Permit Application Status

PRCOM20251795


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20251795
Building Permit - Commercial
Issued
MARION RIDGE SAFETY STORAGE LLC
CHANGE OF TENANT
CHANGE OF TENANT FOR NEW ELECTRICAL MATERIAL DISTRIBUTOR
05/02/2025
07/11/2025
12/20/2025
Locations
Contacts
MARION RIDGE SAFETY STORAGE LLC, Address:1120 NW EAGLE RIDGE BLVD  
MID-WEST ASSOCIATED CONTRACTORS CORPORATION, Address:900 NW HUNTER DR STE 25, Phone:(816) 229-6090  
PRO PLATINUM LLC, Address:6116 ALDEN RD, Phone:(913) 908-3512  
VELOCITY ELECTRIC AND AUTOMATION LLC, Address:1704 SW RED FOX CIR, Phone:(816) 215-1514  
Mayes Plumbing Inc, Address:501 South McCleary Road  
Rel Roberts - Mid-West Associated Contractors, Address:900 NW Hunter Drive, Suite 2 South  
MD Design LLC, Address:201 L Street, Phone:(816) 516-4861  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 07/21/2025 07/18/2025
Craig Hill
Misc
Corrective Action Required
07/18/2025

Information Only: For alarm test call (816) 696-1300 one business day before needing the test.
Fire Plan Review Approved 07/10/2025 07/09/2025
Craig Hill
Construction documents for fire alarm systems
Corrective Action Required
07/02/2025

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide deferred submittal for fire alarm system.
Construction documents - Fire protection systems
Corrective Action Required
07/02/2025

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide deferred submittal for fire protection system.
Building Plan Review Approved 07/10/2025 07/09/2025
Joe Frogge
IBC 1606.2 Design dead load - structural
Resolved
07/09/2025

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional load imposed by new condensing units. 6/23/2025 - Report must be sealed/signed by the engineer.
Misc
Resolved
07/09/2025

Inadequate information to complete review. Action required: Provide engineered designs for how racks are attached to floor. 6/23/2025 - Detail must be sealed/signed by the engineer.
Licensed Contractors Approved 07/10/2025 07/09/2025
Joe Frogge
Building Plan Review Rejected 06/25/2025 06/23/2025
Joe Frogge
IBC 1606.2 Design dead load - structural
Corrective Action Required
06/17/2025

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional load imposed by new condensing units. 6/23/2025 - Report must be sealed/signed by the engineer.
Misc
Corrective Action Required
06/17/2025

Inadequate information to complete review. Action required: Provide engineered designs for how racks are attached to floor. 6/23/2025 - Detail must be sealed/signed by the engineer.
Fire Plan Review Approved with Conditions 06/25/2025 06/17/2025
Joe Frogge
Construction documents for fire alarm systems
Corrective Action Required
06/17/2025

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide deferred submittal for fire alarm system.
Construction documents - Fire protection systems
Corrective Action Required
06/17/2025

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide deferred submittal for fire protection system.
Licensed Contractors Approved 06/25/2025 06/17/2025
Joe Frogge
LC - MEP Subs
Resolved
06/17/2025

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. (Unable to locate license for RES Mechanical)
Sprinkler Plan Review Released for Construction 06/13/2025 06/02/2025
Craig Hill
Fire Plan Review Approved with Conditions 06/02/2025 06/02/2025
Craig Hill
Construction documents for fire alarm systems
Corrective Action Required
06/02/2025

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide deferred submittal for fire alarm system.
Construction documents - Fire protection systems
Corrective Action Required
06/02/2025

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide deferred submittal for fire protection system.
Building Plan Review Rejected 06/02/2025 05/30/2025
Joe Frogge
IBC 1606.2 Design dead load - structural
Corrective Action Required
05/30/2025

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional load imposed by new condensing units.
Misc
Corrective Action Required
05/30/2025

Inadequate information to complete review. Action required: Provide engineered designs for how racks are attached to floor.
Licensed Contractors Rejected 06/02/2025 05/30/2025
Joe Frogge
LC - MEP Subs
Corrective Action Required
05/30/2025

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. (Unable to locate license for RES Mechanical)
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $1,000.00 $1,000.00 Paid 07/10/2025
$6,534.00
Industrial/Warehouse Excise Tax Fee $6,534.00 $6,534.00 Paid 07/10/2025
$6,534.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sprinkler - Hydrostatic Test Pending
Sprinkler - Flow Test Pending
Above Ceiling Inspection Pending
Alarm Test Pending
In-wall Inspection Pending
Misc
Corrective Action Required
07/21/2025
Protect plumbing at restroom 113
Underslab Plumbing Inspection - Commercial Passed 7/18/2025 7/17/2025 07/17/2025
In-wall Inspection Failed 7/17/2025 7/17/2025 07/17/2025
Misc
Corrective Action Required
07/17/2025
In-wall not ready. OK to install GB on one side only
In-wall Inspection Partial 7/21/2025 7/21/2025 07/21/2025
Misc
Corrective Action Required
07/17/2025
Protect plumbing at restroom 113
Documents & Images
Date Uploaded File Type Document Name
05/02/2025 Application Form APPLICATION
05/08/2025 Drawing 25_04_08 Ceiling Plan
05/08/2025 Drawing 25_04_08 Floor Plan
05/21/2025 Plans 25_04_29 Permit Submittal
05/21/2025 Drawing Racks
05/21/2025 Letter License Tax Bill
05/30/2025 Drawing M3568-ButlerSupply-2025_05_28 - Sealed - Signed - Flat
05/30/2025 Specifications M3568-ButlerSupply-Calc-All-2025_05_28 - Sealed - Signed - Flat
06/02/2025 Letter DS P/R Corrections Document
06/02/2025 Drawing M3568-ButlerSupply-2025_05_28 - Sealed - Signed - Flat RFC
06/02/2025 Letter Fire (Sprinkler) Plan Review
06/10/2025 Letter 25_06_10 Plan Review Response Letter PRCOM20251795
06/23/2025 Letter DS P/R Corrections Document
07/02/2025 Letter 25_06_30 Plan Review Response Letter PRCOM20251795
07/02/2025 Engineer Report/Study 25_06_30 Stamped Condenser Report
07/02/2025 Plans Racking Plans and Calcs PRCOM20251795
07/07/2025 Plans Butler Supply Battery Calcs_STAMPED
07/07/2025 Plans Butler Supply Fire Alarm_STAMPED
07/09/2025 Plans 25_07_09 Butler Supply Complete Permit Submittal
07/10/2025 Receipt Receipt for transaction:2025-005393
07/13/2025 Approved Plans Approved construction plans
07/14/2025 Letter DS Building Permit
07/17/2025 Letter INSPECTION SUMMARY
07/17/2025 Letter INSPECTION SUMMARY
07/18/2025 Butler Supply Fire Alarm_STAMPED RFC
07/18/2025 Letter Fire (Alarm) Plan Review Notice
07/21/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home