Summary
PRRES20212841
Building Permit - Residential
Certificate of Occupancy
CMH PARKS INC
NEW SINGLE FAMILY
NEW HOUSE - FINISHED BASEMENT - COVERED DECK STOP WORK ORDER generated on 09/01/2021 12:00 AM by username 'Patrick Schonfeldt'. STOP WORK ORDER removed on 09/02/2021 12:00 AM by username 'Patrick Schonfeldt'.
06/03/2021
06/09/2021
12/01/2021
01/11/2023
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
CMH PARKS INC, Address:5000 CLAYTON RD  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
AJ@SUMMITHOMESKC.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,057.76 $1,057.76 Paid 06/09/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 06/09/2021
7232302-Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 06/09/2021
8331504-EFHB Middle Big Creek, Full $468.72 $468.72 Paid 06/09/2021
8331507-Sewer Connection Fee $420.00 $420.00 Paid 06/09/2021
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 06/09/2021
8350015-Water Meter Fee $455.54 $455.54 Paid 06/09/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 11/14/2022
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 11/14/2022
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 11/14/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Residential Failed 9/1/2021 9/1/2021 09/01/2021
Misc
Corrective Action Required
09/01/2021
INSPECTION DENIED FOOTING POURED WITHOUT INSPECTION, ENGINEER REPORT REQUIRED TO BE SUBMITTED TO PERMIT WITHIN 48 HOURS OF INSPECTION
Footing Inspection - Residential Failed - Stop Work 9/1/2021 9/1/2021 09/01/2021
Misc
Corrective Action Required
09/01/2021
INSPECTION DENIED FOOTING POURED WITHOUT INSPECTION, ENGINEER REPORT REQUIRED TO BE SUBMITTED TO PERMIT WITHIN 48 HOURS OF INSPECTION
Footing Inspection - Residential Passed 9/2/2021 9/2/2021 09/02/2021
Misc
Informational
09/02/2021
APPROVED PER BRADLEY HUXOL 7/29/21
Underslab Plumbing Inspection - Residential Failed 9/3/2021 9/3/2021 09/03/2021
Misc
Corrective Action Required
09/01/2021
-POST ADDRESS -UNABLE TO INSPECT COMPLETE DWV DUE TO COVER FROM MUD/WATER, RESCHEDULE WHEN CONDITIONS ALLOW -SET INTERIOR DRAIN TILE -ADDRESS CAPPED WYE FITTING BENEATH UNDERSLAB
Underslab Plumbing Inspection - Residential Not Ready 9/14/2021 9/14/2021 09/14/2021
Misc
Corrective Action Required
09/03/2021
-POST ADDRESS -UNABLE TO INSPECT COMPLETE DWV DUE TO MUD COVER, UNCOVER DWV FOR INSPECTION -ADDRESS CAPPED WYE FITTING BENEATH UNDERSLAB
Underslab Plumbing Inspection - Residential Not Ready 9/20/2021 9/20/2021 09/20/2021
Misc
Corrective Action Required
09/14/2021
-UNABLE TO INSPECT COMPLETE DWV DUE TO MUD COVER, UNCOVER DWV FOR INSPECTION - SEE WASTE LINE FROM WYE CONNECTOR TO DRAIN TO 4" CLEANOUT, UNABLE TO INSPECT WASTE LINES WITH MUD COVER
Underslab Plumbing Inspection - Residential Failed 9/23/2021 9/23/2021 09/23/2021
Misc
Corrective Action Required
09/20/2021
-UNABLE TO INSPECT COMPLETE DWV DUE TO MUD COVER, UNCOVER DWV FOR INSPECTION - SEE WASTE LINE FROM WYE CONNECTOR TO DRAIN TO 4" CLEANOUT, UNABLE TO INSPECT WASTE LINES WITH MUD COVER
Underslab Plumbing Inspection - Residential Passed 9/27/2021 9/27/2021 09/27/2021
Misc
Resolved
09/27/2021
-UNABLE TO INSPECT COMPLETE DWV DUE TO MUD COVER, UNCOVER DWV FOR INSPECTION - SEE WASTE LINE FROM WYE CONNECTOR TO DRAIN TO 4" CLEANOUT, UNABLE TO INSPECT WASTE LINES WITH MUD COVER
Sewer Service Inspection - R Passed 10/14/2021 10/14/2021
Water Service Inspection - R Passed 10/15/2021 (1:00) 10/15/2021 10/15/2021
Erosion Control Inspection Residential Failed 10/15/2021 10/15/2021 10/15/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
10/15/2021
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
All Rough Inspection - Residential Not Ready 5/27/2022 5/27/2022 05/27/2022
Misc
Corrective Action Required
05/27/2022
INSPECTION DENIED NO CITY STAMPED PLANS ON SITE AT TIME OF INSPECTION
Electrical Service Inspection Failed 5/27/2022 5/27/2022 05/27/2022
Misc
Corrective Action Required
05/27/2022
INSPECTION DENIED NO CITY STAMPED PLANS ON SITE AT TIME OF INSPECTION
