Permit Application Status

PRRES20210875


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20210875
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - FINISHED AND UNFINISHED BASEMENT - COVERED DECK - ROOF TRUSSES AND ENG. FLOOR SYSTEM ( BOTH DEFERRED )
03/02/2021
03/11/2021
09/06/2021
09/22/2022
Locations
Contacts
ROESER HOMES LLC, Address:11415 STRANG LINE RD, Phone:(913) 220-7477  
MELISSA@ROESERHOMES.COM  
MIDWEST HEATING COOLING & PLUMBING, Address:13228 HOLMES RD, Phone:(816) 943-8513  
ELECTRICAL INVESTMENTS, Address:8014 REEDER ST, Phone:(816) 210-1597  
MILLER PLUMBING CO, Address:PO BOX 393 , Phone:(913) 851-1333  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 03/12/2021 03/10/2021
Brandon Kalwei
Residential Plan Review Approved 03/12/2021 03/10/2021
Brandon Kalwei
Plot Plan Review Approved 03/04/2021 03/03/2021
Brandon Kalwei
Residential Plan Review Rejected 03/04/2021 03/02/2021
Brandon Kalwei
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,191.33 $1,191.33 Paid 03/11/2021
8331507-Sewer Connection Fee $360.00 $360.00 Paid 03/11/2021
Right of Way Permit Fee $80.00 $80.00 Paid 03/11/2021
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 03/11/2021
Water Meter Fee $455.54 $455.54 Paid 03/11/2021
Water Tap Fee $3,581.00 $3,581.00 Paid 03/11/2021
Not Ready Inspection Fee $50.00 $50.00 Paid 08/30/2022
Temporary Occupancy Fee $50.00 $50.00 Paid 08/30/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 4/27/2021 (1:30) 4/27/2021 04/27/2021
Underslab Plumbing Inspection - Residential Failed 5/14/2021 5/14/2021 05/14/2021
R506.2.5 Interior Underslab Drains
Corrective Action Required
05/14/2021
- PROVIDE UNDERSLAB INTERIOR DRAIN TILE - - POST ADDRESS - CONCRETE FLOORS (ON GROUND). ADDED 7-927. Where foundations retain earth and enclose habitable or usable space located below grade, drains shall be provided below the floor slab. Drainage tiles, perforated pipe or other approved systems or materials shall be installed at or below the area(s) to be protected; shall be placed with positive or neutral slope to minimize the accumulation of deposits in the drainage system; and shall discharge by gravity or mechanical means to an approved storm water drainage system. The underslab drainage system shall be installed around the inner perimeter of the area(s) to be protected, or, in a manner that will provide adequate drainage for all area(s) to be protected and is approved by the building official. Interior underslab drains installed on uncompacted fill material shall be supported by mechanical means which are adequately tied into the concrete slab to ensure proper drainage throughout the underslab drain(s).
Erosion Control Inspection Residential Failed 05/18/2021
Misc
Corrective Action Required
05/18/2021
-Establish erosion control methods within 48 hours -street cleanup required
Underslab Plumbing Inspection - Residential Passed 6/4/2021 06/04/2021
R506.2.5 Interior Underslab Drains
Resolved
06/04/2021
- PROVIDE UNDERSLAB INTERIOR DRAIN TILE - CONCRETE FLOORS (ON GROUND). ADDED 7-927. Where foundations retain earth and enclose habitable or usable space located below grade, drains shall be provided below the floor slab. Drainage tiles, perforated pipe or other approved systems or materials shall be installed at or below the area(s) to be protected; shall be placed with positive or neutral slope to minimize the accumulation of deposits in the drainage system; and shall discharge by gravity or mechanical means to an approved storm water drainage system. The underslab drainage system shall be installed around the inner perimeter of the area(s) to be protected, or, in a manner that will provide adequate drainage for all area(s) to be protected and is approved by the building official. Interior underslab drains installed on uncompacted fill material shall be supported by mechanical means which are adequately tied into the concrete slab to ensure proper drainage throughout the underslab drain(s).
All Rough Inspection - Residential Failed 7/27/2021 07/27/2021
Misc
Corrective Action Required
07/27/2021
Garage portal ok. Provide report from truss manufacture on screws holding down truss on covered deck. Screws are through the siding and not at the correct height and location through both tope plates.
