Permit Application Status

PRCOM20241283


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20241283
Building Permit - Commercial
Certificate of Occupancy
LANGSFORD DEVELOPMENT INC
CHANGE OF TENANT
CHANGE OF TENANT FOR NEW BUSINESS - CHANGE OF USE ONLY - NO CONSTRUCTION OTHER THAN ELECTRICAL IN PATIENT CARE AREAS
03/19/2024
03/27/2024
04/04/2024
Locations
Contacts
LANGSFORD DEVELOPMENT INC, Address:PO BOX 607  
LIV Aesthetics and Wellness, Address:618 SW 3rd Street, Suite I  
PREMIER ELECTRIC & LIGHTING DESIGN, Address:PO BOX 1311, Phone:(816) 564-7660  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved 03/29/2024 03/27/2024
Joe Frogge
Approved via field inspection by Craig Hill - JOE FROGGE 03/27/2024 4:14 PM
Building Plan Review Approved 03/29/2024 03/20/2024
Joe Frogge
Licensed Contractors Approved 03/29/2024 03/20/2024
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $50.00 $50.00 Paid 03/27/2024
$5,742.00
7232302-Commercial License Tax Fee $2,871.00 $2,871.00 Paid 03/20/2024
$2,871.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Occupancy Inspection - Fire Passed 03/27/2024
Above Ceiling Inspection Passed 03/28/2024
In-wall Inspection Passed 03/28/2024
Rough Electrical Inspection - Commercial Passed 3/28/2024 3/28/2024 03/28/2024
Final Inspection - Commercial Passed 03/28/2024
Occupancy Inspection - Codes Commercial Failed 3/28/2024 03/28/2024
Misc
Corrective Action Required
03/28/2024
-Provide all grab bars at restroom-see below -Provide open faced tiolet seat -Lavatory must be accessible- must have knee and toe clearance, plumbing protection and at max 34" from the floor -Provide accessible restroom signage on latch side of door 48" to 60" from floor -Provide lever style hardware at restroom door ***SCHEDULE RE INSPECTION AS CODES ONLY
Misc
Informational
03/28/2024
**Rear wall grab bar must be spaced no more than 6" from side wall and extend min of 42" at a height of 33"-36" from the floor **Side wall grab bar must be spaced no more than 12" from rear wall and extend to min of 54" at a height of 33"-36" from the floor **Vertical grab bar must be 39"-41" from rear wall, 39"-41" from floor and min of 18" in height
Occupancy Inspection - Codes Commercial Full C of O 4/4/2024 4/4/2024 04/04/2024
Misc
Resolved
04/04/2024
-Provide all grab bars at restroom-see below -Provide open faced tiolet seat -Lavatory must be accessible- must have knee and toe clearance, plumbing protection and at max 34" from the floor -Provide accessible restroom signage on latch side of door 48" to 60" from floor -Provide lever style hardware at restroom door ***SCHEDULE RE INSPECTION AS CODES ONLY
Misc
Resolved
04/04/2024
**Rear wall grab bar must be spaced no more than 6" from side wall and extend min of 42" at a height of 33"-36" from the floor **Side wall grab bar must be spaced no more than 12" from rear wall and extend to min of 54" at a height of 33"-36" from the floor **Vertical grab bar must be 39"-41" from rear wall, 39"-41" from floor and min of 18" in height
Documents & Images
Date Uploaded File Type Document Name
03/19/2024 Application Form APPLICATION
03/19/2024 Plans AUTOCAD LIV AESTHETICS & WELLNESS
03/20/2024 Letter License Tax Bill
03/27/2024 Approved Plans approved plans - LIV AESTHETICS & WELLNESS
03/27/2024 Receipt Receipt for transaction:2024-001966
03/27/2024 Letter DS Building Permit
03/28/2024 Letter INSPECTION SUMMARY
03/28/2024 Letter INSPECTION SUMMARY
03/28/2024 Letter INSPECTION SUMMARY
03/28/2024 Letter INSPECTION SUMMARY
03/28/2024 Letter INSPECTION SUMMARY
04/04/2024 Letter Codes Final Certificate of Occupancy
04/04/2024 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents