Summary
PRRES20241619
Building Permit - Residential
Certificate of Occupancy
DJ23 INVESTMENTS LLC
NEW SINGLE FAMILY
NEW HOUSE. UNFINISHED BASEMENT. ROOF TRUSSES - DEFERRED.
04/03/2024
04/24/2024
10/13/2024
10/23/2024
Locations
Contacts
Avital Homes, LLC, Address:7500 W 151st Street, #23100, Phone:(816) 914-7128  
Doug Jenson, Address:11010 Nora Dodge Dr, Phone:(816) 266-0685  
DJ23 INVESTMENTS LLC, Address:7200 W 132ND ST  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
CARUTHERS ELECTRICAL LLC, Address:30905 E TRUMAN RD, Phone:(816) 508-9050  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
DOUG@APGKC.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Water Tap Fee $3,760.00 $3,760.00 Paid 04/24/2024
Water Meter Fee $680.46 $680.46 Paid 04/24/2024
Sanitary Sewer Development Fee $2,159.00 $2,159.00 Paid 04/24/2024
Right of Way Permit Fee $85.00 $85.00 Paid 04/24/2024
Residential Excise Tax Fee $1,022.72 $1,022.72 Paid 04/24/2024
Valuation Fee New Single Family $1,587.26 $1,587.26 Paid 04/24/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 07/19/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 07/19/2024
3rd and Subsequent Inspection Fee (Per Hour) $50.00 $50.00 Paid 07/19/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 10/17/2024
Outstanding Fees Amount Paid Owing Date Paid


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Partial 4/30/2024 04/30/2024
Miscellaneous Correction
Informational
04/30/2024
Full erosion control is in place and needs to be maintained until CofO
Footing Inspection - Residential Passed 4/30/2024 4/30/2024 04/30/2024
Miscellaneous Correction
Informational
04/30/2024
Ufer is located along the garage south wall There are no exterior piers on this footing inspection
Sewer Service Inspection - R Passed 5/14/2024 05/14/2024
Water Service Inspection - R Partial 5/15/2024 5/15/2024 05/15/2024
Miscellaneous Correction
Informational
05/15/2024
PEX has been installed from the foundation to about 20 feet out towards the street. This is a partial pass only and is okay to cover
Water Service Inspection - R Passed 5/16/2024 5/16/2024 05/16/2024
Miscellaneous Correction
Resolved
05/16/2024
PEX has been installed from the foundation to about 20 feet out towards the street. This is a partial pass only and is okay to cover
Underslab Plumbing Inspection - Residential Not Ready 5/17/2024 5/17/2024 05/17/2024
Miscellaneous Correction
Corrective Action Required
05/17/2024
Plumbing is still being installed. Not ready for inspection 05/17/2024. KBEARD 8:33am
Underslab Plumbing Inspection - Residential Not Ready 5/20/2024 5/20/2024 05/20/2024
Miscellaneous Correction
Resolved
05/20/2024
Plumbing is still being installed. Not ready for inspection 05/17/2024. KBEARD 8:33am
Miscellaneous Correction
Corrective Action Required
05/20/2024
-Proper and safe access must be provided to the foundation for inspection -No access is provided Walk your property before scheduling an inspection Not Ready. KBEARD 9:11am
Underslab Plumbing Inspection - Residential Passed 5/21/2024 5/21/2024 05/21/2024
Miscellaneous Correction
Resolved
05/21/2024
-Proper and safe access must be provided to the foundation for inspection -No access is provided Walk your property before scheduling an inspection Not Ready. KBEARD 9:11am
Erosion Control Inspection Residential Partial 6/4/2024 06/04/2024
Miscellaneous Correction
Resolved
06/04/2024
Full erosion control is in place and needs to be maintained until CofO
Miscellaneous Correction
Informational
06/04/2024
Full erosion control is in place and needs to be maintained until CofO
