Permit Application Status

PRRES20214577


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20214577
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE. COVERED DECK. FINISHED BASEMENT. FINISHED BASEMENT UPDATED PLANS Andrea Sessler 09/27/2021 4:23 PM
09/01/2021
09/09/2021
03/02/2022
11/17/2022
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
LOREN@SUMMITHOMESKC.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $450.00 $450.00 Paid 09/09/2021
Water Tap Fee $3,655.00 $3,655.00 Paid 09/09/2021
Water Meter Fee $479.24 $479.24 Paid 09/09/2021
Right of Way Permit Fee $85.00 $85.00 Paid 09/09/2021
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 09/09/2021
Valuation Fee New Single Family $1,119.32 $1,119.32 Paid 09/09/2021
3rd and Subsequent Inspection Fee (Per Hour) $75.00 $75.00 Paid 11/11/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 9/28/2021 9/28/2021 09/28/2021
Misc
Informational
09/28/2021
APPROVED PER BRADLEY HUXOL 9/24/21
Sewer Service Inspection - R Passed 11/1/2021 (8:45) 11/1/2021 11/01/2021
Water Service Inspection - R Passed 11/3/2021 (9:45) 11/3/2021 11/03/2021
Erosion Control Inspection Residential Failed 11/3/2021 11/3/2021 11/03/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
11/03/2021
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Erosion Control Inspection Residential Failed 12/6/2021 12/06/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
11/03/2021
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
DCM5 ESC INSP DENIED
Corrective Action Required
12/06/2021
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION.
Underslab Plumbing Inspection - Residential Failed 12/6/2021 12/6/2021 12/06/2021
Misc
Corrective Action Required
12/06/2021
EROSION CONTROL NEEDS TO BE IN COMPLIANCE BEFORE INSPECTION CAN BE PERFORMED.
Underslab Plumbing Inspection - Residential Passed 12/9/2021 12/9/2021 12/09/2021
Misc
Resolved
12/09/2021
EROSION CONTROL NEEDS TO BE IN COMPLIANCE BEFORE INSPECTION CAN BE PERFORMED.
Gas Service Inspection - Residential Passed 6/22/2022 6/22/2022 06/22/2022
Electrical Service Inspection Passed 6/22/2022 6/22/2022 06/22/2022
All Rough Inspection - Residential Failed 6/22/2022 6/22/2022 06/22/2022
Misc
Corrective Action Required
06/22/2022
-solid block sheathing breaks in garage -truss screws to be installed per manufacture specifications throughout -attic access in garage -seal top plate penetrations in laundry -address cspf at dining and master not framed correctly -top plate penetration in master -fire block hvac chase in master closet -support ridge beam at both ends above front patio to plans -seal gaps in fireblocking at furr down ends in basement -vertical to horizontal fire blocking every 10’ -fire block into furr down near wall bar -address over notched wall studs throughout garage -anchor bolts to be in the middle 1/3 of sill plate in basement -top plate penetration in bath 3 -fire block dead space to ceiling space and furr down in basement bath -solid blocking under kitchen island per plans -fire block furr out wall to ceiling space in bed 4 -add support to floor joists above for furr down in basement -truss hangers to plans
All Rough Inspection - Residential Failed 7/1/2022 7/1/2022 07/01/2022
Misc
Corrective Action Required
06/22/2022
-truss screws to be installed per manufacture specifications throughout -seal gaps in fireblocking at furr down ends in basement (frame around beam and fireblock S wall) -vertical to horizontal fire blocking every 10’ (missing and penetrations) -fire block into furr down near wall bar -anchor bolts to be in the middle 1/3 of sill plate in basement -top plate penetration in bath 3 -fire block dead space to ceiling space and furr down in basement bath 1 -fire block furr out wall to ceiling space in bed 4 (See furr down ) -truss hangers to plans incorrect hanger sul26
All Rough Inspection - Residential Failed 7/7/2022 7/7/2022 07/07/2022
Misc
Corrective Action Required
07/01/2022
-vertical to horizontal fire blocking every 10’ (missing and penetrations) -SEAL GAP AT “STORAGE BEHIND BAR, STILL MISSING AT REC ROOM AND BED 4 -anchor bolts to be in the middle 1/3 of sill plate in basement-TIGHTEN NUTS -top plate penetration in bath 3-SEE PEX LINE AT TOILET AND HOT WATER PEX AT VANITY -fire block furr out wall to ceiling space in bed 4-SEAL PENETRATION AT NM BY ENTRY DOOR -COMPLETE BATH EXHAUST IN BED 4 -truss hangers to plans incorrect hanger sul26-SEE HIP TRUSS CJ2
All Rough Inspection - Residential Failed 7/11/2022 7/11/2022 07/11/2022
Misc
Corrective Action Required
07/07/2022
-seal dwv penetration into furr down in basement bath -fire block furr out wall to ceiling space in bed 4-SEAL PENETRATION AT NM BY entryway -truss hangers to plans incorrect hanger sul26-SEE HIP TRUSS CJ2
All Rough Inspection - Residential Passed 7/12/2022 7/12/2022 07/12/2022
Misc
Resolved
07/12/2022
-seal dwv penetration into furr down in basement bath -fire block furr out wall to ceiling space in bed 4-SEAL PENETRATION AT NM BY entryway -truss hangers to plans incorrect hanger sul26-SEE HIP TRUSS CJ2
Driveway Inspection Partial 8/8/2022 8/8/2022 08/08/2022
Misc
Informational
08/08/2022
8-8-22 RH. Driveway Forms were up and aggregate was placed and compacted.
