Permit Application Status

PRCOM20242738


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20242738
Building Permit - Commercial
Certificate of Occupancy
NEW TENANT FINISH
JOHNSON STORAGE - OFFICE/RESIDENTIAL MOVING AND STORAGE
05/30/2024
06/26/2024
12/08/2024
10/01/2024
Locations
Contacts
North Oak Safety Storage LLC, Address:1120 NW Eagle Ridge Blvd.  
CLAYTON@SAFETYMINISTORAGE.COM  
F & G MECHANICAL SERVICES INC, Address:17219 BEL RAY PLACE, Phone:(816) 322-0810  
VELOCITY ELECTRIC AND AUTOMATION LLC, Address:1704 SW RED FOX CIR, Phone:(816) 215-1514  
R2 PLUMBING LLC, Address:1705 A SE COUNTY RD AA, Phone:(816) 215-8098  
MIDWEST ARCHITECTS, Address:1120 NW EAGLE RIDGE BLVD, Phone:(816) 229-8115  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 10/07/2024 09/23/2024
Joe Frogge
License Tax - Payment
Corrective Action Required
09/23/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $13,101.00 6/24/2024 - Acknowledged in letter.
Planning - Screening of ground mounted equipment
Corrective Action Required
09/23/2024

Unified Development Ordinance Article 8, Section 8.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO section. 6/25/2024 - boxwoods approvable when properly planted - to be field verified.
Alarm Plan Review Released for Construction 08/22/2024 08/21/2024
Craig Hill
Miscellaneous Correction
Corrective Action Required
08/15/2024

Corrective action: Provide storage and racking plans.
Alarm Plan Review Rejected 07/22/2024 07/22/2024
Craig Hill
Miscellaneous Correction
Corrective Action Required
07/15/2024

Corrective action: Provide storage and racking plans.
Alarm Plan Review Rejected 06/19/2024 07/03/2024
Craig Hill
Miscellaneous Correction
Corrective Action Required
07/03/2024

No alarm plans have been uploaded or found.
Building Plan Review Approved with Conditions 06/25/2024 06/25/2024
Joe Frogge
License Tax - Payment
Corrective Action Required
06/18/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $13,101.00 6/24/2024 - Acknowledged in letter.
Misc
Resolved
06/24/2024

Inadequate information to complete review. Action required: Provide complete design for floor of equipment platform.
IBC 505.3.3 - platform guards
Resolved
06/24/2024

2018 IBC 505.3.3 Guards. Equipment platforms shall have guards where required by Section 1013.2. Action required: Provide complete design of guard rail system at equipment platform.
Planning - Screening of ground mounted equipment
Corrective Action Required
06/18/2024

Unified Development Ordinance Article 8, Section 8.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO section. 6/25/2024 - boxwoods approvable when properly planted - to be field verified.
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Resolved
06/24/2024

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle near new condensing unit.
Suite address
Resolved
06/24/2024

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: Comment is informational. We have assigned the following address - 2225 NW Town Centre Blvd. 6/24/2024 - Acknowledged in letter.
Fire Plan Review Approved with Conditions 06/25/2024 06/25/2024
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
06/18/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide tenant finish alarm plans for review and approval.
Address numbers required
Resolved
06/25/2024

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). THe suite number for the space shall be posted on all exterior doors.
Construction documents - Fire protection systems
Resolved
06/25/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for review and approval.
Portable fire extinguishers - general
Corrective Action Required
06/18/2024

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide one 2A,10B,C fire extinguisher near the front door. Verified at inspection.
Miscellaneous Correction
Corrective Action Required
06/18/2024

3201.3 Construction documents. At the time of building permit application for new structures designed to accommodate high-piled storage or for requesting a change of occupancy/ use, and at the time of application for a storage permit, plans and specifications shall be submitted for review and approval. In addition to the information required by the International Building Code, the storage permit submittal shall include the information specified in this section. The construction documents shall include all of the following: 1. Floor plan of the building showing locations and dimensions of high-piled storage areas. 2. Usable storage height for each storage area. 3. Number of tiers within each rack, if applicable. 4. Commodity clearance between top of storage and the sprinkler deflector for each storage arrangement. 5. Aisle dimensions between each storage array. 6. Maximum pile volume for each storage array. 7. Location and classification of commodities in accordance with Section 3203. 8. Location of commodities that are banded or encapsulated. 9. Location of required fire department access doors. 10. Type of fire suppression and fire detection systems. 11. Location of valves controlling the water supply of ceiling and in-rack sprinklers. 12. Type, location and specifications of smoke removal and curtain board systems. 13. Dimension and location of transverse and longitudinal flue spaces. 14. Additional information regarding required design features,commodities, storage arrangement and fire protectionfeatures within the high-piled storage area shall be provided at the time of permit, where required by the fire code official. Provide a storage plan. 06/25/2024- Provide storage plan as deferred submittal. A final inspection will not be allowed until plan is reviewd and approved.
Licensed Contractors Approved 06/25/2024 06/24/2024
Joe Frogge
Sprinkler Plan Review Released for Construction 06/25/2024 06/24/2024
Craig Hill
Miscellaneous Correction
Corrective Action Required
06/24/2024