All Rough Inspection - Residential Failed 6/5/2024 6/5/2024 06/05/2024
Miscellaneous Correction
Corrective Action Required
06/05/2024
- Exterior sheeting is not nailed to both top plates - Exterior sheeting is not extended to both top plates - This inspection was for a garage portal framing only
All Rough Inspection - Residential Not Ready 6/7/2024 6/7/2024 06/07/2024
Miscellaneous Correction
Resolved
06/07/2024
- Exterior sheeting is not nailed to both top plates - Exterior sheeting is not extended to both top plates - This inspection was for a garage portal framing only
Miscellaneous Correction
Corrective Action Required
06/07/2024
House is not ready for an all rough inspection. M,E,P’s and roof are not complete Not ready
Erosion Control Inspection Residential Partial 06/10/2024
Miscellaneous Correction
Informational
06/04/2024
Full erosion control is in place and needs to be maintained until CofO
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
06/10/2024
6-10-24 Dustin A, EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Street needs to be cleaned
Erosion Control Inspection Residential Passed 6/13/2024 6/13/2024 06/12/2024
Miscellaneous Correction
Informational
06/10/2024
Full erosion control is in place and needs to be maintained until CofO
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
06/10/2024
6-10-24 Dustin A, EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Street needs to be cleaned 6-12-24 Dustin A, Street was cleaned up and erosion control up
All Rough Inspection - Residential Failed 6/14/2024 6/14/2024 06/14/2024
Miscellaneous Correction
Corrective Action Required
06/07/2024
House is not ready for an all rough inspection. M,E,P’s and roof are not complete Not ready
Misc
Informational
06/14/2024
This was a portal frame only inspection. PASSED 6/14/24 AF
Gas Service Inspection - Residential Passed 6/27/2024 6/27/2024 06/27/2024
Electrical Service Inspection Failed 6/27/2024 6/27/2024 06/27/2024
Miscellaneous Correction
Corrective Action Required
06/27/2024
Neutral is not connected to the bus bar in panel
Erosion Control Inspection Residential Partial 6/27/2024 06/27/2024
Miscellaneous Correction
Informational
06/27/2024
Full erosion control is in place and must be maintained until CofO
All Rough Inspection - Residential Failed 6/27/2024 6/27/2024 06/27/2024
Miscellaneous Correction
Resolved
06/27/2024
House is not ready for an all rough inspection. M,E,P’s and roof are not complete Not ready
Misc
Resolved
06/27/2024
This was a portal frame only inspection. PASSED 6/14/24 AF
Miscellaneous Correction
Corrective Action Required
06/27/2024
1805 SW Hightown. All rough - Electrical nail guards are needed throughout -Have plan designer address meaning of EC3, EC1 and load bearing option for roof A&C -Truss tie down screw is missing in bath 2 -Have plumber address the five studs drilled out for 1 1/2 waste line at kitchen exterior load bearing wall -Have engineer better address (3) 2x4 at dining room window -Primary bedroom door is missing the header -Address over bored 2x10 ceiling/floor joist in basement 3 inch waste line -Plans call for double joist under bath tub and kitchen island (missing) -Electrical neutral is not connected to the bus bar in the panel -Nail off exterior sheeting to code
All Rough Inspection - Residential Failed 7/1/2024 7/1/2024 07/01/2024
Miscellaneous Correction
Corrective Action Required
06/27/2024
1805 SW Hightown. All rough -Have plan designer address meaning of EC3, EC1 and load bearing option for roof A&C -Have engineer better address (3) 2x4 at dining room window -Plans call for double joist under bath tub (missing)
