PRRES20143037
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
HOUSE W/ COVERED & UNCOVERED DECK - 2 STORY - FINISHED WALKOUT BASEMENT *FLOOR TRUSSES
10/28/2014
11/04/2014
11/11/2016
Locations
Contacts
RM STANDARD & CO, Address:11233 NALL AVE STE 130, Phone:(913) 469-5585  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
SUPERIOR ELECTRICAL CONSTRUCTION, Address:PO BOX 3137, Phone:(816) 356-1163  
AXIOM PLUMBING LLC, Address:5703 CEDAR ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 10/30/2014 11/03/2014
Tara Mitchell
Plot Plan Review (P&D) Approved 10/30/2014 10/31/2014
Christina Stanton
Misc
Corrective Action Required
10/31/2014

FOUNDATION ONLY! (SEE E-MAILS ATTACHED TO PLOT PLAN.)
FOUNDATION ONLY! (SEE E-MAILS ATTACHED TO PLOT PLAN.)
Plot Plan Review Approved 10/30/2014 10/30/2014
Gene Williams, P.E.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $3,321.99 $3,321.99 Paid 11/04/2014
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 11/04/2014
8331507-Sewer Connection Fee $1,200.00 $1,200.00 Paid 11/04/2014
8331401-Water Tap Fee $8,528.00 $8,528.00 Paid 11/04/2014
8350015-Water Meter Fee $532.00 $532.00 Paid 11/04/2014
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Partial 1/15/2015 at 12:00 AM 01/15/2015
Misc
Corrective Action Required
01/15/2015
FOOTING WAS INSPECTED BY HD ENGINEERING AND LETTER WAS SUBMITTED TO THE CITY FOR RECORD; HOWEVER, THE RE-ROUTE OF THE STORM DRAIN SHALL BE INSPECTED AND APPROVED BY PUBLIC WORKS PRIOR TO ISSUANCE OF ANY TYPE OF OCCUPANCY
Foundation Inspection - Residential Passed 1/15/2015 (1:00) 1/15/2015 at 12:00 AM 01/15/2015
Foundation Inspection - Residential Passed 1/22/2015 (3:30) 1/22/2015 at 12:00 AM 01/22/2015
Suspended Slab Inspection Passed 3/30/2015 (1:00) 3/30/2015 at 12:00 AM 03/30/2015
Storm - Pipe Passed 3/23/2015 at 3:00 AM 04/03/2015
Underslab Plumbing Inspection - Residential Failed 4/3/2015 at 12:00 AM 04/03/2015
Misc
Corrective Action Required
04/03/2015
-PLUMBING IS LOCATED UNDER THE 45 DEGREEE PLANES FROM THE COLUMN PADS. IN THESE AREAS, FILL IN WITH AB3 OR CONCRETE TO PROTECT THE UNDERMINED PADS
Underslab Plumbing Inspection - Residential Passed 6/4/2015 at 12:00 AM 06/04/2015
Misc
Resolved
06/04/2015
-PLUMBING IS LOCATED UNDER THE 45 DEGREEE PLANES FROM THE COLUMN PADS. IN THESE AREAS, FILL IN WITH AB3 OR CONCRETE TO PROTECT THE UNDERMINED PADS
All Rough Inspection - Residential Not Ready 10/1/2015 10/1/2015 at 12:00 AM 10/01/2015
Gas Service Inspection - Residential Passed 10/1/2015 at 12:00 AM 10/01/2015
All Rough Inspection - Residential Failed 10/2/2015 at 12:00 AM 10/02/2015
Misc
Corrective Action Required
10/02/2015
FRAMING: -INSTALL COLLAR TIES FOR THE MAIN RIDGE -FIREBLOCKING: FB THE MASTER SHOWER WALL SPACE FROM ROOF; FB VERTICAL WALL SPACE FROM HORIZONTAL SPACE AT FRONT DINING; FB LENAI WOOD-BURNING FIREPLACE SPACE FROM ROOF; FB SPACE AT GARAGE STEPS FROM ROOF; FB THE DOUBLE STUD WALL AT BEDROOM FROM ROOF; FB BASEMENT LIVING RM FIREPLACE SPACE FROM CEILING/FURDOWN SPACE; FB BASEMENT EXERCISE RM FIREPLACE SPACE FROM CEILING/FURDOWN SPACE -INSTALL HANGER FOR THE LVL CONNECTION ABOVE THE LENAI WOOD-BURNING FIREPLACE -MAKE SURE THE MAXIMUM STAIR RISER HEIGHT DIFFERENCE OF THE ENTRY CURVED STAIR