Before connecting this new area of the building a hydrostatic test will need to be performed at not less than 200 psi for 2 hours.
Fire Plan Review Rejected 06/11/2024 06/10/2024
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
06/10/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide tenant finish alarm plans for review and approval.
Address numbers required
Corrective Action Required
06/10/2024

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). THe suite number for the space shall be posted on all exterior doors.
Construction documents - Fire protection systems
Corrective Action Required
06/10/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for review and approval.
Portable fire extinguishers - general
Corrective Action Required
06/10/2024

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide one 2A,10B,C fire extinguisher near the front door. Verified at inspection.
Miscellaneous Correction
Corrective Action Required
06/10/2024

3201.3 Construction documents. At the time of building permit application for new structures designed to accommodate high-piled storage or for requesting a change of occupancy/ use, and at the time of application for a storage permit, plans and specifications shall be submitted for review and approval. In addition to the information required by the International Building Code, the storage permit submittal shall include the information specified in this section. The construction documents shall include all of the following: 1. Floor plan of the building showing locations and dimensions of high-piled storage areas. 2. Usable storage height for each storage area. 3. Number of tiers within each rack, if applicable. 4. Commodity clearance between top of storage and the sprinkler deflector for each storage arrangement. 5. Aisle dimensions between each storage array. 6. Maximum pile volume for each storage array. 7. Location and classification of commodities in accordance with Section 3203. 8. Location of commodities that are banded or encapsulated. 9. Location of required fire department access doors. 10. Type of fire suppression and fire detection systems. 11. Location of valves controlling the water supply of ceiling and in-rack sprinklers. 12. Type, location and specifications of smoke removal and curtain board systems. 13. Dimension and location of transverse and longitudinal flue spaces. 14. Additional information regarding required design features,commodities, storage arrangement and fire protectionfeatures within the high-piled storage area shall be provided at the time of permit, where required by the fire code official. Provide a storage plan.
Miscellaneous Correction
Corrective Action Required
06/10/2024

Building Plan Review Rejected 06/11/2024 06/10/2024
Joe Frogge
License Tax - Payment
Corrective Action Required
06/10/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $13,101.00
Misc
Corrective Action Required
06/10/2024

Inadequate information to complete review. Action required: Provide complete design for floor of equipment platform.
IBC 505.3.3 - platform guards
Corrective Action Required
06/10/2024

2018 IBC 505.3.3 Guards. Equipment platforms shall have guards where required by Section 1013.2. Action required: Provide complete design of guard rail system at equipment platform.
Planning - Screening of ground mounted equipment
Corrective Action Required
06/10/2024

Unified Development Ordinance Article 8, Section 8.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO section.
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
06/10/2024

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle near new condensing unit.
Suite address
Corrective Action Required
06/10/2024

