Permit Application Status

PRRES20210157


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20210157
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - ROOF TRUSS - UNFINISHED BASEMENT The address on the recorded plat for this lot is 2035 NW Ashurst Dr. Updates have been made to the permit. Mike Weisenborn 12/07/2021 1:54 PM
01/12/2021
01/19/2021
07/13/2021
11/11/2021
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
PERMITTING@SUMMITHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 01/21/2021 01/19/2021
Dylan Eppert
Residential Plan Review Approved 01/21/2021 01/19/2021
Dylan Eppert
Plot Plan Review Approved 01/14/2021 01/19/2021
Dylan Eppert
Miscellaneous Correction
Corrective Action Required
01/14/2021

HOUSE ADDRESS SHOULD BE 2033 NW ASHURST DR. NOT 2035 NW ASHURST DR.
As-graded plot plan
Corrective Action Required
01/14/2021

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
Miscellaneous Correction
Corrective Action Required
01/14/2021

The middle evevation on the west side is proposed as 946.80 and the adjacent plot plan on lot 17 shows and elevation of 943.50 please verify as to the 3 feet in elevation difference.
Residential Plan Review Approved 01/14/2021 01/15/2021
Dylan Eppert
Miscellaneous Correction
Corrective Action Required
01/14/2021

HOUSE ADDRESS SHOULD BE 2033 NW ASHURST DR. NOT 2035 NW ASHURST DR.
Planning Review (RES) Approved 01/14/2021 01/12/2021
Shannon McGuire
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $947.65 $947.65 Paid 01/19/2021
8331507-Sewer Connection Fee $360.00 $360.00 Paid 01/19/2021
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 01/19/2021
8350015-Water Meter Fee $455.54 $455.54 Paid 01/19/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 01/19/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 01/19/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/25/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/25/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 11/10/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Failed 3/1/2021 03/01/2021
Misc
Resolved
03/15/2021
Sewer Service Inspection - R Passed 3/1/2021 (1:15) 3/1/2021 03/01/2021
Water Service Inspection - R Passed 3/2/2021 (1:00) 3/2/2021 03/02/2021
Underslab Plumbing Inspection - Residential Passed 3/12/2021 3/12/2021 03/12/2021
Footing Inspection - Residential Passed 2/22/2021 03/15/2021
Misc
Informational
03/15/2021
- 3RD PARTY FOOTING BY DEREK PEREZ @ RES SIGNED & SEALED BY BRADLEY HUXOL - - UFER CENTER OF WEST GARAGE FOUNDATION WALL -
Piers/Caissons Inspection - Residential Passed 5/3/2021 (10:30) 5/3/2021 05/03/2021
Misc
Informational
05/03/2021
(2) 24 x 36 w/ (4) # 4 VERT BARS
Erosion Control Inspection Residential Failed 5/26/2021 05/26/2021
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
05/26/2021
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. MAINTAIN SILT FENCE CLEAN SREET
Electrical Service Inspection Failed 5/26/2021 05/26/2021
Misc
Corrective Action Required
05/26/2021
IDENTIFY UFER GROUND IN SERVICE PANEL (GREEN TAPE )
Gas Service Inspection - Residential Failed 5/26/2021 05/26/2021
Misc
Corrective Action Required
05/26/2021
PROVIDE MIN 10 PSI FOR 15 MIN ( LEAK ? )
All Rough Inspection - Residential Failed 5/26/2021 5/26/2021 05/26/2021
Misc
Corrective Action Required
05/26/2021
Provide flashing horizontal trim above garage door Provide min 4 studs at GT bearing per plan Provide solid blocking at sheathing breaks above garage door Provide 2 studs supporting LVLs & beam at covered deck Nail stud behind tub/shower bath #2 Fire block tub trap bath #2 Seal floor at dead space master water closet Seal upward penetration foyer/bath #2 Seal upward penetration master closet/laundry Seal top plate laundry above dryer vent Seal hood stub kitchen Tighten anchor bolts basement Identify ufer ground at service panel Provide pressure for gas test Solid blocking under kitchen island Provide anchor bolt at SGD end of plate Provide anchor bolt within 12" of plate break Between basement windows Sister over notched studs basement Nail sheathing per code Provide 3 studs & bottom plate w/ anchor bolts east & west corners basement
