Summary
PRCOM20240501
Building Permit - Commercial
Certificate of Occupancy
WHEELER DEALER 17 MULTI LLC
ALTERATION COMMERCIAL
MCCARTHY JEEP - INTERIOR ALTERATIONS
02/06/2024
03/19/2024
08/26/2024
09/20/2024
Locations
Contacts
WHEELER DEALER 17 MULTI LLC, Address:50 ROCKEFELLER PLAZA 2ND FLR  
ACI Build Group, Address:4917 Woodstock Street  
Taylor Aycock/ACI Build Group, Phone:(816) 699-0855  
CRH ELECTRIC INC, Address:4020 E 137TH TER, Phone:(816) 761-1433  
PRO DESIGN CONTRACTORS LLC, Address:918 E WARREN ST, Phone:(913) 308-6900  
DAVIDSON ARCHITECTURE & ENGINEERING, Address:4301 INDIAN CREEK PKWY, Phone:(913) 451-9390  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved 03/06/2024 02/28/2024
Joe Frogge
Misc
Resolved
02/28/2024

Provide MEP designs or detailed scopes of work that include materials and methods.
Licensed Contractors Approved 02/28/2024 02/28/2024
Joe Frogge
Fire Plan Review Approved with Conditions 03/06/2024 02/28/2024
Joe Frogge
Miscellaneous Correction
Corrective Action Required
02/28/2024

Relocate alarm notification appliances as needed and provide as built plans. 2/28/2024- Acknowledged.
Miscellaneous Correction
Corrective Action Required
02/28/2024

Adjust sprinkler coverage as needed and provide as built plans. 2/28/2024- Acknowledged.
Miscellaneous Correction
Corrective Action Required
02/28/2024

Maintain a temporary fire extinguisher in the area during construction. 2/28/2024- Acknowledged.
Fire Plan Review Approved with Conditions 02/28/2024 02/27/2024
Jim Eden
Miscellaneous Correction
Corrective Action Required
02/21/2024

Relocate alarm notification appliances as needed and provide as built plans. 2/28/2024- Acknowledged.
Miscellaneous Correction
Corrective Action Required
02/21/2024

Adjust sprinkler coverage as needed and provide as built plans. 2/28/2024- Acknowledged.
Miscellaneous Correction
Corrective Action Required
02/21/2024

Maintain a temporary fire extinguisher in the area during construction. 2/28/2024- Acknowledged.
Zoning Review Approved 02/16/2024 02/23/2024
Joe Frogge
Miscellaneous Correction
Resolved
02/23/2024

The proposed ACM panels cannot be approved administratively. Metal may only be used in an incidental role i.e., trim, architectural features, standing seam metal roofing. Architectural metal siding such as the proposed AMC panels can only be approved by the Planning Commission and/or City Council through the Preliminary Development Plan Process. This process requires public hearings and will take approximately 90 days. It appears the existing building materials is limited to EFIS/stucco. Does ACM panels or metal siding currently exist on the building? Please provide additional details of the existing exterior building materials. 2/23/24 - exterior work removed from this submittal. Client has been informed of required PDP/FDP processes.
Building Plan Review Rejected 02/28/2024 02/23/2024
Joe Frogge
IBC 602.1 Type of Construction - general
Resolved
02/23/2024

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Amend Code Synopsis to show correct construction type which is 3B.
ICC A117.1 904.3 Sales and Service Counters
Resolved
02/23/2024

ICC A117.1 Section 904.3 Sales and service counters and windows. Sales and service counters and windows shall comply with Section 904.3.1 and either 904.3.2 or 904.3.3. Where counters are provided, the accessible portion of the countertop shall extend the same depth as the public portion of the sales and service countertop provided for standing customers. (see code for exception) 904.3.1 Vertical barriers. At service windows or service counters, any vertical barrier between service personnel and customers shall be at a height of 43 inches maximum above the floor. (see code for exception regarding security glazing) 904.3.2 Parallel Approach. A portion of the public use side of the counter surface 36 inches minimum in length and 26 inches minimum and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a parallel approach adjacent to the accessible counter shall be provided. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12 inches minimum. (see code for exception) 904.3.3 Forward Approach. A portion of the public use side of the counter surface 30 inches minimum in length and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a forward approach to the accessible counter shall be provided. Knee and toe clearance complying with Section 306 shall be provided under the accessible counter. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12” minimum. Action required: Modify design of detail 8/A1.1 to demonstrate compliance.
Misc
Corrective Action Required
02/21/2024