All Rough Inspection - Residential Failed 8/6/2021 8/6/2021 08/06/2021
Misc
Corrective Action Required
07/27/2021
Garage portal ok. Truss screws over covered deck, ok
Gas Service Inspection - Residential Failed 1/10/2022 1/10/2022 01/10/2022
Miscellaneous Correction
Corrective Action Required
01/10/2022
- provide UL listed clamp for the gas pipe to copper conductor at bonding gas pressure passed
All Rough Inspection - Residential Not Ready 1/10/2022 1/10/2022 01/10/2022
Misc
Corrective Action Required
08/06/2021
Garage portal ok. Truss screws over covered deck, ok
Misc
Corrective Action Required
01/10/2022
Not Ready -no truss package - no fire blocking done provide city stamped truss package and plans
Electrical Service Inspection Passed 1/10/2022 1/10/2022 01/10/2022
All Rough Inspection - Residential Failed 1/25/2022 1/25/2022 01/25/2022
Misc
Corrective Action Required
01/10/2022
Garage portal ok. Truss screws over covered deck, ok
Misc
Corrective Action Required
01/10/2022
- Tighten anchor bolts in garage - Nail truss hanger c13 - Seal under bump out in garage - Nail truss hanger single garage - Girder truss 5 pack need studs above sliding door to transfer loads - Fire block penetration office closet - Solid block sheet breaks office - Seal hole in bathroom floor - Fire block b vent chase hall bath shower - Fire block master shower floor penetrations - Nail off corner of office to master closet - Complete roof boots - Nail all intersecting corners per code - Fire block hutch - Block sheeting breaks garage - Provide lateral bracing for I-joist at stairway basement - Tighten anchor bolts basement - Fire block bedroom 1 - Fire block chase behind shower basement
Gas Service Inspection - Residential Failed 1/25/2022 1/25/2022 01/25/2022
Miscellaneous Correction
Corrective Action Required
01/10/2022
- provide correct bonding clamp fee copper wire - connect fire place - provide 10 lb. Or more pressure
All Rough Inspection - Residential Failed 2/1/2022 02/01/2022
Misc
Resolved
02/01/2022
Garage portal ok. Truss screws over covered deck, ok
Misc
Corrective Action Required
01/25/2022
- Solid block sheet breaks office - Complete roof boots - Fire block hutch
All Rough Inspection - Residential Failed 2/4/2022 2/4/2022 02/04/2022
Misc
Corrective Action Required
02/01/2022
- Complete roof boots OK TO INSULATE
Gas Service Inspection - Residential Failed 2/4/2022 2/4/2022 02/04/2022
Miscellaneous Correction
Corrective Action Required
01/25/2022
- provide correct bonding clamp for copper wire - pressure test passed
Gas Service Inspection - Residential Passed 2/15/2022 2/15/2022 02/15/2022
Miscellaneous Correction
Resolved
02/15/2022
- provide correct bonding clamp for copper wire - pressure test passed
All Rough Inspection - Residential Passed 2/15/2022 2/15/2022 02/15/2022
Misc
Resolved
02/15/2022
Driveway Inspection Partial 4/8/2022 4/8/2022 04/08/2022
Misc
Informational
04/08/2022
Forms were placed and aggregate was present and compacted. RP 4-8-22
Driveway Inspection Passed 4/15/2022 4/15/2022 04/15/2022
Misc
Informational
04/08/2022
Forms were placed and aggregate was present and compacted. RP 4-8-22
Misc
Informational
04/15/2022
Finished driveway meets LS and ADA specs. RP 4-15-22
Erosion Control Inspection Residential Failed 06/08/2022
Misc
Corrective Action Required
05/18/2021
-Establish erosion control methods within 48 hours -street cleanup required
Misc
Corrective Action Required
06/08/2022
Erosion control needs attention to prevent silt/mud from entering roadway. 6/8/22 ES
Sewer Service Inspection - R Passed 6/10/2022 6/10/2022 06/10/2022
Water Service Inspection - R Passed 6/10/2022 06/10/2022
Occupancy Inspection - Codes Residential Failed 8/10/2022 08/10/2022
Misc
Corrective Action Required
07/05/2022
-Water meter in backwards -water meter setter is loose on both sides
Misc
Corrective Action Required
08/10/2022
• final grading and sod • Splash blocks • Obtain irrigation permit and provide back flow certification • Seal exterior penetrations • Seal top of meter can and a/c disconnect • Attach AC whip 12” from disconnect • Sump discharge minimum of 36” from foundation • Pay all fees • Label non gfci outlets • Provide spark rings kitchen counter outlets • Complete hardware and secondary lock on sliding door • Complete deck and guard • Provide spark rings at bar counter outlets • Provide lockouts at electrical panel • Provide steps to grade from back patio up to yard • Provide handrail from patio to grade • Add 2@ 1/2” through bolts at each post to beam connections on deck • Add security screws on exterior doors • Anchor steel column near furnace • Address water meter
Piers/Caissons Inspection - Residential Passed 08/10/2022
Misc
Informational
08/10/2022
inspected by third party.
Erosion Control Inspection Residential Passed 08/10/2022
Misc
Resolved
08/10/2022
Misc
Resolved
08/10/2022
Plot Plan Inspection Passed 08/26/2022
Erosion Control Inspection Residential Failed 8/26/2022 08/26/2022
Misc
Corrective Action Required
08/26/2022
maintain erosion control untill sod is in.