BE NO MORE THAN 3/8". ELECTRICAL: -MAKE SURE ALL THE BATH VANITY RECEPTACLES ARE WITHIN 3 FT OF THE SINK BASINS -LOWER THE FRONT OFFICE CAN LIGHTS TO CEILING LEVEL -ALL BASEMENT UNDERSLAB CIRCUITS CONDUCTORS MUST BE RATED FOR WET LOCATION -ALL THE FEEDERS THAT ARE INSTALLED IN THE ATTIC SPACE SHALL BE DE-RATED FOR TEMPERATURE PLUMBING: -INSULATE THE WATER LINES ABOVE MASTER BATH SHOWER -PROTECT ALL PLUMBING AT THE BOTTOM WALL SOLE PLATE WITH STEEL PLATES THAT PROVIDE EXTRA 2" OF PROTECTION BEYOND THE SOLE PLATE-THROUGHOUT HOUSE. -COMPLETE ALL PLUMBING TO BATH FIXTURES -PROTECTION OF THE CSST GAS LINE IS REQUIRED WHEN INSTALLED WITHIN 3" OF THE CEILING SURFACE ABOVE BASEMENT -PROVIDE ACCESS TO SEWER STACK CLEANOUT INSIDE THE BASEMENT LIVING RM FIREPLACE -COMPLETE & INSTALL THE PLUMBING INSIDE WALL SPACE (CRAFT RM) **OK TO INSULATE **BASEMENT NOT COMPLETED. SOME DEFICIENCIES IN THE BASEMENT ARE ALSO INCLUDED
Electrical Service Inspection Failed 10/2/2015 at 12:00 AM 10/02/2015
Misc
Corrective Action Required
10/02/2015
-NEC 250.24 REQUIRES THAT THE GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTS TO THE BUS THAT THE SERVICE GROUNDED CONDUCTOR IS CONNECTED TO; OR INSTALL A #4 COPPER MAIN JUMPER FROM THE GROUNDING BAR, WHERE THE GEC AND EQUIPMENT GROUNDING CONDUCTORS ARE CONNECTED TO, TO THE SERVICE GROUNDED CONDUCTOR BUS
All Rough Inspection - Residential Partial 10/8/2015 10/8/2015 at 12:00 AM 10/08/2015
Misc
Corrective Action Required
10/02/2015
FRAMING: -FIREBLOCKING: FB BASEMENT LIVING RM FIREPLACE SPACE FROM CEILING/FURDOWN SPACE ELECTRICAL: -ALL BASEMENT UNDERSLAB CIRCUITS CONDUCTORS MUST BE RATED FOR WET LOCATION -ALL THE FEEDERS THAT ARE INSTALLED IN THE ATTIC SPACE SHALL BE DE-RATED FOR TEMPERATURE PLUMBING: -PROTECTION OF THE CSST GAS LINE IS REQUIRED WHEN INSTALLED WITHIN 3" OF THE CEILING SURFACE ABOVE BASEMENT **OK TO ROCK 1ST AND 2ND FLOOR **BASEMENT NOT COMPLETED.
Electrical Service Inspection Passed 10/20/2015 10/20/2015 at 12:00 AM 10/20/2015
Misc
Resolved
10/20/2015
-NEC 250.24 REQUIRES THAT THE GROUNDING ELECTRODE CONDUCTOR (GEC) CONNECTS TO THE BUS THAT THE SERVICE GROUNDED CONDUCTOR IS CONNECTED TO; OR INSTALL A #4 COPPER MAIN JUMPER FROM THE GROUNDING BAR, WHERE THE GEC AND EQUIPMENT GROUNDING CONDUCTORS ARE CONNECTED TO, TO THE SERVICE GROUNDED CONDUCTOR BUS
All Rough Inspection - Residential Passed 10/29/2015 10/29/2015 at 12:00 AM 10/29/2015
Misc
Resolved
10/29/2015
FRAMING: -FIREBLOCKING: FB BASEMENT LIVING RM FIREPLACE SPACE FROM CEILING/FURDOWN SPACE ELECTRICAL: -ALL BASEMENT UNDERSLAB CIRCUITS CONDUCTORS MUST BE RATED FOR WET LOCATION -COMPLETE BASEMENT ELECTRICAL. MAKE SURE THAT ALL RECEPTACLES SHALL BE MINIMUM 6 FT FROM THE HOT TUB IN EXERCISE RM AND SWITCH MINIMUM 5 FT HORIZONTALLY FROM INSIDE WALL OF TUB PLUMBING: -PROTECTION OF THE CSST GAS LINE IS REQUIRED WHEN INSTALLED WITHIN 3" OF THE CEILING SURFACE ABOVE BASEMENT **OK TO ROCK 1ST AND 2ND FLOOR
Sewer Service Inspection - R Passed 3/1/2016 (11:30) 3/1/2016 03/01/2016
Driveway Inspection Passed 6/9/2016 06/09/2016
Footing Inspection - Residential Passed 10/27/2016
Misc
Resolved
10/27/2016
