet rock Basement stairs to platform does not have the code 36 inches of travel distance Electrical wires are hanging from the ceiling in the basement bathroom Sod, sump pump extension and splash pads are not installed Seal all exterior penetrations Electrical ground rod has been partially dug up Ground rod to bonding wire is broken Obtain irrigation permit for system already installed
Occupancy Inspection - Codes Residential Failed 10/9/2024 10/9/2024 10/09/2024
Miscellaneous Correction
Resolved
10/09/2024
1901 SW Hightown Occupancy Check whole house electrical for open ground Fire block gaps in garage sheet rock Basement stairs to platform does not have the code 36 inches of travel distance Electrical wires are hanging from the ceiling in the basement bathroom Sod, sump pump extension and splash pads are not installed Seal all exterior penetrations Electrical ground rod has been partially dug up Ground rod to bonding wire is broken Obtain irrigation permit for system already installed
Miscellaneous Correction
Corrective Action Required
10/09/2024
1901 SW Hightown Occupancy (2) Sod, sump pump extension and splash pads are not installed Seal all exterior penetrations Ground rod is not to code length from meter base
Occupancy Inspection - Codes Residential Ready for Temp CO 10/15/2024 10/15/2024 10/15/2024
Miscellaneous Correction
Corrective Action Required
10/09/2024
1901 SW Hightown Occupancy Sod, sump pump extension and splash pads are not installed
Erosion Control Inspection Residential Partial 10/15/2024 10/15/2024
Miscellaneous Correction
Informational
09/06/2024
Full erosion control measures are in place and needs to be maintained until CofO
Plot Plan Inspection Passed 10/17/2024 10/17/2024
Erosion Control Inspection Residential Passed 10/17/2024 10/17/2024
Miscellaneous Correction
Resolved
10/17/2024
Full erosion control measures are in place and needs to be maintained until CofO
Occupancy Inspection - Codes Residential Full C of O 10/17/2024 10/17/2024 10/17/2024
Miscellaneous Correction
Resolved
10/17/2024
1901 SW Hightown Occupancy Sod, sump pump extension and splash pads are not installed
Documents & Images
Date Uploaded File Type Document Name
06/04/2024 RS 110 License_Tax_Application 6_4_24
06/04/2024 110 SC - SERENADE - C3RF - 240604
06/04/2024 LOT 110 FINAL
06/05/2024 Permit Codes Residential Plan Review
06/07/2024 110 SC - SERENADE - C3RF - 240607
06/07/2024 Permit Codes Residential Plan Review
06/07/2024 LOT 110 CITY
06/07/2024 Plot Plan APPROVED PLOT PLAN
06/07/2024 Permit Codes Residential Plan Review
06/07/2024 Application Form RS 110 Permit Application Signed 6_4_24
06/10/2024 110 SC - SERENADE - C3RF - 240607- (2)
06/10/2024 Approved Plans APPROVED PLANS
06/11/2024 Permit Codes Residential Plan Review
06/11/2024 Permit DS Building Permit
06/11/2024 Receipt Receipt for transaction:2024-004651
06/17/2024 Letter INSPECTION SUMMARY
06/26/2024 Letter INSPECTION SUMMARY
06/26/2024 Letter INSPECTION SUMMARY
06/26/2024 Letter INSPECTION SUMMARY
07/11/2024 Letter INSPECTION SUMMARY
07/11/2024 Letter INSPECTION SUMMARY
07/11/2024 Letter INSPECTION SUMMARY
07/12/2024 Letter INSPECTION SUMMARY
07/23/2024 Letter INSPECTION SUMMARY
07/23/2024 Letter INSPECTION SUMMARY
07/25/2024 Letter INSPECTION SUMMARY
07/26/2024 240729 B5A Repair
08/08/2024 Letter INSPECTION SUMMARY
08/08/2024 Letter INSPECTION SUMMARY
08/15/2024 Letter INSPECTION SUMMARY
08/15/2024 Letter INSPECTION SUMMARY
08/15/2024 Letter INSPECTION SUMMARY
08/15/2024 Letter INSPECTION SUMMARY
08/15/2024 Letter INSPECTION SUMMARY
09/06/2024 Letter INSPECTION SUMMARY
09/10/2024 Letter INSPECTION SUMMARY
09/10/2024 Letter INSPECTION SUMMARY
09/16/2024 Letter INSPECTION SUMMARY
09/19/2024 2024_09_09_1901 SW Hightown_stoop_Sealed
09/26/2024 Receipt Receipt for transaction:2024-007960
10/04/2024 Letter INSPECTION SUMMARY
10/09/2024 Letter INSPECTION SUMMARY
10/15/2024 Letter INSPECTION SUMMARY
10/15/2024 Letter INSPECTION SUMMARY
10/16/2024 Certificate/License Codes Temporary Certificate of Occupancy
10/16/2024 Receipt Receipt for transaction:2024-008378
10/17/2024 Letter INSPECTION SUMMARY
10/17/2024 Letter INSPECTION SUMMARY
10/17/2024 Letter Field Certificate of Occupancy
10/17/2024 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home