Permit Application Status

PRRES20200837


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20200837
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - ROOF TRUSS PACKAGE - UNFINISHED BASEMENT
04/01/2020
04/03/2020
05/06/2021
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
PERMITTING@SUMMITHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 04/03/2020 04/03/2020
Dylan Eppert
Residential Plan Review Approved 04/07/2020 04/03/2020
Dylan Eppert
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,349.34 $1,349.34 Paid 04/03/2020
8331504-EFHB Middle Big Creek, Full $669.60 $669.60 Paid 04/03/2020
8331507-Sewer Connection Fee $600.00 $600.00 Paid 04/03/2020
8331401-Water Tap Fee $3,477.00 $3,477.00 Paid 04/03/2020
8350015-Water Meter Fee $425.02 $425.02 Paid 04/03/2020
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 04/03/2020
7232302-Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 04/03/2020
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 12/08/2020
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 12/08/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 4/30/2020 (1:00) 4/30/2020 at 1:05 PM 04/30/2020
Underslab Plumbing Inspection - Residential Passed 5/22/2020 5/22/2020 05/22/2020
Piers/Caissons Inspection - Residential Passed 6/8/2020 (11:15) 6/8/2020 06/08/2020
Sewer Service Inspection - R Passed 6/18/2020 (11:00) 6/18/2020 06/18/2020
Water Service Inspection - R Passed 6/25/2020 (11:15) 6/25/2020 06/25/2020
All Rough Inspection - Residential Not Ready 8/11/2020 8/11/2020 08/11/2020
Misc
Corrective Action Required
08/11/2020
NO INSPECTION PERFORMED, WRONG SET OF PLANS ON SITE, PLANS ON SITE FOR 1413 SW GEORGETOWN
Electrical Service Inspection Passed 8/13/2020 8/13/2020 08/13/2020
Gas Piping Inspection - Residential Passed 8/13/2020 8/13/2020 08/13/2020
Gas Service Inspection - Residential Passed 8/13/2020 8/13/2020 08/13/2020
All Rough Inspection - Residential Failed 8/13/2020 8/13/2020 08/13/2020
Misc
Corrective Action Required
08/11/2020
- Garage PFH per plans - Secure all DWV 2” or less at mid point - Header at HVAC chase in pantry, floor joist supported on non bearing wall pantry side of box out - Fireblock above top plate between floor joists at owner entry/pantry from garage - Install stud shoes on studs bored more that 40% bearing and 60% non-bearing, see kitchen - Fireblock vertical to horizontal at chase/ furred down in living room - EC#2 per plans - Support all DWV 48” o.c., traps not considered support - 3” SCH 40 steel column at pier location “B” in basement per plans - 3” SCH 40 steel column at W12x16 beam in garage - Anchor all columns to floor in basement - Protection plate at DWV 2nd floor bath - Truss hangers per plans - Trusses missing at front porch per plans - Secure electrical box at front porch - Truss bracing per plans
All Rough Inspection - Residential Failed 8/18/2020 8/18/2020 08/18/2020
Misc
Corrective Action Required
08/13/2020
- Fireblock/solid block above top plate between floor joists at owner entry/pantry from garage - EC#2 per plans - 3” SCH 40 steel column at pier location “B” in basement per plans - 3” SCH 40 steel column at W12x16 beam in garage per plans - Anchor all columns to floor in basement - Truss hangers per plans - Trusses missing at front porch per plans - Secure electrical box at front porch - Truss bracing per plans
All Rough Inspection - Residential Not Ready 9/14/2020 9/14/2020 09/14/2020
Misc
Corrective Action Required
08/18/2020
- Fireblock/solid block above top plate between floor joists at owner entry/pantry from garage - EC#2 per plans - 3” SCH 40 steel column at pier location “B” in basement per plans - 3” SCH 40 steel column at W12x16 beam in garage per plans - Anchor all columns to floor in basement - Truss hangers per plans - Trusses missing at front porch per plans - Secure electrical box at front porch - Truss bracing per plans 9/14 - Not ready for inspection, trades on site working on corrections at time of inspection. Reschedule inspection when ready.