Gas Service Inspection - Residential Failed 5/27/2022 5/27/2022 05/27/2022
Misc
Corrective Action Required
05/27/2022
INSPECTION DENIED NO CITY STAMPED PLANS ON SITE AT TIME OF INSPECTION
Erosion Control Inspection Residential Partial 05/27/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
05/27/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Electrical Service Inspection Passed 6/1/2022 6/1/2022 06/01/2022
Misc
Resolved
06/01/2022
INSPECTION DENIED NO CITY STAMPED PLANS ON SITE AT TIME OF INSPECTION
Gas Service Inspection - Residential Passed 6/1/2022 6/1/2022 06/01/2022
Misc
Resolved
06/01/2022
INSPECTION DENIED NO CITY STAMPED PLANS ON SITE AT TIME OF INSPECTION
All Rough Inspection - Residential Failed 6/1/2022 6/1/2022 06/01/2022
Misc
Corrective Action Required
05/27/2022
-provide anchor bolt right side single car bay portal sill plate -provide stud shoe at SE cable stud bore garage -address top plate corner lap connection required by code at NE garage corner -seal all top plate penetrations at garage wall -seal HVAC plate penetration laundry -provide bocca protection plate at top plate kitchen -seal gas line floor penetration at fireplace -protect gas line entry at fireplace casing per manufacturer installation instructions -unable to inspect covered porch framing with lid installed -provide bearing and lateral restraint at ridge ends covered porch -provide full bearing for covered porch beam at front bed wall -solid shim all trimmer studs cut short of headers throughout -provide H2.5 clips at ends and full bearing for C3 truss at front bedroom -seal top plate penetration at front bedroom -support bath exhaust duct master bath -provide proper slope for plumbing vents across trusses in attic -provide protection plate DWV stud master closet -extend WSP panel to interior and exterior side of wall along great room/kitchen wall per plans -address D1 girder truss, per plans the D1 girder truss shows the B and A trusses attached to girder with truss hangers and does not show ledger or fur out face nailed to girder with truss hangers attached to ledgers -provide bocca protection plate top plate DWV basement bath -fireblock vertical every 10’ between foundation/framing and studs at finished basement -fireblock vent at top plate basement bed closet -install windows basement bed -exterior bracing at basement den exterior wall per plans -full height 6x6 cedar post at covered deck per plans -provide lag bolt spacing for covered deck ledger attachment per detail page S1.0
Erosion Control Inspection Residential Partial 06/01/2022
All Rough Inspection - Residential Failed 6/14/2022 6/14/2022 06/14/2022
Misc
Corrective Action Required
06/01/2022
-provide stud shoe at SE cable stud bore garage (INSTALL NAILS PER MANUFACTURER INSTRUCTIONS. COMPLETE, NOT SCREWS) -provide H2.5 clips at ends and full bearing for C3 truss at front bedroom (HAVE ENGINNER WITH TRUSS MANUFACTURER ADDRESS, TRUSS HAS NOW BEEN CUT AND MODIFIED) -provide proper slope for plumbing vents across trusses in attic -extend WSP panel to interior and exterior side of wall along great room/kitchen wall per plans -address D1 girder truss, per plans the D1 girder truss shows the B and A trusses attached to girder with truss hangers and does not show ledger or fur out face nailed to girder with truss hangers attached to ledgers -fireblock master tub trap, location has been moved -install windows basement bed -exterior bracing at basement den exterior wall per plans
All Rough Inspection - Residential Failed 7/1/2022 7/1/2022 07/01/2022
Misc
Corrective Action Required
06/14/2022
-extend WSP panel to interior and exterior side of wall along great room/kitchen wall per plans -install windows basement bed -exterior bracing at basement den exterior wall per plans
All Rough Inspection - Residential Failed 7/8/2022 7/8/2022 07/08/2022
Misc
Corrective Action Required
07/01/2022
-install windows basement bed Ok to insulate
All Rough Inspection - Residential Passed 7/15/2022 7/15/2022 07/15/2022