Electrical Service Inspection Passed 7/1/2024 7/1/2024 07/01/2024
Miscellaneous Correction
Resolved
07/01/2024
Neutral is not connected to the bus bar in panel
All Rough Inspection - Residential Passed 7/2/2024 7/2/2024 07/02/2024
Miscellaneous Correction
Resolved
07/02/2024
1805 SW Hightown. All rough -Have plan designer address meaning of EC3, EC1 and load bearing option for roof A&C -Have engineer better address (3) 2x4 at dining room window -Plans call for double joist under bath tub (missing)
Driveway Inspection Partial 8/6/2024 08/06/2024
Misc
Informational
08/06/2024
8-6-24 Dustin A, Dw is framed and compacted to city specs. Curb was missing a chunk. Enough that it needed to be replaced. Contractor cut out Curb that was damaged ( seam to seam) and meets pre pour specs. Approved to pour
Driveway Inspection Passed 8/13/2024 8/13/2024 08/13/2024
Misc
Informational
08/06/2024
8-6-24 Dustin A, Dw is framed and compacted to city specs. Curb was missing a chunk. Enough that it needed to be replaced. Contractor cut out Curb that was damaged ( seam to seam) and meets pre pour specs. Approved to pour 8-13-24 Dustin A, DW is poured to city specs. Passed
Erosion Control Inspection Residential Partial 8/16/2024 08/16/2024
Miscellaneous Correction
Informational
06/27/2024
Full erosion control is in place and must be maintained until CofO
Erosion Control Inspection Residential Partial 8/29/2024 08/29/2024
Miscellaneous Correction
Corrective Action Required
08/29/2024
Full erosion control measures are in place and must be maintained until CofO
Occupancy Inspection - Codes Residential Failed 8/29/2024 8/29/2024 08/29/2024
Miscellaneous Correction
Corrective Action Required
08/29/2024
1805 SW Hightown. Occupancy -Seal all sheet rock gaps for fire blocking in the garage -Basement escape well needs to have more gravel added so the bottom rung of the ladder to gravel is 18 inches or less -Water meter in the front yard appears to be to high for plot elevation -Sod and splash pads are not installed
Erosion Control Inspection Residential Partial 9/6/2024 09/06/2024
Miscellaneous Correction
Informational
08/16/2024
Full erosion control is in place and must be maintained until CofO
Occupancy Inspection - Codes Residential Failed 9/25/2024 9/25/2024 09/25/2024
Miscellaneous Correction
Resolved
09/25/2024
1805 SW Hightown. Occupancy -Seal all sheet rock gaps for fire blocking in the garage -Basement escape well needs to have more gravel added so the bottom rung of the ladder to gravel is 18 inches or less -Water meter in the front yard appears to be to high for plot elevation -Sod and splash pads are not installed
Miscellaneous Correction
Corrective Action Required
09/25/2024
1805 SW Hightown. Occupancy (2) Seal all sheet rock gaps for fire blocking in the garage Water meter in the front yard appears to be to high for plot elevation Sod and splash pads are not installed Seal all exterior penetrations Sump pump extension is not installed
Plot Plan Inspection Passed 9/25/2024 09/25/2024
Erosion Control Inspection Residential Partial 9/25/2024 09/25/2024
Miscellaneous Correction
Corrective Action Required
09/06/2024
Full erosion control measures are in place and must be maintained until CofO
Occupancy Inspection - Codes Residential Not Ready 10/1/2024 10/1/2024 10/01/2024
Miscellaneous Correction
Corrective Action Required
09/25/2024
1805 SW Hightown. Occupancy (2) Seal all sheet rock gaps for fire blocking in the garage Water meter in the front yard appears to be to high for plot elevation Sod and splash pads are not installed Seal all exterior penetrations Sump pump extension is not installed
Misc
Corrective Action Required
10/01/2024
1805 SW Hightown. Occupancy (2) Seal all sheet rock gaps for fire blocking in the garage Water meter in the front yard appears to be to high for plot elevation Sod and splash pads are not installed Seal all exterior penetrations Sump pump extension is not installed Front door was locked (No access) Not ready 10/01/24 KBEARD 10.00am
Erosion Control Inspection Residential Passed 10/9/2024 10/09/2024
Miscellaneous Correction
Resolved
10/09/2024
Full erosion control measures are in place and must be maintained until CofO
Occupancy Inspection - Codes Residential Failed 10/9/2024 10/9/2024 10/09/2024
Miscellaneous Correction
Resolved
10/09/2024
1805 SW Hightown. Occupancy (2) Seal all sheet rock gaps for fire blocking in the garage Water meter in the front yard appears to be to high for plot elevation Sod and splash pads are not installed Seal all exterior penetrations Sump pump extension is not installed
Miscellaneous Correction
Corrective Action Required
10/09/2024
Pay $75 fee associated with this permit
Occupancy Inspection - Codes Residential Full C of O 10/23/2024 10/23/2024 10/23/2024
Miscellaneous Correction
Resolved
10/23/2024
Pay $75 fee associated with this permit
Documents & Images
Date Uploaded File Type Document Name
04/03/2024 LOT 107 FINAL
04/13/2024 107 Reserve at Stoney Creek - Avalon - 041224
04/13/2024 RS 107 Permit Application Signed (1)
04/13/2024 RS 107 Tax Application Signed
04/16/2024 Permit Codes Residential Plan Review
04/23/2024 107 Reserve at Stoney Creek - Avalon - 041824
04/23/2024 1805 SW HIGHTOWN DR RESPONSE LETTER
04/23/2024 Approved Plans APPROVED PLANS
04/23/2024 Plot Plan APPROVED PLOT PLAN
04/23/2024 Permit Codes Residential Plan Review
04/24/2024 Permit DS Building Permit
04/24/2024 Receipt Receipt for transaction:2024-002637
04/30/2024 Letter INSPECTION SUMMARY
04/30/2024 Letter INSPECTION SUMMARY
05/14/2024 Letter INSPECTION SUMMARY
05/15/2024 Letter INSPECTION SUMMARY
05/16/2024 Letter INSPECTION SUMMARY
05/17/2024 Letter INSPECTION SUMMARY
05/20/2024 Letter INSPECTION SUMMARY
05/21/2024 Letter INSPECTION SUMMARY
06/04/2024 Letter INSPECTION SUMMARY
06/05/2024 Letter INSPECTION SUMMARY
06/07/2024 Letter INSPECTION SUMMARY
06/10/2024 Letter INSPECTION SUMMARY
06/10/2024 Letter INSPECTION SUMMARY
06/12/2024 Letter INSPECTION SUMMARY
06/13/2024 Engineer Report/Study TRUSS REPAIR E1
06/14/2024 Letter INSPECTION SUMMARY
06/19/2024 3RD Party Insp Report ENGINEER TRUSS REPAIR REPORT
06/27/2024 Letter INSPECTION SUMMARY
06/27/2024 Letter INSPECTION SUMMARY
06/27/2024 Letter INSPECTION SUMMARY
06/27/2024 Letter INSPECTION SUMMARY
07/01/2024 Letter INSPECTION SUMMARY
07/01/2024 Letter INSPECTION SUMMARY
07/01/2024 Engineer Report/Study ENGINEER ROUGH IN LETTER
07/02/2024 Letter INSPECTION SUMMARY
07/19/2024 Receipt Receipt for transaction:2024-005998
08/06/2024 Letter INSPECTION SUMMARY
08/13/2024 Letter INSPECTION SUMMARY
08/16/2024 Letter INSPECTION SUMMARY
08/29/2024 Letter INSPECTION SUMMARY
08/29/2024 Letter INSPECTION SUMMARY
09/06/2024 Letter INSPECTION SUMMARY
09/25/2024 Letter INSPECTION SUMMARY
09/25/2024 Letter INSPECTION SUMMARY
09/25/2024 Letter INSPECTION SUMMARY
10/01/2024 Letter INSPECTION SUMMARY
10/09/2024 Letter INSPECTION SUMMARY
10/09/2024 Letter INSPECTION SUMMARY
10/17/2024 Receipt Receipt for transaction:2024-008416
10/23/2024 Letter Codes Final Certificate of Occupancy
10/23/2024 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home