Summary
PRCOM20255330
Building Permit - Commercial
Issued
CITY OF LEES SUMMIT
NEW OTHER (COMMERCIAL)
LEE'S SUMMIT JOINT OPERATIONS FACILITY - NEW TELECOMMUNICATIONS TOWER AND SHELTER BUILDING
12/05/2025
01/15/2026
06/14/2026
Locations
Contacts
HAYDEN TOWER SERVICE, Address:2836 NW HWY 24, Phone:(785) 232-1840  
Kim Bailey - Hayden Tower Co, Phone:(785) 213-6921  
LESSER ELECTRIC INC, Address:P O BOX 8244, Phone:(785) 232-5161  
CITY OF LEES SUMMIT, Address:207 SW MARKET ST  
SELECTIVE SITE CONSULTANTS,INC, Address:7171 W 95TH ST. SUITE 600  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 01/12/2026 01/15/2026
Joe Frogge
Building Plan Review Approved 01/12/2026 01/14/2026
Joe Frogge
Misc
Resolved
01/14/2026

Engineer's seal required on base plate plans
Fire Plan Review Approved 01/12/2026 01/08/2026
Craig Hill
Final Development Plan Review Approved 12/29/2025 12/29/2025
Grant White
Building Plan Review Rejected 12/19/2025 12/16/2025
Joe Frogge
Final Development Plan
Corrective Action Required
12/16/2025

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational.
IBC 502.1 - Address Identification
Corrective Action Required
12/16/2025

2018 IBC 502.1 Address identification. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be a minimum of 4 inches high with a minimum stroke width of ½ inch. Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building address cannot be viewed from the public way, a monument, pole or other approved sign or means shall be used to identify the structure. Address identification shall be maintained. Action required: Comment is informational. The address assigned to this project is 2 NE Tudor Rd.
IBC 1809.5 Frost protection - foundation
Corrective Action Required
12/16/2025

2018 IBC 1809.5 Frost protection. Except where otherwise protected from frost, foundations and other permanent supports of buildings and structures shall be protected from frost by one or more of the following methods: 1. Extending below the frost line of the locality; 2. Constructing in accordance with ASCE 32; or 3. Erecting on solid rock. (see code section for exceptions) Shallow foundations shall not bear on frozen soil unless such frozen condition is of a permanent character. Action required: Amend sheets A-4.0 in Hayden Tower plans & S-1 in Shelter Drawings to show minimum frost protection depth of 36". (measured to grade, not top of slab.)
Misc
Corrective Action Required
12/16/2025

Inadequate information. Action required: Provide detail as to how tower will be anchored to its base.
IBC 1803.1 General - geotech
Corrective Action Required
12/16/2025

2018 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Geotech report must be sealed/signed by engineer of record and must not be marked as 'draft.'
Gen - Plan submittals 2018 codes
Corrective Action Required
12/16/2025

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Amend Code Compliance block on sheet T-1 to show correct code cycle years.
Licensed Contractors Rejected 12/19/2025 12/16/2025
Joe Frogge
LC - General Contractor
Corrective Action Required
12/16/2025

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact.
LC - MEP Subs
Corrective Action Required
12/16/2025

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved 12/19/2025 12/16/2025
Craig Hill
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Commercial $800.00 $800.00 Paid 01/15/2026
Parks Impact Fee Non-Residential - Zone 4 $0.20 $0.20 Paid 01/15/2026
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Pending
Piers/Caissons Inspection - Commercial Pending
Electrical Service Inspection Pending
Gas Service Inspection - Commercial Pending
Miscellaneous Inspection Pending
Rough Electrical Inspection - Commercial Pending
Misc
Informational
02/04/2026
**Ground rods and conductors for loop at tower
Foundation Inspection - Commercial Pending 2/11/2026
Misc
Corrective Action Required
02/11/2026
Call back in when ready
Footing Inspection - Commercial Partial 2/3/2026 02/03/2026
Misc
Informational
02/03/2026
Footing for tower ok
Rough Electrical Inspection - Commercial Partial 02/04/2026
Misc
Informational
02/04/2026
**Ground rods and conductors for loop at tower
Foundation Inspection - Commercial Failed 2/11/2026 2/11/2026 02/11/2026
Misc
Corrective Action Required
02/11/2026
Call back in when ready
Footing Inspection - Commercial Passed 02/11/2026
Misc
Resolved
02/11/2026
Footing for tower ok
Underground Electrical Inspection - Commercial Passed 2/18/2026 2/18/2026 02/18/2026
Documents & Images
Date Uploaded File Type Document Name
12/05/2025 Application Form APPLICATION
12/05/2025 Letter Final Development Plan - PL2025140 - Approval Letter 12_02_25
12/05/2025 Plans Hayden Tower Lee's Summit - CD Rev 0 12_03_25 PDF
12/05/2025 Plans Tower & Foundation Structural Design Package
12/05/2025 Engineer Report/Study Geotechnical Report
12/05/2025 Plans Shelter Drawings
12/16/2025 Letter DS P/R Corrections Document
01/05/2026 Letter Hayden Tower Lee's Summit - Response Letter 01_05_25
01/05/2026 Plans Hayden Tower Lee's Summit - CD Rev 1 12_18_25 PDF
01/05/2026 Engineer Report/Study Geotech Report S&S
01/05/2026 Plans Shelter Drawings Rev 1
01/05/2026 Plans Base Plate Drawings
01/14/2026 Letter Hayden Tower Lee's Summit - Response Letter 01_14_25
01/14/2026 Plans Base Plate Drawings v2
01/14/2026 Engineer Report/Study Tower & Foundation Structural Design Package v2
01/14/2026 Plans Tower & Foundation Structural Design Package v2 UNLOCKED
01/14/2026 Plans Base Plate Drawings v2 UNLOCKED
01/14/2026 Approved Plans Approved construction plans
01/15/2026 Receipt Receipt for transaction:2026-000326
01/15/2026 Letter DS Building Permit
02/03/2026 Letter INSPECTION SUMMARY
02/04/2026 Letter INSPECTION SUMMARY
02/11/2026 Letter INSPECTION SUMMARY
02/11/2026 Letter INSPECTION SUMMARY
02/11/2026 Letter INSPECTION SUMMARY
02/18/2026 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home