Summary
PRRES20202250
Building Permit - Residential
Certificate of Occupancy
MALTBY CAROLE J
ADDITION SINGLE FAMILY
ADDITION OF MASTER BR & BATH WITH BASEMENT ADDITON 680 SQFT W/SUSPENDED SLAB - GARAGE EXPANSION 449 SQFT
08/11/2020
08/17/2020
05/13/2021
Locations
Contacts
MALTBY CAROLE J, Address:15926 DALMATIAN AVE  
Aaron & Megan Rhoads, Phone:(816) 678-6791  
megan@rhoadsfamily.us  
BUTTERWORTH ELECTRIC SERVICE, Address:4001 N KOGER RD, Phone:(816) 650-6772  
ONE HOUR HEATING & AIR CONDITIONING, Address:712 SW BLUE PKWY, Unit A, Phone:(816) 524-2121  
TRI-COUNTY PLUMBING LLC, Address:PO BOX 234, Phone:(816) 720-3222  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 08/14/2020 08/17/2020
Dylan Eppert
electrical and mechanical contractors Steven Conrick 08/11/2020 4:55 PM waiting on electrical contractor Steven Conrick 08/12/2020 4:05 PM
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Add/Alter Single Family $525.00 $525.00 Paid 08/17/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 9/17/2020 (1:00) 9/17/2020 09/17/2020
Footing Inspection - Residential Passed 10/7/2020 (8:30) 10/7/2020 10/07/2020
Informational
10/07/2020
36" COLUMN PAD IN BASEMENT-OK
Suspended Slab Inspection Failed 12/4/2020 12/4/2020 12/04/2020
Miscellaneous Correction
Corrective Action Required
12/04/2020
-Provide engineered drawing of suspended slab at stoop
Suspended Slab Inspection Passed 12/8/2020 (1:00) 12/8/2020 12/08/2020
Miscellaneous Correction
Resolved
12/08/2020
-Provide engineered drawing of suspended slab at stoop
All Rough Inspection - Residential Failed 2/10/2021 2/10/2021 02/10/2021
Misc
Corrective Action Required
02/10/2021
-Install security blocking for all exterior doors; fill in gaps with solid wood at: at strike side 12” on each side of strike plate; fill in gap at each hinge -Over-filled electrical box at upper stair landing -Protect plumbing at kitchen wall; at master shower -Protect electrical wiring at kitchen wall -Secure SE cable within 12" of meter box -Fb all ceiling and floor penetrations and openings -Secure exterior stoop receptacle box -Provide full bearing support for master bedroom ceiling and roof support bearing point loads; at master bathroom roof beam point load -Provide 5 studs support for 24” lvl all the way to basement pad -Complete electrical to wall receptacle in bedroom -Seal all penetrations of return air space -Fb plumbing chase in basement from ceiling space **OK TO INSULATE
All Rough Inspection - Residential Partial 2/12/2021 02/12/2021
Misc
Corrective Action Required
02/10/2021
-Install security blocking for all exterior doors; fill in gaps with solid wood at: at strike side 12” on each side of strike plate; fill in gap at each hinge -Over-filled electrical box at upper stair landing **OK TO ROCK AFTER DONE WITH THE ABOVE AND SEND IN PICTURES TO KHANH.NGUYEN@CITYOFLS.NET
Electrical Service Inspection Passed 3/31/2021 3/31/2021 03/31/2021
All Rough Inspection - Residential Passed 05/07/2021
Misc
Resolved
05/07/2021
-Install security blocking for all exterior doors; fill in gaps with solid wood at: at strike side 12” on each side of strike plate; fill in gap at each hinge -Over-filled electrical box at upper stair landing **OK TO ROCK AFTER DONE WITH THE ABOVE AND SEND IN PICTURES TO KHANH.NGUYEN@CITYOFLS.NET
Occupancy Inspection - Codes Residential Failed 5/7/2021 5/7/2021 05/07/2021
Misc
Corrective Action Required
05/07/2021
-Seal exterior lights, wall penetrations, etc -Install spark ring at exterior receptacle box recessed behind combustible wall siding; seal around box -Install tamper proof caps at AC valves -Install 36” sump pump extension or splash block -Fasten ladder to window well and provide landing -Garage receptacle near dwelling entry door not gfci-protected -Doors from dwelling to garage must be self-closing -Provide 5/8” GB rock under pull down attic access and around I beam column -Provide afci protection for disposal/dishwasher, washing machines, all kitchen light&receptacle outlets, etc. NEC 210.12 -Provide max 25 amp for the new AC -Install breaker locks for oven and cooktop Secure all wiring within 12” of panels
Occupancy Inspection - Codes Residential Temporary C of O 5/12/2021 5/12/2021 05/12/2021
Misc
Corrective Action Required
05/07/2021
-Provide afci protection for all kitchen light&receptacle outlets, etc. NEC 210.12 **microwave and hood not afci
Occupancy Inspection - Codes Residential Full C of O 5/13/2021 05/13/2021
Misc
Resolved
05/13/2021
-Provide afci protection for all kitchen light&receptacle outlets, etc. NEC 210.12 **microwave and hood not afci
Documents & Images
Date Uploaded File Type Document Name
08/11/2020 APP
08/11/2020 APPROVED PLANS
08/11/2020 APPROVED PLOT PLAN
08/17/2020 Receipt Receipt for transaction:2020-005309
08/17/2020 Letter DS Building Permit
09/17/2020 Letter INSPECTION SUMMARY
10/07/2020 Letter INSPECTION SUMMARY
12/04/2020 Letter INSPECTION SUMMARY
12/08/2020 Plans APPROVED REVISED HOUSE PLANS WITH SUSPENDED SLAB
12/08/2020 Letter INSPECTION SUMMARY
02/10/2021 Letter INSPECTION SUMMARY
02/12/2021 Letter INSPECTION SUMMARY
03/31/2021 Letter INSPECTION SUMMARY
05/07/2021 Letter INSPECTION SUMMARY
05/07/2021 Letter INSPECTION SUMMARY
05/07/2021 Letter INSPECTION SUMMARY
05/12/2021 Letter Codes Temporary Certificate of Occupancy
05/13/2021 Letter Codes Final Certificate of Occupancy
05/13/2021 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home