Occupancy Inspection - Codes Residential Failed 8/26/2022 8/26/2022 08/26/2022
Misc
Resolved
08/26/2022
-Water meter in backwards -water meter setter is loose on both sides
Misc
Corrective Action Required
08/10/2022
• final grading and sod • Obtain irrigation permit and provide back flow certification • Seal top of meter can and a/c disconnect • Attach AC whip 12” from disconnect • Pay all fees • Label non gfci outlets • Complete hardware and secondary lock on sliding door
Erosion Control Inspection Residential Passed 08/30/2022
Misc
Resolved
08/30/2022
Occupancy Inspection - Codes Residential Failed 8/30/2022 8/30/2022 08/30/2022
Misc
Corrective Action Required
08/26/2022
• final grading and sod • Pay all fees • Complete hardware on sliding door * Prrovide gaurd rail or adjest grade front stoop over 30"
Occupancy Inspection - Codes Residential Ready for Temp CO 8/30/2022 08/30/2022
Misc
Corrective Action Required
08/30/2022
• final grading and sod • Pay all fees • Complete hardware on sliding doo, no handle and latch, but does have secondary lock. ( NOT A POINT OF ERGRESS :NO STAIRS)
Occupancy Inspection - Codes Residential Temporary C of O 08/30/2022
Misc
Corrective Action Required
08/30/2022
• final grading and sod • Pay all fees • Complete hardware on sliding doo, no handle and latch, but does have secondary lock. ( NOT A POINT OF ERGRESS :NO STAIRS)
Occupancy Inspection - Codes Residential Full C of O 9/22/2022 9/22/2022 09/22/2022
Misc
Resolved
09/22/2022
Documents & Images
Date Uploaded File Type Document Name
03/02/2021 Application Form APPLICATION
03/02/2021 Activity Document excise tax
03/02/2021 Final Plot Plan - Lot 1483 WV
03/02/2021 I-Joist Engineered - Lot 1483 WV
03/02/2021 Engineered Plans_ - Lot 1483 WVpdf
03/02/2021 Letter Codes Residential Plan Review
03/02/2021 Approved Plans approved i joists
03/03/2021 Plot Plan APPROVED PLOT PLAN
03/10/2021 Engineered Plans_ - Lot 1483 WV
03/10/2021 Approved Plans APPROVED PLANS
03/11/2021 Receipt Receipt for transaction:2021-001201
03/11/2021 Letter DS Building Permit
04/19/2021 3057 NW Thoreau Ln_PIER INSP_2021-04-15
04/19/2021 PIER PLAN - Lot 1483 WV
04/20/2021 Approved Plans APPROVED PIER PLAN
04/27/2021 Letter INSPECTION SUMMARY
05/18/2021 Letter INSPECTION SUMMARY
05/18/2021 Letter INSPECTION SUMMARY
06/04/2021 Letter INSPECTION SUMMARY
06/16/2021 3057 NW Thoreau Ln_ALL SLAB INSP_2021-06-10
07/27/2021 Letter INSPECTION SUMMARY
08/06/2021 Letter INSPECTION SUMMARY
01/10/2022 Letter INSPECTION SUMMARY
01/10/2022 Letter INSPECTION SUMMARY
01/10/2022 Letter INSPECTION SUMMARY
01/21/2022 Approved Plans APPROVED TRUSS LAYOUT
01/21/2022 Approved Plans APPROVED TRUSS PACKAGE
01/25/2022 Letter INSPECTION SUMMARY
01/25/2022 Letter INSPECTION SUMMARY
02/01/2022 Letter INSPECTION SUMMARY
02/04/2022 Letter INSPECTION SUMMARY
02/04/2022 Letter INSPECTION SUMMARY
02/15/2022 Letter INSPECTION SUMMARY
02/15/2022 Letter INSPECTION SUMMARY
04/08/2022 Letter INSPECTION SUMMARY
04/15/2022 Letter INSPECTION SUMMARY
06/08/2022 Letter INSPECTION SUMMARY
06/10/2022 Letter INSPECTION SUMMARY
06/10/2022 Letter INSPECTION SUMMARY
08/10/2022 Letter INSPECTION SUMMARY
08/10/2022 Letter INSPECTION SUMMARY
08/10/2022 Letter INSPECTION SUMMARY
08/26/2022 Letter INSPECTION SUMMARY
08/26/2022 Letter INSPECTION SUMMARY
08/26/2022 Letter INSPECTION SUMMARY
08/30/2022 Letter INSPECTION SUMMARY
08/30/2022 Receipt Receipt for transaction:2022-007136
08/30/2022 Letter Codes Temporary Certificate of Occupancy
09/22/2022 Letter Codes Final Certificate of Occupancy
09/22/2022 Letter Codes Final Certificate of Occupancy
09/22/2022 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home