Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 10/31/2017
Kim Brennan
North arrow and scale
Resolved
10/31/2017

The plot plan must be submitted on either (1) 81/2” x 11”, (2) 81/2”x 14”, or (3) 11” x 17” paper. All information on the plot plan must be drawn to scale. Scale must be 1” = 10’, 20’, or 30’; smaller scales that are multiples of the preceding scales may be used if necessary to represent large sites. All information on the plot plan must be clearly legible.) *Plot plan is not to scale.
Property boundary
Resolved
10/31/2017

Property boundary distances and bearings, as shown on the recorded plat, must be provided on the plot plan. * Can you please double check the property boundarys they seem off.
Misc
Informational
10/31/2017

*Can you please submit two copies or send a pdf over and I will print off two copies with the corrections.
Spot elevations
Resolved
10/31/2017

Spot elevations and/or drainage flow arrows shall be provided throughout the lot. *Can you provide some spot elevations in the driveway.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Other $215.67 $215.67 Paid 11/03/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Not Ready 11/27/2017 (9:00) 11/27/2017 at 9:25 AM 11/27/2017
Misc
Corrective Action Required
11/27/2017
VERTICAL RE-BAR DRIVEN INTO TRENCH BOTTOM
Footing Inspection - Residential Failed 11/27/2017 (11:00) 11/27/2017 at 11:15 AM 11/27/2017
Misc
Corrective Action Required
11/27/2017
VERTICAL RE-BAR DRIVEN INTO TRENCH BOTTOM
Footing Inspection - Residential Passed 11/27/2017 at 11:55 AM 11/27/2017
Misc
Resolved
11/27/2017
VERTICAL RE-BAR DRIVEN INTO TRENCH BOTTOM
Piers/Caissons Inspection - Residential Not Ready 11/29/2017 11/29/2017 at 8:10 AM 11/29/2017
Misc
Corrective Action Required
11/29/2017
LSCO SEC 7-142; IBC 106: PERMIT DRAWINGS NOT FOUND ON SITE. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT PRINTS.
Piers/Caissons Inspection - Residential Passed 11/29/2017 (9:15) 11/29/2017 at 9:25 AM 11/29/2017
Misc
Resolved
11/29/2017
LSCO SEC 7-142; IBC 106: PERMIT DRAWINGS NOT FOUND ON SITE. NO INSPECTIONS WITHOUT CITY-STAMPED PERMIT PRINTS.
All Rough Inspection - Residential Partial 12/22/2017 12/22/2017 12/22/2017
Misc
Corrective Action Required
12/22/2017
Stud under carport rafter at wall to floor for bearing. ok to cover exterior.
Final Inspection - Residential Not Ready 1/8/2018 1/8/2018 at 3:45 PM 01/08/2018
Misc
Corrective Action Required
01/08/2018
NOT READY FOR FINAL. ILLEGAL BURN BARREL NEEDS TO BE REMOVED.
All Rough Inspection - Residential Failed 1/26/2018 at 11:10 AM 01/26/2018
Misc
Corrective Action Required
01/26/2018
ANCHORAGE OF EXTERIOR WALL SILL PLATE IBC 2308.6 / IRC 403.1.6: ONE BOLT WITHIN 12" OF ENDS OF EACH PIECE; BOLTS CENTERED IN PLATE - NOT AT EDGE AS SOME ARE INSTALLED; PLATE WASHERS REQUIRED PER DRAWING NOTES. DO NOT INSULATE OR OTHERWISE COVER WALLS BEFORE SILL PLATE ANCHORAGE IS APPROVED.
All Rough Inspection - Residential Partial 3/13/2018 at 12:40 PM 03/13/2018
Misc
Resolved
03/13/2018
ANCHORAGE OF EXTERIOR WALL SILL PLATE IBC 2308.6 / IRC 403.1.6: ONE BOLT WITHIN 12" OF ENDS OF EACH PIECE; BOLTS CENTERED IN PLATE - NOT AT EDGE AS SOME ARE INSTALLED; PLATE WASHERS REQUIRED PER DRAWING NOTES. DO NOT INSULATE OR OTHERWISE COVER WALLS BEFORE SILL PLATE ANCHORAGE IS APPROVED.
Corrective Action Required
03/13/2018
IBC 718.2; IRC R502.13; R602.8 FIREBLOCKING: IN WOOD-FRAMED STRUCTURE FIRE-BLOCK ALL LEVEL-TO-LEVEL OPENINGS AND INTERSECTIONS OF VERTICAL AND HORIZONTAL CAVITIES. ANY HOLES OR DISCONTINUITIES IN TOP & BOTTOM PLATES; INTERFACES OF WALLS WITH FLOOR/CEILING. ABOVE PERTAINS TO LOWER LEVEL AND, IF TO RECEIVE DRYWALL, UPPER LEVEL AS WELL. DO NOT INSULATE OR OTHERWISE COVER WALLS BEFORE SILL PLATE ANCHORAGE IS APPROVED. ANCHOR BOLTS OK; ELECTRICAL WIRING OK
All Rough Inspection - Residential Partial 3/13/2018 at 1:35 PM 03/13/2018
All Rough Inspection - Residential Passed 3/15/2018 3/15/2018 at 9:55 AM 03/15/2018
Electrical Service Inspection Passed 3/15/2018 at 10:05 AM 03/15/2018
Investigation Inspection Complete 4/3/2018 04/03/2018
All Rough Inspection - Residential Passed 4/4/2018 at 4:40 PM 04/04/2018
Final Inspection - Residential Passed 4/16/2018 at 3:20 PM 04/16/2018
Misc
Resolved
04/04/2018
NOT READY FOR FINAL. ILLEGAL BURN BARREL NEEDS TO BE REMOVED.
Documents & Images
Date Uploaded File Type Document Name
10/17/2017 Letter Codes Residential Plan Review
11/03/2017 Receipt Receipt for transaction: 2017-007106
11/03/2017 Letter Codes Building Permit
11/03/2017 Plot Plan DOC110317-014
11/27/2017 Letter Inspection Summary
11/29/2017 Letter Inspection Summary
11/29/2017 Letter Inspection Summary
12/22/2017 Letter Inspection Summary
01/26/2018 Letter Inspection Summary
02/01/2018 Letter Codes Building Permit
03/13/2018 Letter Inspection Summary
03/15/2018 Letter Inspection Summary
04/04/2018 Letter Inspection Summary
04/16/2018 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home