Summary
PRRES20220428
Building Permit - Residential
Certificate of Occupancy
CLAYTON PROPERTIES GROUP INC
NEW SINGLE FAMILY
NEW SPLIT HOUSE. UNFINISHED BASEMENT. UNCOVERED DECK. ROOF TRUSSES.
02/02/2022
02/08/2022
09/07/2023
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
CLAYTON PROPERTIES GROUP INC, Address:120 SE 30TH ST  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
TAYLOR@CLOVERANDHIVE.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $450.00 $450.00 Paid 02/08/2022
8331401-Water Tap Fee $3,655.00 $3,655.00 Paid 02/08/2022
8350015-Water Meter Fee $479.24 $479.24 Paid 02/08/2022
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 02/08/2022
7232302-Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 02/08/2022
9110078-Valuation Fee New Single Family $953.77 $953.77 Paid 02/08/2022
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 07/03/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 3/8/2022 3/8/2022 03/08/2022
Misc
Corrective Action Required
03/08/2022
APPROVED PER DAVID P AINSWORTH 3/1/22
Underslab Plumbing Inspection - Residential Failed 3/30/2022 3/30/2022 03/30/2022
Miscellaneous Correction
Corrective Action Required
03/30/2022
UNDERSLAB PLUMBING WATER COVERED RECALL WHEN VISIABLE
Underslab Plumbing Inspection - Residential Passed 4/6/2022 4/6/2022 04/06/2022
Miscellaneous Correction
Resolved
04/06/2022
Sewer Service Inspection - R Passed 6/7/2022 (11:00) 6/7/2022 06/07/2022
Water Service Inspection - R Passed 6/14/2022 06/14/2022
Electrical Service Inspection Passed 12/15/2022 12/15/2022 12/15/2022
Gas Service Inspection - Residential Failed 12/15/2022 12/15/2022 12/15/2022
Misc
Corrective Action Required
12/15/2022
-min 10 psi pressure at gas service
All Rough Inspection - Residential Failed 12/15/2022 12/15/2022 12/15/2022
Misc
Corrective Action Required
12/15/2022
-maintain gravel filter on drive -fireblock vertical to horizontal at furred down soffit garage -fireblock plumbing fur out at garage wall -provide joist hanger at joist to header at basement den -nail off all floor joists at basement den -top plate corner lap at front entry -nail stud shoes master vanity -seal all plate penetrations 2nd floor -12” oc nailing all abutting corners -provide (4) 2x4 stud pack at trpl lvl bearing beneath 1st floor rim joist to support load at foundation -repair B2 truss per engineer letter -min 10 psi pressure at gas service
Gas Service Inspection - Residential Passed 12/16/2022 12/16/2022 12/16/2022
Misc
Resolved
12/16/2022
-min 10 psi pressure at gas service
All Rough Inspection - Residential Passed 12/19/2022 12/19/2022 12/19/2022
Misc
Resolved
12/19/2022
Driveway Inspection Failed 1/26/2023 1/26/2023 01/26/2023
Misc
Corrective Action Required
01/26/2023
1-26-23 PS Forms in place and aggregate has been compacted however subgrade is below freezing and not approved to pour. Inspection rescheduled for tomorrow morning to check subgrade temps.
Sidewalk Inspection Failed 1/26/2023 1/26/2023 01/26/2023
Misc
Corrective Action Required
01/26/2023
1-26-23 PS Forms in place and aggregate has been compacted. However, subgrade is below freezing and not approved to pour. Inspection rescheduled for tomorrow morning to check subgrade temps.
Driveway Inspection Partial 1/27/2023 1/27/2023 01/27/2023
Misc
Corrective Action Required
01/26/2023
1-26-23 PS Forms in place and aggregate has been compacted however subgrade is below freezing and not approved to pour. Inspection rescheduled for tomorrow morning to check subgrade temps. 1-27-23 PS Subgrade temp above freezing, ok to pour
Sidewalk Inspection Partial 1/27/2023 1/27/2023 01/27/2023
Misc
Corrective Action Required
01/26/2023
1-26-23 PS Forms in place and aggregate has been compacted. However, subgrade is below freezing and not approved to pour. Inspection rescheduled for tomorrow morning to check subgrade temps. 1-27-23 PS Subgrade temp above freezing, ok to pour
Driveway Inspection Passed 2/10/2023 2/10/2023 02/06/2023
Misc
Corrective Action Required
01/27/2023
1-26-23 PS Forms in place and aggregate has been compacted however subgrade is below freezing and not approved to pour. Inspection rescheduled for tomorrow morning to check subgrade temps. 1-27-23 PS Subgrade temp above freezing, ok to pour 2-6-23 PS Driveway meets LS and ADA specifications
Sidewalk Inspection Passed 2/10/2023 2/10/2023 02/06/2023
Misc
Corrective Action Required
01/27/2023
1-26-23 PS Forms in place and aggregate has been compacted. However, subgrade is below freezing and not approved to pour. Inspection rescheduled for tomorrow morning to check subgrade temps. 1-27-23 PS Subgrade temp above freezing, ok to pour 2-6-23 PS Sidewalk meets LS and ADA specifications
Occupancy Inspection - Codes Residential Not Ready 6/29/2023 6/30/2023 06/30/2023
Miscellaneous Correction
Corrective Action Required
06/30/2023
Address numbers are not posted on the residence. This is the second day they are not installed. I talked to the builder on 06/29/23 and told him I would reschedule inspections for today. Occupancy and or temporary occupancy can not be obtained until address numbers are installed. Time 8:08AM, 06/30/2023 KBEARD
Occupancy Inspection - Codes Residential Failed 7/3/2023 7/3/2023 07/03/2023
Miscellaneous Correction
Resolved
07/03/2023
Address numbers are not posted on the residence. This is the second day they are not installed. I talked to the builder on 06/29/23 and told him I would reschedule inspections for today. Occupancy and or temporary occupancy can not be obtained until address numbers are installed. Time 8:08AM, 06/30/2023 KBEARD
Miscellaneous Correction
Corrective Action Required
07/03/2023
- address numbers are above light and will not illuminate correctly - Exterior garage lights need to be sealed along the top - Kitchen backsplash electrical plugs need spark rings installed - Basement bathroom needs a electrical outlet within 3 feet of the sink - Handrail in basement is not installed - Gas line needs to be bonded - Seal boards at ceiling in interior garage - Sod splash pads are not installed - Exterior penetrations need to be sealed - Slump pump drain needs to extend 36 inches from foundation
Occupancy Inspection - Codes Residential Failed 7/6/2023 7/6/2023 07/06/2023
Miscellaneous Correction
Corrective Action Required
07/03/2023
- Sod splash pads are not installed - Exterior penetrations need to be sealed - Slump pump drain needs to extend 36 inches from foundation - Final grading is not completed 07/07/2023 - Since the first occupancy inspection a door seal has been placed in the garage to house door and will not allow the self closing hinge to work properly and shut correctly. - to obtain a TCO, the garage to house door must be able to fully shut and close correctly
Occupancy Inspection - Codes Residential Temporary C of O 7/7/2023 7/7/2023 07/07/2023
Miscellaneous Correction
Informational
07/07/2023
- Sod needs to be completed - Final grading is not completed 07/07/2023
Erosion Control Inspection Residential Passed 7/19/2023 07/19/2023
Occupancy Inspection - Codes Residential Failed 7/19/2023 7/19/2023 07/19/2023
Miscellaneous Correction
Corrective Action Required
07/19/2023
-Grade at back of house does not have proper slope -Must have min 6" in first 10' away from foundation for proper drainage
Plot Plan Inspection Failed 7/19/2023 07/19/2023
Misc
Corrective Action Required
07/19/2023
-Grade at back of house does not have proper slope -Must have min 6" in first 10' away from foundation for proper drainage
Occupancy Inspection - Codes Residential Temporary C of O 8/7/2023 08/07/2023
Miscellaneous Correction
Corrective Action Required
07/19/2023
-Grade at back of house does not have proper slope -Must have min 6" in first 10' away from foundation for proper drainage
Plot Plan Inspection Passed 9/7/2023 09/07/2023
Misc
Resolved
09/07/2023
-Grade at back of house does not have proper slope -Must have min 6" in first 10' away from foundation for proper drainage
Occupancy Inspection - Codes Residential Full C of O 9/7/2023 09/07/2023
Miscellaneous Correction
Resolved
09/07/2023
-Grade at back of house does not have proper slope -Must have min 6" in first 10' away from foundation for proper drainage
Documents & Images
Date Uploaded File Type Document Name
02/02/2022 CB #142 - PERMIT APPLICATION
02/04/2022 Approved Plans APPROVED TRUSS PACKAGE
02/04/2022 Approved Plans APPROVED TRUSS LAYOUT
02/04/2022 Permit Codes Residential Plan Review
02/08/2022 Permit Codes Residential Plan Review
02/08/2022 Permit DS Building Permit
02/08/2022 Receipt Receipt for transaction:2022-000690
02/23/2022 Plot Plan APPROVED PLOT PLAN
02/23/2022 Approved Plans APPROVED DRAWINGS
03/07/2022 M L Crose 3541 SE Corbin Dr LSMO Cobey Creek Lot 142 Clayton Permit 2022-0428 Footing Inspection Report 3-1-22
03/08/2022 Letter INSPECTION SUMMARY
03/30/2022 Letter INSPECTION SUMMARY
04/06/2022 Letter INSPECTION SUMMARY
06/07/2022 Letter INSPECTION SUMMARY
06/14/2022 Letter INSPECTION SUMMARY
12/02/2022 Approved Plans APPROVED TRUSS REPAIR
12/02/2022 Approved Plans APPROVED TRUSS REPAIR
12/02/2022 Approved Plans APPROVED TRUSS REPAIR
12/02/2022 Approved Plans APPROVED TRUSS REPAIR
12/12/2022 142 cobey creek truss inspection letter- signed
12/15/2022 Letter INSPECTION SUMMARY
12/15/2022 Letter INSPECTION SUMMARY
12/15/2022 Letter INSPECTION SUMMARY
12/16/2022 Letter INSPECTION SUMMARY
12/19/2022 Letter INSPECTION SUMMARY
01/26/2023 Letter INSPECTION SUMMARY
01/26/2023 Letter INSPECTION SUMMARY
01/27/2023 Letter INSPECTION SUMMARY
01/27/2023 Letter INSPECTION SUMMARY
02/06/2023 Letter INSPECTION SUMMARY
02/06/2023 Letter INSPECTION SUMMARY
06/26/2023 Letter Codes 140 Day Letter
06/30/2023 Letter INSPECTION SUMMARY
06/30/2023 Letter Codes 140 Day Letter
07/03/2023 Receipt Receipt for transaction:2023-005114
07/03/2023 Letter INSPECTION SUMMARY
07/06/2023 Letter INSPECTION SUMMARY
07/07/2023 Certificate/License Codes Temporary Certificate of Occupancy
07/19/2023 Letter INSPECTION SUMMARY
07/19/2023 Letter INSPECTION SUMMARY
07/19/2023 Letter INSPECTION SUMMARY
07/19/2023 Letter INSPECTION SUMMARY
08/07/2023 Certificate/License Codes Temporary Certificate of Occupancy
09/07/2023 Letter INSPECTION SUMMARY
09/07/2023 Letter Codes Final Certificate of Occupancy
09/07/2023 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home