Permit Application Status

PRRES20210399


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20210399
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - COVERED DECK
01/28/2021
03/23/2021
08/01/2021
05/02/2022
Locations
Contacts
SPELLERBERG ENTERPRISES LLC, Address:613 NE VIEWPARK DR, Phone:(816) 550-5535  
SPELLERBERGENTERPRISES@GMAIL.COM  
AFC HEATING AND COOLING, Address:824 NW MAIN ST , Phone:(816) 347-8388  
NEW HEIGHTS ELECTRIC LLC, Address:P O BOX 163, Phone:(816) 625-9504  
TRI-COUNTY PLUMBING LLC, Address:PO BOX 234, Phone:(816) 720-3222  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 02/04/2021 02/02/2021
Dylan Eppert
Easements
Corrective Action Required
02/02/2021

All easements with dimensions must be provided on the plot plan. PLAT SHOWS A 20' U/E NOT 15' PLEASE REVISE.
Residential Plan Review Approved 02/04/2021 02/02/2021
Dylan Eppert
Plot Plan Review Rejected 02/01/2021 02/02/2021
Dylan Eppert
Easements
Corrective Action Required
02/02/2021

All easements with dimensions must be provided on the plot plan. PLAT SHOWS A 20' U/E NOT 15' PLEASE REVISE.
Residential Plan Review Approved 02/01/2021 02/02/2021
Dylan Eppert
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,423.15 $1,423.15 Paid 03/23/2021
8331507-Sewer Connection Fee $630.00 $630.00 Paid 03/23/2021
8350015-Water Meter Fee $455.54 $455.54 Paid 03/23/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 03/23/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 03/23/2021
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 03/23/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 4/12/2021 (1:00) 4/12/2021 04/12/2021
Erosion Control Inspection Residential Failed 5/10/2021 5/10/2021 05/10/2021
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
05/10/2021
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. RE ESTABLISH SILT FENCE AT FRONT OF LOT
Underslab Plumbing Inspection - Residential Failed 5/10/2021 5/10/2021 05/10/2021
Misc
Corrective Action Required
05/10/2021
-MAINTAIN SILT FENCE EROSION CONTROL AT FRONT OF LOT
Sewer Service Inspection - R Passed 5/18/2021 (3:00) 5/18/2021 05/18/2021
Water Service Inspection - R Partial 5/18/2021 (9:30) 5/18/2021 05/18/2021
Misc
Informational
05/18/2021
-PARTIAL ON PEX
Water Service Inspection - R Passed 5/19/2021 (9:30) 5/19/2021 05/19/2021
Misc
Resolved
05/19/2021
Underslab Plumbing Inspection - Residential Passed 5/20/2021 5/20/2021 05/20/2021
Misc
Resolved
05/20/2021
Electrical Service Inspection Passed 10/29/2021 10/29/2021 10/29/2021
Gas Service Inspection - Residential Failed 10/29/2021 10/29/2021 10/29/2021
Misc
Corrective Action Required
10/29/2021
-GAS LINE BOND REQUIRED - GAS PRESSURE TEST OK
All Rough Inspection - Residential Failed 10/29/2021 10/29/2021 10/29/2021
Misc
Corrective Action Required
10/29/2021
-Maintain erosion control silt fence at front of lot -Nail exterior sheathing garage PFH per plans -Tension straps at garage PFH -Nail protection plates at all NM (romex) 1 1/4” or less from end of stud- see garage, kitchen -Fireblock HVAC plumbing chase garage -Pan off and fur down for insulation at HVAC RA garage ceiling, Pan off through furred down at garage wall -Seal plate penetration for SEC cable at 1st floor bedroom N wall -Add stud shoe, sgl stud at kitchen wall for DWV -Add electrical for kitchen island -seal top plate penetrations - see front entry, 2nd floor front East bedroom, master shower -Joist hangers at floor joists 4’ or more at front entry -Nail dbl joist hanger complete at lvl connection front entry -Secure CSST gas line at fireplace -Fireblock plumbing chase great room -Protect pex against recessed can light at great room -security blocking back door -Nail exterior sheathing CS-PF design per plans at dining room windows and 2nd floor bedroom -Dbl top plate requires 24” min offset between plate breaks - see 2nd floor bath west exterior wall -Add joist hanger to tail joist at attic access 2nd floor laundry -Protect NM within 6’ of attic access 2nd floor -Land NM to box at jacuzzi tub master bath -smoke/co outside of bedroom at 2nd floor bedroom East side near stairs -Secure all NM and SEC cables above service panel at basement -Anchor all SCH 40 steel columns to floor at basement -All bath exhaust fans shall vent direct to exterior, see general notes in plans page D2 -No inspection of covered patio framing prior to cover -Electrical for AC compressor
Gas Service Inspection - Residential Passed 11/4/2021 11/4/2021 11/04/2021
Misc
Resolved
11/04/2021
All Rough Inspection - Residential Passed 11/4/2021 11/4/2021 11/04/2021
Misc
Resolved
11/04/2021
Occupancy Inspection - Codes Residential Failed 11/4/2021 11/4/2021 11/04/2021
Misc
Corrective Action Required
11/04/2021
11/4/21 - BELOW CORRECTIONS CARRIED FROM ALL ROUGH -ANCHOR ALL SCH 40 STEEL COLUMNS TO FLOOR AT BASEMENT -AC ELECTRICAL DISCONNECT NOT INSTALLED AT ROUGH, CONFIRM ELECTRICAL AND RECEPTACLE WITHIN 25' AT OCCUPANCY
Piers/Caissons Inspection - Residential Passed 11/22/2021 (8:00) 11/22/2021 11/22/2021
Occupancy Inspection - Codes Residential Failed 3/11/2022 3/11/2022 03/11/2022
Misc
Corrective Action Required
11/04/2021
-Final driveway inspection required, contact development services to schedule -Final grade and sod -remove all construction debris/rebar from lot -splash blocks at all downspout and sump pump discharge locations, min 36” discharge from foundation -install deadbolt lock front door -Install all outlets and cover plates/switches at kitchen -Install spark rings kitchen counter outlets, more than 1/4” setback on non combustible surface -Handrail required at garage steps, 4 rises -label all circuit breaker locations at service panel -add breaker lockout for hardwired appliances -complete rear deck install, stairs, handrail, guard rails, landing, etc -handrail required at walkout/walk up stairs to patio area, depending on final configuration a guardrail might be required around wall if walking surface -install exterior security light at rear, exposed NM at wall -Due to conditions at time of inspection a full inspection has not been performed for full exterior. Additional items might be added at reinspection
Driveway Inspection Passed 11/29/2021 11/29/2021 03/21/2022
Misc
Informational
11/29/2021
On Monday 11/29/2021 I performed a driveway inspection and pass the subgrade to pour concrete
Driveway Inspection Passed 3/21/2022 3/21/2022 03/21/2022
Misc
Informational
11/29/2021
On Monday 11/29/2021 I performed a driveway inspection and pass the subgrade to pour concrete
Erosion Control Inspection Residential Passed 03/22/2022
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
05/10/2021
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. RE ESTABLISH SILT FENCE AT FRONT OF LOT
Deck Final Inspection - Residential Failed 3/22/2022 03/22/2022
Misc
Corrective Action Required
03/22/2022
- Provide corrections for deck ledger patio side - Provide 2 @ 1/2” through bolts at deck at the beam to post connections
Occupancy Inspection - Codes Residential Temporary C of O 3/22/2022 3/22/2022 03/22/2022
Misc
Corrective Action Required
03/11/2022
-Final grade and sod - Provide corrections for deck ledger patio side - Provide 2 @ 1/2” through bolts at deck at the beam to post connections
Plot Plan Inspection Passed 5/2/2022 5/2/2022 05/02/2022
Occupancy Inspection - Codes Residential Full C of O 5/2/2022 5/2/2022 05/02/2022
Misc
Resolved
05/02/2022
Documents & Images
Date Uploaded File Type Document Name
01/28/2021 Application Form 4524 SW Nautilus permit app
01/28/2021 8 Creekside at Raintree FOR PERMIT (1)
01/28/2021 CR 8-LSMO
02/02/2021 Approved Plans APPROVED HOUSE PLANS
02/02/2021 Letter Codes Residential Plan Review
02/02/2021 Plot Plan APPROVED PLOT PLAN
03/23/2021 Receipt Receipt for transaction:2021-001450
03/23/2021 Letter DS Building Permit
04/12/2021 Letter INSPECTION SUMMARY
05/10/2021 Letter INSPECTION SUMMARY
05/10/2021 Letter INSPECTION SUMMARY
05/18/2021 Letter INSPECTION SUMMARY
05/18/2021 Letter INSPECTION SUMMARY
05/19/2021 Letter INSPECTION SUMMARY
05/20/2021 Letter INSPECTION SUMMARY
10/29/2021 Letter INSPECTION SUMMARY
10/29/2021 Letter INSPECTION SUMMARY
10/29/2021 Letter INSPECTION SUMMARY
11/04/2021 Letter INSPECTION SUMMARY
11/04/2021 Letter INSPECTION SUMMARY
11/04/2021 Letter INSPECTION SUMMARY
11/22/2021 Letter INSPECTION SUMMARY
11/29/2021 Letter INSPECTION SUMMARY
03/11/2022 Letter INSPECTION SUMMARY
03/22/2022 Letter INSPECTION SUMMARY
03/22/2022 Letter INSPECTION SUMMARY
03/22/2022 Letter Codes Temporary Certificate of Occupancy
04/19/2022 Letter INSPECTION SUMMARY
04/19/2022 Letter INSPECTION SUMMARY
04/19/2022 Letter INSPECTION SUMMARY
05/02/2022 Letter INSPECTION SUMMARY
05/02/2022 Letter Field Certificate of Occupancy
05/02/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home