Misc
Resolved
07/15/2022
Driveway Inspection Partial 8/9/2022 8/9/2022 08/09/2022
Misc
Informational
08/09/2022
8.9.2022 I conducted a driveway inspection and pass the sub-grade to pour concrete
Sidewalk Inspection Partial 8/9/2022 8/9/2022 08/09/2022
Misc
Informational
08/09/2022
8.9.2022 I conducted a sidewalk inspection and pass the subgrade to pour concrete
Driveway Inspection Passed 8/15/2022 (1:00) 8/15/2022 08/12/2022
Misc
Informational
08/09/2022
8.9.2022 I conducted a driveway inspection and pass the sub-grade to pour concrete 8.12.2022 Driveway appears to be compliant
Sidewalk Inspection Passed 8/15/2022 (1:00) 8/15/2022 08/12/2022
Misc
Informational
08/09/2022
8.9.2022 I conducted a sidewalk inspection and pass the subgrade to pour concrete 9.12.2022 Sidewalk appears to be compliant
Occupancy Inspection - Codes Residential Failed 11/11/2022 11/11/2022 11/11/2022
Misc
Corrective Action Required
11/11/2022
-pay all inspections fees -install strike plates at front door, adjust for latching -master bath jacuzzi tub, secure electrical box, fireblock tub trap, access to pump motor as required by code P2720.1 -install kitchen wall light -garage door must be self closing -fireblock open beam pocket to basement at garage -no more than 3/8” variance between stair rises at garage -install handrail basement stairs -install basement egress ladder -install basement vanity lights -provide water pressure regulator at water line -secure main water line to foundation wall -security screws basement walkout -splash blocks -6” clearance required between siding and grade, provide required 6” of fall within first 10’ of foundation - see rear -replace vegetation disturbed by construction at rear of lot, clean all old silt fence and construction trash
Erosion Control Inspection Residential Passed 11/11/2022 11/11/2022 11/11/2022
Plot Plan Inspection Passed 01/11/2023
Occupancy Inspection - Codes Residential Full C of O 1/11/2023 1/11/2023 01/11/2023
Misc
Resolved
01/11/2023
Documents & Images
Date Uploaded File Type Document Name
06/03/2021 RR #92 - PERMIT APP
06/04/2021 Approved Plans Approved Drawings
06/04/2021 Approved Plans Approved Truss Package
06/04/2021 Approved Plans Approved Truss Layout
06/04/2021 Permit Codes Residential Plan Review
06/04/2021 Engineer Report for Walkout basement
06/04/2021 Plot Plan Approved Plot Plan
06/04/2021 Permit Codes Residential Plan Review
06/09/2021 Permit DS Building Permit
06/09/2021 Receipt Receipt for transaction:2021-004184
09/01/2021 Letter INSPECTION SUMMARY
09/01/2021 Letter Stop Work Order
09/01/2021 92 Reserve at Stoney Creek FDTN
09/01/2021 Lot 92 Reserve at Stoney Creek Footing Inspection 1
09/02/2021 Letter INSPECTION SUMMARY
09/03/2021 Letter INSPECTION SUMMARY
09/14/2021 Letter INSPECTION SUMMARY
09/20/2021 Letter INSPECTION SUMMARY
09/23/2021 Letter INSPECTION SUMMARY
09/27/2021 Letter INSPECTION SUMMARY
10/14/2021 Letter INSPECTION SUMMARY
10/15/2021 Letter INSPECTION SUMMARY
10/15/2021 Letter INSPECTION SUMMARY
05/27/2022 Letter INSPECTION SUMMARY
05/27/2022 Letter INSPECTION SUMMARY
05/27/2022 Letter INSPECTION SUMMARY
05/27/2022 Letter INSPECTION SUMMARY
06/01/2022 Letter INSPECTION SUMMARY
06/01/2022 Letter INSPECTION SUMMARY
06/01/2022 Letter INSPECTION SUMMARY
06/01/2022 Letter INSPECTION SUMMARY
06/14/2022 Letter INSPECTION SUMMARY
06/23/2022 C3 Gable Truss
06/28/2022 92 reserve at stoney creek letter 2
07/01/2022 Letter INSPECTION SUMMARY
07/08/2022 Letter INSPECTION SUMMARY
07/15/2022 Letter INSPECTION SUMMARY
08/09/2022 Letter INSPECTION SUMMARY
08/09/2022 Letter INSPECTION SUMMARY
08/12/2022 Letter INSPECTION SUMMARY
08/12/2022 Letter INSPECTION SUMMARY
08/12/2022 Letter INSPECTION SUMMARY
11/11/2022 Letter INSPECTION SUMMARY
11/11/2022 Letter INSPECTION SUMMARY
11/14/2022 Receipt Receipt for transaction:2022-008905
01/11/2023 Letter INSPECTION SUMMARY
01/11/2023 Letter Field Certificate of Occupancy
01/11/2023 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home