FOOTING WAS INSPECTED BY HD ENGINEERING AND LETTER WAS SUBMITTED TO THE CITY FOR RECORD; HOWEVER, THE RE-ROUTE OF THE STORM DRAIN SHALL BE INSPECTED AND APPROVED BY PUBLIC WORKS PRIOR TO ISSUANCE OF ANY TYPE OF OCCUPANCY
Occupancy Inspection - Codes Residential Failed 10/27/2016 10/28/2016 10/28/2016
Misc
Corrective Action Required
10/27/2016
-FINAL GRADE, SOD -WATER SERVICE WAS NOT INSPECTED&APPROVED ON RECORD -OBTAIN IRRIGATION PERMIT -PAINT GAS SERVICE PIPING -AC UNITS: SECURE ALL WHIPS WITHIN 12" OF DISCONNECTS; MAKE SURE THAT THE BREAKER SIZE IS PER AC LABE. LABEL EACH AC WITH NUMBER SO I CAN CHECK (AC1, AC2, ETC) -LUMINARE INSIDE CLOTHES CLOSET MUST BE ENCLOSED-LAMP TYPE. MASTER CLOSET -RECEPTACLE LOCATED IN MASTER BATH (NEAR CLOSET) MUST BE GFCI -ALL OUTDOOR RECEPTACLES FOR TV AND GRILLS MUST BE GFCI-PROTECTED -INSTALL LISTED OUTDOOR SWITCH&RECEPTACLES -GROUT GAS LINE PENETRATION INTO CDECK FIREPLACE FIERBOX -SUPPORT RECEPTACLE YOKE NEAR DECK FIREPLACE -ALL RECEPTACLES SERVING KITCHEN COUNTERTOP (MAIN FLOOR KITCHEN AT PULL-OUT SHELF, BASEMENT KITCHEN NEAR WET BAR) MUST BE GFCI-PROTECTED -RECEPTACLE NEAR PANTRY SINK AND OUTSIDE PANTRY MUST BE GFCI-PROTECTED -INSTALL BREAKER LOCK SUPPLYING KITCHEN HOOD -LOOP AND SECURE THE DISH WASHER DRAIN UP (BOTH MAIN FL AND BASEMENT KITCHENS) -INSTALL WATER ANTI-HAMMERING ARRESTORS FOR DISH WASHER WATER SUPPLIES -ALL GARAGE DOORS OPENING INTO THE DWELLING MUST BE SELF-CLOSING -INSTALL BREAKER LOCKS FOR GARAGE HEATERS -INSTALL SPARK RINGS FOR RECEPTACLES IN GARAGE -WEST BED AFCI BREAKER NOT TRIPPING -INSTALL BREAKER LOCK FOR OVEN -SECURELY FASTEN SE CABLE AT LEAST EVERY 4.5 FT -INSTALL FACE PLATE FOR ATTIC FURNACE SWITCH ABOVE MASTER BED -INSTALL LUMINAIRE INSIDE THE GUEST BED HIDDEN CLOSET -VERIFY THAT THE SMOKE ALARM OUTSIDE EACH BEDROOM AREA IS ALSO CO DETECTOR&ALARM -ALL RECEPTACLES IN UNFINISHED PORTIONS OF BASEMENT AND UNDER GARAGE MUST BE GFCI-PROTECTED OR BE DEDICATED -LABEL ALL BREAKERS -INSTALL A DISCONNECT FOR THE HYDROTUB MOTOR -INSTALL SPARK RING FOR BASEMENT BATH SINK RECEPTACLE (BATH NEAR GARAGE)
Water Service Inspection - R Passed 11/11/2016
Occupancy Inspection - Codes Residential Temporary C of O 11/11/2016 11/11/2016 11/11/2016
Misc
Corrective Action Required
10/28/2016
-RE-GRADE AROUND THE WATER METER TO SLOPE AWAY AND RAISE WATER SERVICE TO FINAL GRADE
Occupancy Inspection - Codes Residential Full C of O 11/11/2016
Misc
Resolved
11/11/2016
-RE-GRADE AROUND THE WATER METER TO SLOPE AWAY AND RAISE WATER SERVICE TO FINAL GRADE
Documents & Images
Date Uploaded File Type Document Name
11/04/2014 Letter Codes Building Permit
11/04/2014 Receipt Receipt for transaction: 2014-002131
12/02/2014 Engineer Report/Study DOC120214
12/29/2014 Engineer Report/Study DOC122914-006
01/15/2015 Letter Inspection Summary
01/22/2015 Letter Inspection Summary
03/30/2015 Letter Inspection Summary
06/04/2015 Letter Inspection Summary
10/01/2015 Letter Inspection Summary
10/02/2015 Letter Inspection Summary
10/08/2015 Letter Inspection Summary
10/20/2015 Letter Inspection Summary
10/29/2015 Letter Inspection Summary
03/01/2016 Letter Inspection Summary
10/28/2016 Letter Inspection Summary
11/11/2016 Letter Codes Temporary Certificate of Occupancy
11/11/2016 Letter Field Certificate of Occupancy
11/14/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home