All Rough Inspection - Residential Failed 9/15/2020 9/15/2020 09/15/2020
Misc
Corrective Action Required
09/14/2020
- EC#2 per plans - Secure electrical box at front porch - Truss bracing per plans OK to Insulate Do not rock until approved reinspection
All Rough Inspection - Residential Failed 9/18/2020 9/18/2020 09/18/2020
Misc
Corrective Action Required
09/15/2020
9/18 - INSPECTION DENIED, MAINTAIN EROSION CONTROL AT FRONT OF LOT AND CLEAN MUD/GRAVEL AT STREET BEFORE RESCHEDULING INSPECTION - EC#2 per plans - Secure electrical box at front porch - Truss bracing per plans OK to Insulate Do not rock until approved reinspection
Erosion Control Inspection Residential Failed 9/18/2020 9/18/2020 09/18/2020
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
09/18/2020
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. MAINTAIN EROSION CONTROL AT FRONT OF LOT AND CLEAN MUD/GRAVEL IN STREET
All Rough Inspection - Residential Passed 9/23/2020 9/23/2020 09/23/2020
Misc
Resolved
09/23/2020
Driveway Inspection Partial 9/30/2020 09/30/2020
Misc
Informational
09/30/2020
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Sidewalk Inspection Partial 9/30/2020 09/30/2020
Misc
Informational
09/30/2020
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Driveway Inspection Passed 10/7/2020 10/7/2020 10/12/2020
Misc
Informational
09/30/2020
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Sidewalk Inspection Passed 10/7/2020 10/7/2020 10/12/2020
Misc
Informational
09/30/2020
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Occupancy Inspection - Codes Residential Failed 12/8/2020 12/8/2020 12/08/2020
Misc
Corrective Action Required
12/08/2020
-Resolve outstanding inspection fee(s) before final c of o -cover/protect NM at kitchen exhaust hood -label dedicated receptacles in garage and unfinished basement as not a GFCI protected -Handrail required at basement stairs -Mark breaker locations at main service panel -AFCI protection per code E3902.16 -B vent for furnace/hot water requires 1” clearance, address NM on b vent -Guardrail required at front porch, more than 30” from grade -Security light required at backyard -Complete final grade and sod -seal around exterior light fixtures -seal all penetrations in siding, seal along top of AC disconnect and meter can -splash blocks at all downspout and sump pump discharge locations, minimum 36” distance from foundation
Occupancy Inspection - Codes Residential Failed 12/11/2020 12/11/2020 12/11/2020
Misc
Corrective Action Required
12/08/2020
-Handrail required at basement stairs -Complete final grade and sod -seal around exterior light fixtures -seal all penetrations in siding, seal along top of AC disconnect and meter can -splash blocks at all downspout and sump pump discharge locations, minimum 36” distance from foundation
Occupancy Inspection - Codes Residential Failed 12/18/2020 12/18/2020 12/18/2020
Misc
Corrective Action Required
12/11/2020
-Complete final grade and sod -seal around exterior light fixtures -seal all penetrations in siding, seal along top of AC disconnect and meter can -splash blocks at all downspout and sump pump discharge locations, minimum 36” distance from foundation
Occupancy Inspection - Codes Residential Temporary C of O 12/21/2020 12/21/2020 12/21/2020
Misc
Corrective Action Required
12/18/2020
-Complete final grade and sod -seal around exterior light fixtures -seal all penetrations in siding, seal along top of AC disconnect and meter can -splash blocks at all downspout and sump pump discharge locations, minimum 36” distance from foundation OK FOR TCO - TCO EXPIRES 1/4/21
Erosion Control Inspection Residential Failed 1/25/2021 1/25/2021 01/25/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
01/25/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
01/25/2021
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. -MAINTAIN SILT FENCE AT FRONT OF LOT, -CLEAN MUD AND GRAVEL FROM STREET
Occupancy Inspection - Codes Residential Failed 4/7/2021 4/7/2021 04/07/2021
Misc
Corrective Action Required
12/21/2020
-Submit revised plot plan with retaining wall at back of house and changes to lot drainage -seal penetration in siding, east side of house near AC
Plot Plan Inspection Passed 5/6/2021 05/06/2021
Occupancy Inspection - Codes Residential Full C of O 5/6/2021 5/6/2021 05/06/2021
Documents & Images
Date Uploaded File Type Document Name
04/01/2020 Scope of Work SCOPE OF WORK
04/01/2020 400145
04/03/2020 Plot Plan Approved Plot Plan
04/03/2020 Plans Approved House Plans
04/03/2020 Receipt Receipt for transaction:2020-001387
04/03/2020 Letter DS Building Permit
04/03/2020 Plans Approved 2nd Floor Truss Layout
04/03/2020 Plans Approved 1st Floor Truss Layout
04/03/2020 Drawing Approved Truss Package
04/30/2020 Letter INSPECTION SUMMARY
05/22/2020 Letter INSPECTION SUMMARY
06/08/2020 Letter INSPECTION SUMMARY
06/18/2020 Letter INSPECTION SUMMARY
06/25/2020 Letter INSPECTION SUMMARY
08/11/2020 Letter INSPECTION SUMMARY
08/13/2020 Letter INSPECTION SUMMARY
08/13/2020 Letter INSPECTION SUMMARY
08/13/2020 Letter INSPECTION SUMMARY
08/13/2020 Letter INSPECTION SUMMARY
08/18/2020 Letter INSPECTION SUMMARY
09/14/2020 Letter INSPECTION SUMMARY
09/15/2020 Letter INSPECTION SUMMARY
09/18/2020 Letter INSPECTION SUMMARY
09/18/2020 Letter INSPECTION SUMMARY
09/23/2020 Letter INSPECTION SUMMARY
09/30/2020 Letter INSPECTION SUMMARY
09/30/2020 Letter INSPECTION SUMMARY
10/12/2020 Letter INSPECTION SUMMARY
10/12/2020 Letter INSPECTION SUMMARY
12/08/2020 Letter INSPECTION SUMMARY
12/08/2020 Receipt Receipt for transaction:2020-007913
12/11/2020 Letter INSPECTION SUMMARY
12/18/2020 Letter INSPECTION SUMMARY
12/21/2020 Letter Codes Temporary Certificate of Occupancy
12/21/2020 Letter Codes Temporary Certificate of Occupancy
01/25/2021 Letter INSPECTION SUMMARY
04/07/2021 Letter INSPECTION SUMMARY
05/05/2021 Plot Plan Approved As Graded Plot Plan
05/06/2021 Letter INSPECTION SUMMARY
05/06/2021 Letter Field Certificate of Occupancy
05/06/2021 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home