Permit Application Status

PRRES20181488


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20181488
Building Permit - Residential
Certificate of Occupancy
TRAILS OF PARK RIDGE LLC
NEW SINGLE FAMILY
NEW HOUSE FINISHED AND UNFINISHED BASEMENT COVERED DECK
05/15/2018
05/22/2018
07/01/2019
Locations
Contacts
TRAILS OF PARK RIDGE LLC, Address:3170 NE CARNEGIE DR STE 400  
WYSS HOME BUILDING LLC, Address:PO BOX 6620, Phone:(816) 820-0142  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
ROBERTSON PLUMBING LLC, Address:PO BOX 165, Phone:(816) 781-9340  
MIKE BRYANT HEATING & COOLING , Address:1711 E 123RD , Phone:(913) 441-7807  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 05/17/2018 05/17/2018
Steve Conrick
Residential Plan Review Rejected 05/17/2018 05/15/2018
Brandon Kalwei
07 Identify emergency escape openings from bedrooms
Corrective Action Required
05/15/2018

Identify emergency escape openings from bedrooms and basement(s). (IRC Section R310 as amended per Ordinance) Master bedroom egress not labled
10 Combustion air
Corrective Action Required
05/15/2018

Provide combustion air calculations and specify transfer air grilles for fuel burning appliances located in confined space(s). (IRC Chapter 17 and Section G2407)
Misc
Corrective Action Required
05/15/2018

