Summary
PRRES20240888
Building Permit - Residential
Certificate of Occupancy
KEVIN HIGDON CONSTRUCTION
NEW SINGLE FAMILY
NEW HOUSE. UNFINISHED BASEMENT. COVERED DECK. *Permit 20216538 for Footing, sewer, water, under slab inspections. Andrea Sessler 02/27/2024 4:56 PM *50% of original valuation fee was paid to renew expired permit # PRRES20216538 TRACY DEISTER 03/04/2024 11:14 AM
02/27/2024
03/04/2024
08/27/2024
Locations
Contacts
KEVIN HIGDON CONSTRUCTION, LLC, Address:P O BOX 847, Phone:(816) 524-9797  
KEVIN@HIGDONBUILDERS.COM  
KEVIN HIGDON CONSTRUCTION, Address:PO BOX 847, Phone:(816) 524-9797  
PRAIRIE CENTER PLUMBING HEATING & A/C, Address:242 N MARION, Phone:(913) 829-6263  
INTERSTATE CONSTRUCTION SERVICES, Address:1450 SE BROADWAY DR, Phone:(816) 524-9797  
PRAIRIE CENTER PLUMBING HEATING & A/C, Address:242 N MARION, Phone:(913) 829-6263  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 03/06/2024 03/04/2024
Tracy Deister
Plot Plan Review Approved 03/06/2024 03/04/2024
Tracy Deister
Fees
Paid Fees Amount Paid Owing Date Paid
Investigation Fee $695.62 $695.62 Paid 03/04/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Residential Partial 3/7/2024 3/7/2024 03/07/2024
Misc
Informational
03/07/2024
-Portal frame inspection only. PASSED
Piers/Caissons Inspection - Residential Passed 3/8/2024 03/08/2024
Miscellaneous Correction
Informational
03/08/2024
Back deck piers passed by a third party
Erosion Control Inspection Residential Partial 4/9/2024 04/09/2024
Miscellaneous Correction
Informational
04/09/2024
Full erosion control is in place and needs to be maintained until CofO
Gas Service Inspection - Residential Passed 4/17/2024 4/17/2024 04/17/2024
Electrical Service Inspection Passed 5/21/2024 5/21/2024 05/21/2024
All Rough Inspection - Residential Failed 5/21/2024 5/21/2024 05/21/2024
Misc
Resolved
05/21/2024
-Portal frame inspection only. PASSED
Miscellaneous Correction
Corrective Action Required
05/21/2024
Have revised house plans on site before rescheduling all rough
All Rough Inspection - Residential Failed 5/23/2024 5/23/2024 05/23/2024
Miscellaneous Correction
Resolved
05/23/2024
Have revised house plans on site before rescheduling all rough
Miscellaneous Correction
Corrective Action Required
05/23/2024
1833 SW Sage All rough ADDRESS NUMBERS ARE MISSING -5/8 inch anchor bolts are missing in the garage -Garage anchor bolts need to be located in the middle 1/3 of the sole plate -Garage anchor bolts needs to be installed 4-12 inches from the sole plate ends -Blocking is missing above the LVL in garage entry to main house -Seal penetrations in the HVAC chase above LVL in garage to house entry -Nails are missing in joist hanger located at the great room to stairs -Master bathroom toilet vent fan is not hooked up to flex vent pipe
Erosion Control Inspection Residential Partial 5/23/2024 05/23/2024
Miscellaneous Correction
Resolved
05/23/2024
Full erosion control is in place and needs to be maintained until CofO
Miscellaneous Correction
Informational
05/23/2024
Full erosion control is in place and needs to be maintained until CofO
All Rough Inspection - Residential Failed 5/28/2024 5/28/2024 05/28/2024
Miscellaneous Correction
Corrective Action Required
05/23/2024
**Remove blockings. Do not block the return air space above top landing of stair to basement -Master bathroom toilet vent fan is not hooked up to flex vent pipe **Tape connection of flex duct to bath fan **OK TO INSULATE
All Rough Inspection - Residential Passed 5/30/2024 5/30/2024 05/30/2024
Miscellaneous Correction
Resolved
05/30/2024
**Remove blockings. Do not block the return air space above top landing of stair to basement -Master bathroom toilet vent fan is not hooked up to flex vent pipe **Tape connection of flex duct to bath fan **OK TO INSULATE
Erosion Control Inspection Residential Failed 6/10/2024 06/10/2024
Miscellaneous Correction
Resolved
06/10/2024
Full erosion control is in place and needs to be maintained until CofO
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
06/10/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. -Silt fence is torn down and needs to be repaired or replaced -Lot weeds and or grass is about 3 feet in height and needs to be trimmed
Driveway Inspection Partial 7/18/2024 07/18/2024
Misc
Informational