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: Comment is informational. We have assigned the following address - 2225 NW Town Centre Blvd.
Licensed Contractors Approved 06/11/2024 06/10/2024
Joe Frogge
LC - General Contractor
Resolved
06/10/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact which is where inspection reports will be sent.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $1,120.00 $1,120.00 Paid 06/26/2024
7232302-Industrial/Warehouse License Tax Fee $13,101.00 $13,101.00 Paid 10/01/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rated Assembly Inspection Partial 6/27/2024 6/27/2024 06/27/2024
Misc
Informational
06/27/2024
West side demising wall framing-OK to rock wall
Underslab Plumbing Inspection - Commercial Passed 6/28/2024 06/28/2024
In-wall Inspection Failed 7/1/2024 7/1/2024 07/01/2024
Misc
Corrective Action Required
07/01/2024
Fb restroom wall from ceiling space
Electrical Service Inspection Failed 7/2/2024 7/2/2024 07/02/2024
Misc
Corrective Action Required
07/02/2024
-Remove enamel at bonding connection and tighten the screw -Isolate the feeder EGC from the grounded conductor -Too many conductors inside raceway at subpanel subjected to de-rating -Color EGC at subpanel with green tape
Gas Service Inspection - Commercial Failed 7/2/2024 7/2/2024 07/02/2024
Misc
Corrective Action Required
07/02/2024
Gas line to furnace is 1/2”, instead of 3/4” as shown on plan
Electrical Service Inspection Passed 7/3/2024 7/3/2024 07/03/2024
Misc
Resolved
07/03/2024
Rated Assembly Inspection Partial 7/8/2024 7/8/2024 07/08/2024
Misc
Informational
06/27/2024
West side demising wall framing-east side screw pattern OK **close off excessize gap at soffit
Rated Assembly Inspection Passed 7/11/2024 7/11/2024 07/11/2024
Misc
Informational
07/08/2024
West demising wall framing-screw pattern OK
Gas Service Inspection - Commercial Failed 8/1/2024 8/1/2024 08/01/2024
Misc
Corrective Action Required
07/02/2024
Gas line to furnace is 1/2”, instead of 3/4” as shown on plan **need to retest
Above Ceiling Inspection Failed 8/1/2024 8/1/2024 08/01/2024
Misc
Corrective Action Required
08/01/2024
Color tag, paint, or color tape the MC support wires
Gas Service Inspection - Commercial Passed 8/5/2024 8/5/2024 08/05/2024
Misc
Resolved
08/05/2024
Gas line to furnace is 1/2”, instead of 3/4” as shown on plan **need to retest
Above Ceiling Inspection Passed 8/5/2024 8/5/2024 08/05/2024
Misc
Resolved
08/05/2024
Color tag, paint, or color tape the MC support wires
Occupancy Inspection - Planning Passed 10/01/2024
In-wall Inspection Passed 10/01/2024
Misc
Resolved
10/01/2024
Fb restroom wall from ceiling space
Occupancy Inspection - Codes Commercial Failed 10/1/2024 10/1/2024 10/01/2024
Misc
Corrective Action Required
10/01/2024
-Fire has not approved on portal -License tax fee owe has not been paid -Move the grab bar to within 12” of wall; min 54” from wall at the other end of grab bar
Occupancy Inspection - Codes Commercial Full C of O 10/1/2024 10/1/2024 10/01/2024
Misc
Resolved
10/01/2024
-Fire has not approved on portal -License tax fee owe has not been paid -Move the grab bar to within 12” of wall; min 54” from wall at the other end of grab bar
Occupancy Inspection - Fire Passed 10/1/2024 10/1/2024 10/02/2024
Documents & Images
Date Uploaded File Type Document Name
05/30/2024 Application Form APPLICATION
05/30/2024 Plans 24_05_29 Johnson Storage Permit Submittal Reduced File Size
05/30/2024 Letter License Tax Bill
06/11/2024 Letter DS P/R Corrections Document
06/12/2024 Drawing Johnson TI FP
06/18/2024 Letter 24_06_11 Plan Review Response Letter PR20242738
06/18/2024 Drawing A-002 Revised 24_06_11
06/18/2024 Drawing A-410 Revised 24_06_11
06/18/2024 Drawing E-2 Revised 24_06_12
06/24/2024 Drawing Johnson TI FP RFC
06/24/2024 Letter Fire (Sprinkler) Plan Review
06/26/2024 Approved Plans Approved construction plans
06/26/2024 Receipt Receipt for transaction: 2024-005220
06/26/2024 Letter DS Building Permit
06/27/2024 Letter DS Building Permit
06/27/2024 Letter INSPECTION SUMMARY
06/28/2024 Letter INSPECTION SUMMARY
07/01/2024 Letter INSPECTION SUMMARY
07/02/2024 Letter INSPECTION SUMMARY
07/02/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter Fire (Alarm) Plan Review Notice
07/08/2024 Letter INSPECTION SUMMARY
07/11/2024 Letter INSPECTION SUMMARY
07/15/2024 Data Sheets
07/15/2024 Johnson TI-3 BatteryCalc_PSN-64_stamped
07/15/2024 Johnson TI-3 Fire Alarm Plans_stamped
07/22/2024 Letter Fire (Sprinkler) Plan Review
08/01/2024 Letter INSPECTION SUMMARY
08/01/2024 Letter INSPECTION SUMMARY
08/05/2024 Letter INSPECTION SUMMARY
08/05/2024 Letter INSPECTION SUMMARY
08/15/2024 Johnson BatteryCalc_PSN-106 New L Series
08/15/2024 Johnson TI-3R
09/23/2024 Engineer Report/Study 24-0917-10 JOHNSON STORAGE AND MOVING CALCS
09/23/2024 Plans 24-0917-10 JOHNSON STORAGE AND MOVING FINALS
10/01/2024 Letter INSPECTION SUMMARY
10/01/2024 Letter INSPECTION SUMMARY
10/01/2024 Letter INSPECTION SUMMARY
10/01/2024 Receipt Receipt for transaction: 2024-008045
10/01/2024 Letter Field Certificate of Occupancy
10/01/2024 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home