Permit Application Status

PRCOM20233906


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20233906
Building Permit - Commercial
Certificate of Occupancy
MONTE CRISTO II LLC
CHANGE OF TENANT
CHANGE OF TENANT FOR PRIVATE REHAB COUNSELING FACILITY
08/10/2023
09/29/2023
01/24/2024
Locations
Contacts
KD CHRISTIAN CONSTRUCTION CO, Address:7387 W 162ND ST, Phone:(913) 451-0466  
KDSM, Inc., Address:1101 Guinotte Avenue  
ELECTRIC ONE LLC, Address:7312 N ANTIOCH RD, Phone:(816) 437-9312  
MONTE CRISTO II LLC, Address:PO BOX 11250  
John Johnson - KD Christian Construction, Phone:(816) 589-3442  
[K] WARMAN ARCHITECTS, Address:1828 SWIFT, SUITE 101, Phone:(816) 474-2233  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 10/18/2023
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
10/18/2023

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received 10/17/2023.
Installation acceptance testing
Corrective Action Required
10/18/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. A visual inspection will be conducted at the occupancy inspection.
Alarm Plan Review Released for Construction 10/19/2023 10/18/2023
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
10/18/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Received 10/5/2023.
Installation acceptance testing
Corrective Action Required
10/18/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Test at occupancy inspection. Schedule before regular hours of the attached tenant.
Licensed Contractors Approved 08/22/2023 09/29/2023
Joe Frogge
LC - General Contractor
Resolved
09/27/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent. 9/27/23 - Electric One not currently licensed with us.
LC - MEP Subs
Resolved
09/29/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 08/22/2023 08/22/2023
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
08/22/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide as built plans for adjustments to notification appliances, if needed.
Construction documents - Fire protection systems
Corrective Action Required
08/22/2023

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for review and approval.
Portable fire extinguishers - general
Corrective Action Required
08/22/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Existing fire extinguishers verified at time of inspection. Add additional if needed.
MISC
Corrective Action Required
08/22/2023

All existing conditions i.e. exit and emergency lighting will be inspected at occupancy inspection..
Address numbers required
Corrective Action Required
08/22/2023

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide address on the rear door. Verified at inspection.
Building Plan Review Approved 08/22/2023 08/17/2023
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $940.00 $940.00 Paid 09/29/2023
$13,596.00
7232302-Commercial Excise Tax Fee $6,798.00 $6,798.00 Paid 08/10/2023
$6,798.00
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 12/28/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 10/25/2023 10/25/2023 10/25/2023
Above Ceiling Inspection Failed 11/29/2023 11/29/2023
Misc
Corrective Action Required
11/29/2023
-All materials within plenum space shall be non-combustible or shall have flame spread index not more than 25 and smoke develop index not more than 50. (Wood sheathing, plastic tubing, etc). Exceptions: IMC 602.2.1 -All low-voltage cables within plenum space shall be plenum-rated -Support MC cable to wire with a listed device -Support low-voltage cables off ceiling grid in a workmanlike manner -Complete supply air ceiling registers -Support flexible duct off ceiling grids every 5 ft or less with min 1.5” straps -Secure MC cables within 12” of j-boxes; support MC at max 6 ft intervals
Above Ceiling Inspection Passed 12/11/2023 12/11/2023 12/11/2023
Misc
Informational
12/11/2023
Existing non-compliance: materials within plenum space (Wood sheathing, plastic tubing, etc) not meeting requirement of flame spread index not more than 25 and smoke develop index not more than 50. -All new low-voltage cables within plenum space shall be plenum-rated
Alarm Test Passed 12/15/2023
Occupancy Inspection - Codes Commercial Ready for Temp CO 12/22/2023 12/22/2023
Misc
Corrective Action Required
12/22/2023
-Complete exterior door at back side
Occupancy Inspection - Fire Passed 12/22/2023 12/22/2023
Occupancy Inspection - Codes Commercial Full C of O 1/24/2024 1/24/2024 01/24/2024
Misc
Resolved
01/24/2024
-Complete exterior door at back side
Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home