Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Plan Review
|
Approved with Conditions
|
06/30/2023
|
06/30/2023
|
|
Jim Eden
|
|
Miscellaneous Correction
Provide a scope of work,intended use, floor plans, MEP's, and updated code analysis. The information provided is insufficient to complete a review.
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide shop drawings for modifications to the existing sprinkler system. Submit plans to devservices.cityofls.net
|
|
Portable fire extinguishers - general
Corrective Action Required
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Verified at inspection.
|
|
Misc
Corrective Action Required
All existing conditions subject to inspection and correction to meet requirements for the change in use.
|
|
Construction documents for fire alarm systems
Corrective Action Required
2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Provide plans for modications to notification appliances.
|
|
|
Building Plan Review
|
Approved
|
06/30/2023
|
06/23/2023
|
|
Joe Frogge
|
|
IBC 1004.1 Design occupant load
2018 IBC 1004.1 Design occupant load. In determining means of egress requirements, the number of occupants for whom means of egress facilities shall be provided shall be determined in accordance with this section.
Action required: Provided detailed breakdown of each area and assign occupant loads per table 1004.5.
|
|
Misc
Inadequate information to complete review.
Action required: Provide complete MEP designs or detailed scopes of work per trade.
|
|
IPC 403.1 Minimum number of fixtures
2018 IPC 403.1 Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code.
Action required: Provide drinking fountains or approved equivalent.
|
|
Misc
To avoid confusion, remove historic code analysis.
|
|
|
Licensed Contractors
|
Approved
|
06/23/2023
|
06/23/2023
|
|
Joe Frogge
|
|
LC - General Contractor
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Provide an email address & phone number for the on-site contact which is where inspection reports will be sent.
|
|
LC - MEP Subs
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
|
|
|
Fire Plan Review
|
Rejected
|
06/12/2023
|
06/12/2023
|
|
Jim Eden
|
|
Miscellaneous Correction
Corrective Action Required
Provide a scope of work,intended use, floor plans, MEP's, and updated code analysis. The information provided is insufficient to complete a review.
|
|
|
Building Plan Review
|
Rejected
|
06/12/2023
|
06/11/2023
|
|
Joe Frogge
|
|
IBC 1004.1 Design occupant load
Corrective Action Required
2018 IBC 1004.1 Design occupant load. In determining means of egress requirements, the number of occupants for whom means of egress facilities shall be provided shall be determined in accordance with this section.
Action required: Provided detailed breakdown of each area and assign occupant loads per table 1004.5.
|
|
Misc
Corrective Action Required
Inadequate information to complete review.
Action required: Provide complete MEP designs or detailed scopes of work per trade.
|
|
IPC 403.1 Minimum number of fixtures
Corrective Action Required
2018 IPC 403.1 Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code.
Action required: Provide drinking fountains or approved equivalent.
|
|
Misc
Corrective Action Required
To avoid confusion, remove historic code analysis.
|
|
|
Licensed Contractors
|
Rejected
|
|
06/11/2023
|
|
Joe Frogge
|
|
LC - General Contractor
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Provide an email address & phone number for the on-site contact which is where inspection reports will be sent.
|
|
LC - MEP Subs
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
|
|
|
Zoning Review
|
Approved
|
06/01/2023
|
05/31/2023
|
|
Joe Frogge
|
|
see email from Shannon
|