Sidewalk Inspection Partial 8/8/2022 08/08/2022
Misc
Informational
08/08/2022
8-8-22 RH. Sidewalk forms were up and aggregate placed and compacted.
Sidewalk Inspection Partial 8/8/2022 8/8/2022 08/08/2022
Misc
Informational
08/08/2022
8-8-22 RH. Sidewalk forms were up and aggregate was placed and compacted.
Driveway Inspection Passed 8/15/2022 8/15/2022 08/15/2022
Misc
Informational
08/08/2022
8-8-22 RH. Driveway Forms were up and aggregate was placed and compacted. 8-15-22 RH. Driveway meets LS and ADA specification.
Sidewalk Inspection Passed 8/15/2022 8/15/2022 08/15/2022
Misc
Informational
08/08/2022
8-8-22 RH. Sidewalk forms were up and aggregate placed and compacted. 8-15-22 RH. Sidewalk meets LS and ADA specification.
Plot Plan Inspection Failed 9/15/2022 09/15/2022
Misc
Corrective Action Required
09/15/2022
uncover covered manhole ensure proper fall at rear of lot
Piers/Caissons Inspection - Residential Passed 11/10/2022 11/10/2022
Plot Plan Inspection Passed 11/10/2022 11/10/2022
Misc
Resolved
11/10/2022
uncover covered manhole ensure proper fall at rear of lot
Erosion Control Inspection Residential Failed 11/10/2022 11/10/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
11/10/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
DCM5 ESC INSP DENIED
Resolved
11/10/2022
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION.
Misc
Corrective Action Required
11/10/2022
clean driveway and sidewalk
Occupancy Inspection - Codes Residential Failed 11/10/2022 11/10/2022 11/10/2022
Misc
Corrective Action Required
11/10/2022
-clean mud and dirt from driveway and sidewalk -pay all fees -provide code compliant access for Jacuzzi tub motor in master -cover plate for outlet in master toilet room -splash blocks and sump pump discharge to extend 36” from foundation
Erosion Control Inspection Residential Passed 11/17/2022 11/17/2022
Misc
Resolved
11/17/2022
clean driveway and sidewalk
Occupancy Inspection - Codes Residential Full C of O 11/17/2022 11/17/2022 11/17/2022
Misc
Resolved
11/17/2022
-provide code compliant access for Jacuzzi tub motor in master -cover plate for outlet in master toilet room -splash blocks and sump pump discharge to extend 36” from foundation
Documents & Images
Date Uploaded File Type Document Name
09/01/2021 HT #156 - PERMIT APP
09/02/2021 Approved Plans APPROVED TRUSS LAYOUT
09/02/2021 Approved Plans APPROVED TRUSS PACKAGE
09/03/2021 Permit Codes Residential Plan Review
09/09/2021 Plot Plan APPROVED PLOT PLAN
09/09/2021 Permit Codes Residential Plan Review
09/09/2021 Permit DS Building Permit
09/09/2021 Receipt Receipt for transaction:2021-007237
09/27/2021 156 Hawthorne Ridge FTNG
09/27/2021 Approved Plans APPROVED DRAWINGS
09/27/2021 Approved Plans APPROVED BASEMENT PLANS
09/28/2021 Letter INSPECTION SUMMARY
11/01/2021 Letter INSPECTION SUMMARY
11/03/2021 Letter INSPECTION SUMMARY
11/03/2021 Letter INSPECTION SUMMARY
12/06/2021 Letter INSPECTION SUMMARY
12/06/2021 Letter INSPECTION SUMMARY
12/09/2021 Letter INSPECTION SUMMARY
12/13/2021 Letter INSPECTION SUMMARY
12/13/2021 Letter INSPECTION SUMMARY
04/28/2022 Letter Codes 140 Day Letter
06/07/2022 Letter Codes 180 Day Letter
06/22/2022 Letter INSPECTION SUMMARY
06/22/2022 Letter INSPECTION SUMMARY
06/22/2022 Letter INSPECTION SUMMARY
07/01/2022 Letter INSPECTION SUMMARY
07/07/2022 Letter INSPECTION SUMMARY
07/11/2022 Letter INSPECTION SUMMARY
07/12/2022 Letter INSPECTION SUMMARY
08/08/2022 Letter INSPECTION SUMMARY
08/08/2022 Letter INSPECTION SUMMARY
08/08/2022 Letter INSPECTION SUMMARY
08/15/2022 Letter INSPECTION SUMMARY
08/15/2022 Letter INSPECTION SUMMARY
09/14/2022 Plot Plan APPROVED AS BUILT PLOT PLAN
09/15/2022 Letter INSPECTION SUMMARY
11/10/2022 Letter INSPECTION SUMMARY
11/10/2022 Letter INSPECTION SUMMARY
11/10/2022 Letter INSPECTION SUMMARY
11/10/2022 Letter INSPECTION SUMMARY
11/11/2022 Receipt Receipt for transaction:2022-008874
11/17/2022 Letter INSPECTION SUMMARY
11/17/2022 Letter Field Certificate of Occupancy
11/17/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home