Please provide address on construction drawings
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $913.12 $913.12 Paid 05/22/2018
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 05/22/2018
8331401-Water Tap Fee $3,343.00 $3,343.00 Paid 05/22/2018
8350015-Water Meter Fee $431.83 $431.83 Paid 05/22/2018
8331507-Sewer Connection Fee $360.00 $360.00 Paid 05/22/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Failed 6/5/2018 (3:00) 6/5/2018 at 2:20 PM 06/05/2018
Misc
Corrective Action Required
06/05/2018
NO EROSION CONTROL. INSPECTION DENIED
Erosion Control Inspection Residential Failed 6/5/2018 06/05/2018
DCM5 ESC INSP DENIED
Corrective Action Required
06/05/2018
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION.
Footing Inspection - Residential Passed 6/6/2018 at 12:45 PM 06/06/2018
Misc
Resolved
06/06/2018
NO EROSION CONTROL. INSPECTION DENIED
Piers/Caissons Inspection - Residential Passed 6/15/2018 6/15/2018 at 9:00 AM 06/15/2018
Erosion Control Inspection Residential Failed 7/24/2018 07/24/2018
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
06/05/2018
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Sewer Service Inspection - R Passed 7/24/2018 at 1:35 PM 07/24/2018
Water Service Inspection - R Passed 7/25/2018 at 11:10 AM 07/25/2018
Underslab Plumbing Inspection - Residential Passed 7/27/2018 7/26/2018 at 3:15 PM 07/26/2018
Suspended Slab Inspection Passed 8/9/2018 (8:30) 8/9/2018 at 9:00 AM 08/09/2018
Gas Service Inspection - Residential Failed 11/6/2018 11/6/2018 at 7:15 AM 11/06/2018
Misc
Corrective Action Required
11/06/2018
LSCO 7-608: GAS PIPING PRESSURE TEST BELOW LEE'S SUMMIT 10 PSI REQUIRED MINIMUM.
Gas Service Inspection - Residential Passed 11/16/2018 11/16/2018 11/16/2018
Misc
Corrective Action Required
11/06/2018
LSCO 7-608: GAS PIPING PRESSURE TEST BELOW LEE'S SUMMIT 10 PSI REQUIRED MINIMUM.
Electrical Service Inspection Passed 11/16/2018 11/16/2018 11/16/2018
All Rough Inspection - Residential Failed 11/16/2018 11/16/2018 at 8:15 AM 11/16/2018
Misc
Corrective Action Required
11/16/2018
FRAMING: -Shim gap between garage wall studs and 2” washers -Anchor garage sill plates per code -Fb kitchen arch wall space from roof; Fb the double stud wall space at max ten ft interval ; Fb the laundry/toilet wall from roof -Reinforce hinge points at rear dining -Brace pantry and powder bathroom wall per plan -Staple the fireblocking insulation in place without the paper facing -Add another stud support(3 total) for lvl beam at stair/garage wall -Missing ceiling joist hangers above stair -Support valley rafters at ridge above great room -Brace ends of lvl beam above great room -Security blocking for master bedroom exterior door -Provide vapor barrier fabric at master bedroom -Hangers for laundry ceiling joists -Nail corner studs per code full height. Use ladder MECHANICAL: -Provide min 3” top clearance from fireplace vent to combustible PLUMBING: -Protect laundry plumbing and 3” vent stack with BOCA plate **OK TO INSULATE
All Rough Inspection - Residential Passed 11/20/2018 11/20/2018 at 8:00 AM 11/20/2018
Misc
Resolved
11/20/2018
FRAMING: -Shim gap between garage wall studs and 2” washers -Anchor garage sill plates per code -Fb kitchen arch wall space from roof; Fb the double stud wall space at max ten ft interval ; Fb the laundry/toilet wall from roof -Reinforce hinge points at rear dining -Brace pantry and powder bathroom wall per plan -Staple the fireblocking insulation in place without the paper facing -Add another stud support(3 total) for lvl beam at stair/garage wall -Missing ceiling joist hangers above stair -Support valley rafters at ridge above great room -Brace ends of lvl beam above great room -Security blocking for master bedroom exterior door -Provide vapor barrier fabric at master bedroom -Hangers for laundry ceiling joists -Nail corner studs per code full height. Use ladder MECHANICAL: -Provide min 3” top clearance from fireplace vent to combustible PLUMBING: -Protect laundry plumbing and 3” vent stack with BOCA plate **OK TO INSULATE
Driveway Inspection Partial 3/21/2019 3/21/2019 03/21/2019
Misc
Informational
03/21/2019
Pre-inspection of contractor forms and materials passed.
Erosion Control Inspection Residential Passed 05/07/2019
DCM2 ESC DEFICIENT INSTALLATION
Resolved
05/07/2019
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Occupancy Inspection - Codes Residential Failed 5/7/2019 5/7/2019 at 8:10 AM 05/07/2019
Misc
Corrective Action Required
05/07/2019
-Driveway not approved on record -Lawn irrigation permit -Install sump pump discharge pipe -Install security strike plate at deck door and nail embedded metal brace into studs -Secure cooktop FMC raceway per code -Anchor columns -Secure PEX water lines at mid-wall height -Lag deck ledger board -Landing at bedroom escape window and ladder
Occupancy Inspection - Codes Residential Temporary C of O 5/14/2019 5/14/2019 at 8:50 AM 05/14/2019
Misc
Corrective Action Required
05/07/2019
-Driveway not approved on record -Lawn irrigation permit
Driveway Inspection Passed 5/14/2019 (A.M.) 5/14/2019 05/14/2019
Misc
Informational
03/21/2019
Pre-inspection of contractor forms and materials passed.
Misc
Informational
05/14/2019
Driveway passed inspection.
Occupancy Inspection - Codes Residential Full C of O 7/1/2019 at 8:10 AM 07/01/2019
Misc
Resolved
07/01/2019
-Lawn irrigation permit
Documents & Images
Date Uploaded File Type Document Name
05/15/2018 Letter Codes Residential Plan Review
05/22/2018 Receipt Receipt for transaction: 2018-002902
05/22/2018 Letter Codes Building Permit
05/22/2018 Plot Plan DOC052218-004
06/05/2018 Letter Inspection Summary
06/06/2018 Letter Inspection Summary
06/15/2018 Letter Inspection Summary
07/24/2018 Letter Inspection Summary
07/25/2018 Letter Inspection Summary
07/26/2018 Letter Inspection Summary
08/09/2018 Letter Inspection Summary
11/06/2018 Letter Inspection Summary
03/21/2019 Letter INSPECTION SUMMARY
03/21/2019 Letter INSPECTION SUMMARY
05/07/2019 Letter INSPECTION SUMMARY
05/07/2019 Letter INSPECTION SUMMARY
05/14/2019 Letter Codes Temporary Certificate of Occupancy
05/14/2019 Letter INSPECTION SUMMARY
07/01/2019 Letter Codes Final Certificate of Occupancy
07/01/2019 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home