07/18/2024
7-18-24 PS Driveway approach pre pour, forms in place and aggregate compacted, approved to pour
Erosion Control Inspection Residential Failed 7/24/2024 07/24/2024
DCM3 ESC REQUIRED 2 DAY
Resolved
07/24/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. -Silt fence is torn down and needs to be repaired or replaced -Lot weeds and or grass is about 3 feet in height and needs to be trimmed
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
07/24/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Silt fence has been removed from the front of the property. Remove gravel from street Full erosion control measures are required and must be maintained until CofO
Driveway Inspection Passed 7/25/2024 7/25/2024 07/25/2024
Misc
Informational
07/18/2024
7-18-24 PS Driveway approach pre pour, forms in place and aggregate compacted, approved to pour 7-25-24 PS Driveway approach meets LS specs
Plot Plan Inspection Passed 8/15/2024 08/15/2024
Erosion Control Inspection Residential Passed 8/26/2024 08/26/2024
DCM3 ESC REQUIRED 2 DAY
Resolved
08/26/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Silt fence has been removed from the front of the property. Remove gravel from street Full erosion control measures are required and must be maintained until CofO
Occupancy Inspection - Codes Residential Failed 8/26/2024 8/26/2024 08/26/2024
Miscellaneous Correction
Corrective Action Required
08/26/2024
1833 SW Sage Canyon. Occupancy •Street address numbers are not properly illuminated •Front office windows are less than 18 inches from the floor and needs to have safety glass installed •Install spark rings in kitchen backsplash for lights and receptacles •Garage to house self closing door does not fully shut and lock •Fire block gaps in garage sheet rock above overhead doors •Sprinkler receptacle needs to state it is non GFCI protected •Stairwell to the upper floor does not have the required 6’8” head clearance from the stair tread to the upper floor/ceiling. Current clearance is 6’6” •Seal exterior gas line to siding penetration •Sod to siding does not have the proper height clearance
Occupancy Inspection - Codes Residential Failed 8/26/2024 08/26/2024
Miscellaneous Correction
Corrective Action Required
08/26/2024
1833 SW Sage Canyon. Occupancy •Street address numbers are not properly illuminated •Front office windows are less than 18 inches from the floor and needs to have safety glass installed •Install spark rings in kitchen backsplash for lights and receptacles •Garage to house self closing door does not fully shut and lock •Fire block gaps in garage sheet rock above overhead doors •Sprinkler receptacle needs to state it is non GFCI protected •Stairwell to the upper floor does not have the required 6’8” head clearance from the stair tread to the upper floor/ceiling. Current clearance is 6’6” •Seal exterior gas line to siding penetration •Sod to siding does not have the proper height clearance
Occupancy Inspection - Codes Residential Full C of O 8/27/2024 8/27/2024 08/27/2024
Documents & Images
Date Uploaded File Type Document Name
02/27/2024 Application Form APPLICATION
02/27/2024 Plot Plan APPROVED PLOT PLAN
02/27/2024 Permit Codes Residential Plan Review
03/04/2024 Approved Plans APPROVED REVISED PLANS
03/04/2024 Permit DS Building Permit
03/04/2024 Receipt Receipt for transaction:2024-001309
03/07/2024 Letter INSPECTION SUMMARY
03/08/2024 Final_2024_03_04_DPier_LSMO_FECO
03/08/2024 Letter INSPECTION SUMMARY
04/09/2024 Letter INSPECTION SUMMARY
04/17/2024 Letter INSPECTION SUMMARY
05/21/2024 Letter INSPECTION SUMMARY
05/21/2024 Letter INSPECTION SUMMARY
05/23/2024 Letter INSPECTION SUMMARY
05/23/2024 Letter INSPECTION SUMMARY
05/28/2024 Letter INSPECTION SUMMARY
05/30/2024 Letter INSPECTION SUMMARY
06/10/2024 Letter INSPECTION SUMMARY
07/18/2024 Letter INSPECTION SUMMARY
07/24/2024 Letter INSPECTION SUMMARY
07/25/2024 Letter INSPECTION SUMMARY
08/14/2024 Plot Plan APPROVED AS BUILT PLOT PLAN
08/15/2024 Letter INSPECTION SUMMARY
08/26/2024 Letter INSPECTION SUMMARY
08/26/2024 Letter INSPECTION SUMMARY
08/26/2024 Letter INSPECTION SUMMARY
08/27/2024 Letter INSPECTION SUMMARY (Occupancy Inspection - Codes Residential)
08/27/2024 Letter Field Certificate of Occupancy
08/27/2024 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home