Permit Application Status

PRCOM20231559


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20231559
Building Permit - Commercial
Certificate of Occupancy
MMPF III LEES SUMMIT MO LLC
NEW TENANT FINISH
Expansion of existing orthopedics office into adjacent unoccupied shell space
04/11/2023
07/28/2023
01/25/2024
Locations
Contacts
MMPF III LEES SUMMIT MO LLC, Address:3807 CLEGHORN AVE STE 903  
EXCEL CONSTRUCTORS, INC, Address:8041 W 47TH ST, Phone:(913) 261-1000  
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
EDWARDS MCDOWELL INC, Address:400 E 10TH AVE, Phone:(816) 221-7878  
KASA ELECTRIC LLC, Address:1206 NW VALLEY RIDGE DR, Phone:(816) 228-4886  
FIVE STAR MECHANICAL CONTRACT INC, Address:P O BOX 11964, Phone:(816) 358-4444  
jon.tippie@excelconstructors.com, Address:jon.tippie@excelconstructors.com  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 09/27/2023 09/26/2023
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
09/26/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Stamped plans received 9/13/2023.
Installation acceptance testing
Corrective Action Required
09/26/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
Licensed Contractors Approved 04/21/2023 07/28/2023
Joe Frogge
LC - General Contractor
Resolved
07/28/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Provide an email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Resolved
07/28/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 04/21/2023 04/20/2023
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
04/20/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required- Provide shop drawings for review and approval of new and relocated alarm notification appliances.
Construction documents - Fire protection systems
Corrective Action Required
04/20/2023

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for review and approval for sprinkler alterations needed to maintain coverage. Upload to devservices.cityofls.net .
Portable fire extinguishers - general
Corrective Action Required
04/20/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required- Confirm there is a new or existing fire extinguisher within a 75 foot travel distance of anywhere in the new space. Verified at inspection.
Building Plan Review Approved 04/21/2023 04/17/2023
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $500.00 $500.00 Paid 07/28/2023
7232302-Commercial Excise Tax Fee $4,521.00 $4,521.00 Paid 06/05/2023
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 11/30/2023
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 12/01/2023
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 01/11/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 9/28/2023 09/28/2023
Misc
Corrective Action Required
09/28/2023
Partial in-wall-OK to cover below: -rm 200.29-30; 200.35-36
In-wall Inspection Partial 10/11/2023 10/11/2023 10/11/2023
Misc
Corrective Action Required
09/28/2023
Partial in-wall-OK to cover below: -rm 200.29-30; 200.32-33; 200.35-36
Above Ceiling Inspection Partial 10/26/2023 10/26/2023 10/26/2023
Misc
Informational
10/26/2023
Above-ceiling OK: -200.30; 200.32-36 **Support ceiling grid outside X-ray rm
In-wall Inspection Passed 10/31/2023
Misc
Resolved
10/31/2023
Partial in-wall-OK to cover below: -rm 200.29-30; 200.32-33; 200.35-36
Occupancy Inspection - Codes Commercial Ready for Temp CO 10/31/2023 10/31/2023 10/31/2023
Misc
Corrective Action Required
10/31/2023
-All receptacles in 200.29 where located within 6 ft of the sinks must be gfci-protected -Physical therapy rm 200.37 and X ray rm 200.31 not completed **Sinks in rm exam 11 and 200.39 omitted **OK to occupy rooms 200.30-200.36
Alarm Test Passed 10/31/2023
Occupancy Inspection - Fire Passed 10/31/2023 10/31/2023 10/31/2023
Occupancy Inspection - Codes Commercial Ready for Temp CO 11/30/2023 11/30/2023
Misc
Corrective Action Required
10/31/2023
-All receptacles in 200.29 where located within 6 ft of the sinks must be gfci-protected -Physical therapy rm 200.37 and X ray rm 200.31 not completed **Sinks in rm exam 11 and 200.39 omitted **OK to occupy rooms 200.30-200.36
In-wall Inspection Passed 12/8/2023 12/8/2023 12/08/2023
Misc
Informational
12/08/2023
x-ray rm OK to rock
Above Ceiling Inspection Passed 1/3/2024 1/3/2024 01/03/2024
Misc
Resolved
01/03/2024
Above-ceiling OK: -200.30; 200.32-36, x-ray
Occupancy Inspection - Codes Commercial Ready for Temp CO 1/11/2024 01/11/2024
Misc
Corrective Action Required
11/30/2023
-All receptacles in 200.29 where located within 6 ft of the sinks must be gfci-protected -Physical therapy rm 200.37 and X ray rm 200.31 not completed **Sinks in rm exam 11 and 200.39 omitted **OK to occupy rooms 200.30-200.36
Occupancy Inspection - Codes Commercial Full C of O 1/25/2024 1/25/2024 01/25/2024
Misc
Resolved
01/25/2024
-All receptacles in 200.29 where located within 6 ft of the sinks must be gfci-protected -Physical therapy rm 200.37 and X ray rm 200.31 not completed **Sinks in rm exam 11 and 200.39 omitted **OK to occupy rooms 200.30-200.36
Documents & Images
Date Uploaded File Type Document Name
04/11/2023 Application Form Sano Commercial Permit Application
04/11/2023 Plans SANO CD-set 04-07-2023
04/11/2023 Letter License Tax Bill
06/05/2023 Receipt Receipt for transaction: 2023-003972
07/28/2023 Approved Plans approved - SANO CD-set 04-07-2023
07/28/2023 Receipt Receipt for transaction:2023-005862
07/28/2023 Letter DS Building Permit
09/13/2023 SANO FA Plans 8-29-2023
09/13/2023 SANO FA Submittal
09/26/2023 Letter Fire (Alarm) Plan Review Notice
09/26/2023 SANO FA Plans 8-29-2023
09/28/2023 Letter Fire Building Plan Review
09/28/2023 Letter INSPECTION SUMMARY
10/11/2023 Letter INSPECTION SUMMARY
10/26/2023 Letter INSPECTION SUMMARY
10/31/2023 Letter INSPECTION SUMMARY
11/30/2023 Certificate/License Codes Temporary Certificate of Occupancy
11/30/2023 Receipt Receipt for transaction:2023-008810
12/01/2023 Certificate/License Codes Temporary Certificate of Occupancy
12/01/2023 Receipt Receipt for transaction:2023-008814
12/08/2023 Letter INSPECTION SUMMARY
01/03/2024 Letter INSPECTION SUMMARY
01/03/2024 Letter INSPECTION SUMMARY
01/11/2024 Certificate/License Codes Temporary Certificate of Occupancy
01/11/2024 Receipt Receipt for transaction:2024-000195
01/25/2024 Letter Field Certificate of Occupancy
01/25/2024 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home