Provide MEP designs or detailed scopes of work that include materials and methods.
Licensed Contractors Approved 02/28/2024 02/23/2024
Joe Frogge
LC - General Contractor
Resolved
02/23/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Resolved
02/23/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Zoning Review Rejected 02/16/2024 02/18/2024
Shannon McGuire
Miscellaneous Correction
Corrective Action Required
02/18/2024

The proposed ACM panels cannot be approved administratively. Metal may only be used in an incidental role i.e., trim, architectural features, standing seam metal roofing. Architectural metal siding such as the proposed AMC panels can only be approved by the Planning Commission and/or City Council through the Preliminary Development Plan Process. This process requires public hearings and will take approximately 90 days. It appears the existing building materials is limited to EFIS/stucco. Does ACM panels or metal siding currently exist on the building? Please provide additional details of the existing exterior building materials.
Building Plan Review Rejected 02/16/2024 02/16/2024
Joe Frogge
IBC 602.1 Type of Construction - general
Corrective Action Required
02/16/2024

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Amend Code Synopsis to show correct construction type which is 3B.
ICC A117.1 904.3 Sales and Service Counters
Corrective Action Required
02/16/2024

ICC A117.1 Section 904.3 Sales and service counters and windows. Sales and service counters and windows shall comply with Section 904.3.1 and either 904.3.2 or 904.3.3. Where counters are provided, the accessible portion of the countertop shall extend the same depth as the public portion of the sales and service countertop provided for standing customers. (see code for exception) 904.3.1 Vertical barriers. At service windows or service counters, any vertical barrier between service personnel and customers shall be at a height of 43 inches maximum above the floor. (see code for exception regarding security glazing) 904.3.2 Parallel Approach. A portion of the public use side of the counter surface 36 inches minimum in length and 26 inches minimum and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a parallel approach adjacent to the accessible counter shall be provided. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12 inches minimum. (see code for exception) 904.3.3 Forward Approach. A portion of the public use side of the counter surface 30 inches minimum in length and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a forward approach to the accessible counter shall be provided. Knee and toe clearance complying with Section 306 shall be provided under the accessible counter. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12” minimum. Action required: Modify design of detail 8/A1.1 to demonstrate compliance.
Misc
Corrective Action Required
02/16/2024

Provide MEP designs or detailed scopes of work that include materials and methods.
Licensed Contractors Rejected 02/16/2024 02/16/2024
Joe Frogge
LC - General Contractor
Corrective Action Required
02/16/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
02/16/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 02/16/2024 02/15/2024
Jim Eden
Miscellaneous Correction
Corrective Action Required
02/15/2024

Relocate alarm notification appliances as needed and provide as built plans.
Miscellaneous Correction
Corrective Action Required
02/15/2024

Adjust sprinkler coverage as needed and provide as built plans.
Miscellaneous Correction
Corrective Action Required
02/15/2024

Maintain a temporary fire extinguisher in the area during construction.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $1,126.06 $1,126.06 Paid 03/05/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Occupancy Inspection - Fire Pending 9/20/2024 9/20/2024
Rough Electrical Inspection - Commercial Passed 4/22/2024 04/22/2024
In-wall Inspection Passed 4/22/2024 04/22/2024
Final Plumbing Inspection - Commercial Passed 9/20/2024 09/20/2024
Above Ceiling Inspection Passed 9/20/2024 09/20/2024
Final Electrical Inspection - Commercial Passed 9/20/2024 09/20/2024
Occupancy Inspection - Codes Commercial Full C of O 9/20/2024 9/20/2024 09/20/2024
Documents & Images
Date Uploaded File Type Document Name
02/06/2024 Scope of Work SCOPE OF WORK
02/07/2024 Plans 23164 Permit Set 2023-12-15
02/20/2024 Letter DS P/R Corrections Document
02/21/2024 Letter PRCOM20240501 Response to City Comments 2024-02-20
02/21/2024 Plans 23164 Permit Set R1 2024-02-21
02/28/2024 Letter DS P/R Corrections Document
02/28/2024 Letter PRCOM20240501 Response to City Comments 2024-02-28
02/28/2024 Approved Plans approved - 23164 Permit Set R1 2024-02-21
03/05/2024 Receipt Receipt for transaction:2024-001332
04/22/2024 Letter INSPECTION SUMMARY
04/22/2024 Letter INSPECTION SUMMARY
09/09/2024 Letter Codes 140 Day Letter
09/20/2024 Letter INSPECTION SUMMARY
09/20/2024 Letter INSPECTION SUMMARY
09/20/2024 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.