All Rough Inspection - Residential Failed 6/21/2021 6/21/2021 06/21/2021
Misc
Corrective Action Required
05/26/2021
Provide solid blocking at sheathing breaks above garage door Provide pressure for gas test - gauge at 8 psi, must maintain 10 psi Nail sheathing per code Provide 3 studs & bottom plate w/ anchor bolts east & west corners basement - bottom plate and stud added, anchor bolt req at bottom plate **OK TO INSULATE**
Electrical Service Inspection Passed 6/21/2021 06/21/2021
Misc
Resolved
06/21/2021
All Rough Inspection - Residential Not Ready 6/24/2021 6/24/2021 06/24/2021
Misc
Corrective Action Required
06/21/2021
Provide solid blocking at sheathing breaks above garage door ( 2 car overhead door ) Provide pressure for gas test - gauge at 8 psi, must maintain 10 psi ( only 5 psi) **OK TO INSULATE**
All Rough Inspection - Residential Passed 6/30/2021 6/30/2021 06/30/2021
Misc
Resolved
06/30/2021
Provide solid blocking at sheathing breaks above garage door ( 2 car overhead door ) Provide pressure for gas test - gauge at 8 psi, must maintain 10 psi ( only 5 psi) **OK TO INSULATE**
Gas Service Inspection - Residential Passed 6/30/2021 06/30/2021
Misc
Resolved
06/30/2021
PROVIDE MIN 10 PSI FOR 15 MIN ( LEAK ? )
Driveway Inspection Partial 7/14/2021 7/14/2021 07/14/2021
Misc
Informational
07/14/2021
Forms were placed and aggregate was present and compacted. RP 7-14-21
Misc
Informational
07/14/2021
Forms were placed and aggregate was present and compacted. RP 7-14-21
Driveway Inspection Passed 7/23/2021 7/23/2021 07/23/2021
Misc
Informational
07/14/2021
Forms were placed and aggregate was present and compacted. RP 7-14-21
Misc
Informational
07/14/2021
Forms were placed and aggregate was present and compacted. RP 7-14-21
Misc
Informational
07/23/2021
Finished driveway meets LS and ADA specs. RP 7-23-21
Sidewalk Inspection Not Ready 9/16/2021 9/16/2021 09/16/2021
Misc
Corrective Action Required
09/16/2021
No aggregate in place.
Sidewalk Inspection Partial 9/17/2021 9/17/2021 09/17/2021
Misc
Corrective Action Required
09/16/2021
No aggregate in place.
Misc
Informational
09/17/2021
Forms were placed and aggregate was present and compacted. RP 9-17-21
Sidewalk Inspection Passed 9/24/2021 9/24/2021 09/24/2021
Misc
Corrective Action Required
09/17/2021
No aggregate in place.
Misc
Informational
09/17/2021
Forms were placed and aggregate was present and compacted. RP 9-17-21
Misc
Informational
09/24/2021
Sidewalk is good and meets ADA spec of 1.5% or less
Occupancy Inspection - Codes Residential Failed 10/13/2021 10/13/2021 10/13/2021
Misc
Corrective Action Required
10/13/2021
-submit as-graded plot plan. -pay re-inspection fees. - sod ,final grade, exterior items. - lower water meter to flush with grade, excavate and lower water meter. lid to lid must be 14-18" at re-inspection. - over 7 /34" from threshold to patio basement sliding door. - missing hardware both sliding doors. -deck guard less than 34". -provide engineers report on continuous deck posts. -support and secure gas line to water heater. - pex piping in contract with B vent at water heater. -sheetrock platform at garage. -seal DWV where exits foundation wall. -support outside rim joist at deck where connects to house. -guard needed at front porch
Occupancy Inspection - Codes Residential Not Ready 11/2/2021 11/2/2021 11/02/2021
Misc
Corrective Action Required
10/13/2021
-submit as-graded plot plan. -pay re-inspection fees. - sod ,final grade, exterior items. - lower water meter to flush with grade, excavate and lower water meter. lid to lid must be 14-18" at re-inspection. -provide engineers report on continuous deck posts. -support and secure gas line to water heater. -seal DWV where exits foundation wall. -support outside rim joist at deck where connects to house.(corner bracket)
Plot Plan Inspection Passed 11/3/2021 11/03/2021
Occupancy Inspection - Codes Residential Full C of O 11/11/2021 11/11/2021 11/11/2021
Misc
Resolved
11/11/2021
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home